The status texts for the values “0” and “1” can be edited in the
Inactive text
and
Active text
input
fields. For this object type, BACnet allows a “change-of-state counter” to be activated. The object is
automatically extended to all object properties necessary for this purpose. This also applies for the
“elapsed active timer” (operating seconds counter). BACnet alarming is activated for this object with
“intrinsic reporting”. The “time delay” property determines the report delay in seconds. All further
information can be taken from the BACnet standard.
Using the Trend button, you can create a new Trendlog object with this object as the input
reference in another dialog.
6.4.5
BACnet > Files
The entire BACnet configuration is saved in three files:
bac1.cfg
(driver);
bac1.txt
(data points);
dispatch.txt
(global dispatch file)