Device instance:
Defines the device instance number of the gateway, which has to be unique within the overall
BACnet network. The value range of this property is between 0 and 4,194,302.
Device name:
Defines the UGW device name, which also must be unique.
Description:
Defines the BACnet description of the UGW. This is free descriptive text.
Location:
Defines the BACnet location of the UGW. This is free text for the installation location.
Vendor identifier:
Manufacturer ID for unique identification of the device manufacturer
Vendor name:
Manufacturer name as unique designation of the device manufacturer
Model name:
Model description of the UGW.
Firmware revision:
Firmware version of the UGW software
APDU max length accepted:
Maximum telegram size in bytes
The following values are possible: 50, 206, 480, 1024 and 1476 bytes.
ADPU timeout:
This value in milliseconds defines the period of time after which a telegram that requires confirmation
is deemed to have failed in the absence of confirmation. The default value is 3000 ms.
APDU retries:
This value defines how often a failed telegram is to be repeated (default = 5).
APDU segmentation supported:
Possible values: 0-both, 1-transmit, 2-receive, 3-no