background image

20

Natural Gas  Minimum: 4.5" w.c. Maximum: 10.0" w.c.

INLET GAS SUPPLY PRESSURE

Table 9

9.  Turn OFF all electrical power and gas supply to the 

system.

10. Remove the manometer hose from the hose barb fitting 

or inlet pressure Tap.

11. Replace inlet pressure tap:

a.  White-Rodgers valve:

 

Turn inlet pressure test screw in to seal pressure port 

(clockwise, 7 in-lb minimum).

12. Retest for leaks. If bubbles form, shut down gas and   

repair leaks immediately.

13.  If there are no leaks, turn ON electrical power and gas 

supply to the system.

14. Turn valve switch ON.

 

NOTE:

 If measuring gas pressure at the drip leg, a 

field-supplied hose barb fitting must be installed prior to 

making the hose connection. If using the inlet pressure 

Tap on the White-Rodgers gas valve, then use the 

36G/J Valve Pressure Check Kit, Goodman Part No. 

0151K00000S.



.

Measuring Inlet Gas Pressure (Alt. Method)

Figure 11 

Gas Manifold Pressure Measurement and 

Adjustment

T

O

 

PREVENT

 

UNRELIABLE

 

OPERATION

 

OR

 

EQUIPMENT

 

DAMAGE

THE

 

GAS

 

MANIFOLD

 

PRESSURE

 

MUST

 

BE

 

AS

 

SPECIFIED

 

ON

 

THE

 

UNIT

 

RATING

 

PLATE

. O

NLY

 

MINOR

 

ADJUSTMENTS

 

SHOULD

 

BE

 

MADE

 

BY

 

ADJUSTING

 

THE

 

GAS

 

VALVE

 

PRESSURE

 

REGULATOR

.

CAUTION

Only small variations in gas pressure should be made by 

adjusting the gas valve pressure regulator. The manifold 

pressure must be measured with the burners operating. To 

measure and adjust the manifold pressure, use the following 

procedure.

1.  Turn  OFF  gas  to  furnace  at  the  manual  gas  shutoff 

valve external to the furnace.

2.  Turn OFF all electrical power to the system.

3.  Outlet pressure tap connections:

a.  White-Rodgers  valve:

 

Back outlet pressure test screw (outlet pressure Tap) 

out one turn (counterclockwise, not more than one 

turn).

4.  Connect calibrated manometer (or appropriate pressure 

gauge) at the gas valve outlet pressure tap. See White-

Rodgers 36J22Y-204 gas valve Figure 13 for location 

of outlet pressure tap.

5.  Turn ON the gas supply.

6.  Turn ON power and close thermostat “R” and “W” 

contacts to provide a call for heat.

7.  Using a leak detection solution or soap suds, check 

for leaks at outlet pressure Tap screw (White-Rodgers 

valve). Bubbles forming indicate a leak. SHUT OFF 

GAS AND REPAIR ALL LEAKS IMMEDIATELY!

8.  Measure the gas manifold pressure with burners firing. 

Adjust manifold pressure using the following

 Manifold 

Gas Pressure 

table.

Natural Gas

2.8" - 3.2" w.c.

Manifold Gas Pressure

Table 10

9.  Remove regulator cover screw from the outlet pressure 

regulator and turn screw clockwise to increase pressure 

or counterclockwise to decrease pressure. Replace 

regulator cover screw.

10. Turn OFF all electrical power and gas supply to the 

system.

11. Remove the manometer hose from the hose barb fitting 

or outlet pressure Tap.

12. Replace outlet pressure tap:

a.  White-Rodgers valve: Turn outlet pressure test screw 

in to  seal pressure port (clockwise, 7 in-lb minimum).

13. Turn ON electrical power and gas supply to the system.

14. Close thermostat contacts to provide a call for heat.

15. Retest for leaks. If bubbles form, SHUT OFF GAS AND 

REPAIR ALL LEAKS IMMEDIATELY!

Gas Input Rate Measurement (Natural Gas 

Only)

The gas input rate to the furnace must never be greater than 

that specified on the unit rating plate.  To measure natural 

gas input using the gas meter, use the following procedure.

1.  Turn OFF the gas supply to all other gas-burning 

appliances except the furnace.

2.   While the furnace is operating at high fire rate, time 

and record one complete revolution of the gas meter 

dial, measuring the smallest quantity, usually the dial 

that indicates 1/2 cu. ft. per revolution. You will use this 

number to calculate the quantity of gas in cubic ft. if the 

furnace would consume if it ran steadily for one hour 

Содержание Amana M9S80-U Series

Страница 1: ...stat Location 9 COMBUSTION AND VENTILATION AIR REQUIREMENTS 10 CATEGORY I VENTING VERTICAL VENTING 10 MASONRY CHIMNEYS 11 Masonry Chimney Termination 11 ELECTRICAL CONNECTIONS 11 Wiring Harness 11 120...

Страница 2: ...peed Selection 22 Heat Pump Heating Mode Speed Slection 22 Circulator Blower Fan Timing Adjustment 23 On Off Fan Delay Selection 23 OPERATIONAL CHECKS 23 Checking Duct Static 23 SAFETY CIRCUIT DESCRIP...

Страница 3: ...ce qui peut entra ner la mort des blessures ou des dommages mat riels IF THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL I...

Страница 4: ...nt pas suivies pour chacun des appareils raccord s au syst me de ventilation au moment de sa mise en marche cela peut entra ner une intoxication au monoxyde de carbone ou la mort Les tapes suivantes d...

Страница 5: ...ing precautions during furnace installation and servicing to protect the integrated control module from damage By putting the furnace the control and the person at the same electrostatic potential the...

Страница 6: ...furnace A return air temperature range between 60 F 16 C and 80 F 27 C is maintained Air filters are installed in the system and replaced daily during construction and upon completion of construction...

Страница 7: ...icals halogen type refrigerants printing inks cleaning solutions such as perchloroethylene paint removers varnishes hydrochloric acid cements and glues antistatic fabric softeners for clothes dryers m...

Страница 8: ...gas electrical and drain line connections NOTE In addition to the required clearances to combustible materials a minimum of 24 service clearance must be available in front of the unit Installation Po...

Страница 9: ...ndition c In so far as practical close all building doors and windows and all doors between the space in which the appliance s connected to the venting system are located and other spaces of the build...

Страница 10: ...oset or utility room must have two ventilation openings with a total minimum free area of 0 25 square inches per 1 000 BTU hr of furnace input rating Refer to Specification Sheet applicable to your mo...

Страница 11: ...ation purposes Refer to the wiring diagram for wire routings If any of the original wire as supplied with the furnace must be replaced it must be replaced with wiring material having a temperature rat...

Страница 12: ...NG OR CHANGING ANY ELECTRICAL WIRING WARNING 4 Attach the junction box to the left side of the fur nace using the screws removed in step 2 5 Check the location of the wiring Confirm that it will not b...

Страница 13: ...e is equipped with de di cated inch EAC and HUM relay terminals for controlling external power to an optional field supplied humidifier and or electronic air cleaner Additional line voltage wiring to...

Страница 14: ...90 170 350 530 90 40 84 160 320 490 100 38 79 150 305 460 Pressure 0 5 psig or less and pressure drop of 0 3 W C Based on 0 60 Specific Gravity Gas CFH BTUH Furnace Input Heating Value of Gas BTU Cubi...

Страница 15: ...he furnace should be installed in parallel with or on the upstream side of the cooling unit to avoid condensa tion in the heating element With a parallel flow arrange ment the dampers or other means u...

Страница 16: ...thermostat contacts close initiating a call for heat The control will display heat mode in status menu g h Integrated control module performs safety circuit checks Induced draft blower is energized fo...

Страница 17: ...od The electronic air cleaner EAC and humidifier HUM relays will close the contacts After the thermostat is satisfied the compressor is de energized and the electronic air cleaner EAC and humidifier H...

Страница 18: ...The control is now ready to receive demands from the room thermostat Refer to Status Menu in this manual for interpretation of items displayed in the status menu Quick Start Initial set up of outdoor...

Страница 19: ...irculation blower will shut down when the time delay expires Time delay is selectable on all models 2 Turn off the electrical power supply to the furnace 3 Remove the burner compartment door 4 White R...

Страница 20: ...re gauge at the gas valve outlet pressure tap See White Rodgers 36J22Y 204 gas valve Figure 13 for location of outlet pressure tap 5 Turn ON the gas supply 6 Turn ON power and close thermostat R and W...

Страница 21: ...the supply air temperature to determine the air temperature rise Allow adequate time for thermometer readings to stabilize 4 Adjust temperature rise by adjusting the circulator blower speed Increase...

Страница 22: ...Cooling Speed Table Gas Heating Mode Speed Selection To change the main blower speed in GAS HEATING mode see the following steps 1 Press menu button until LED displays gAF Press option button and LED...

Страница 23: ...ic refers to everything external to the furnace cabinet Cooling coils filters ducts grilles registers must all be considered when reading your total external static pressure The supply duct pressure m...

Страница 24: ...horizontal right and horizontal left installations Regardless of airflow direction it does not need to be relocated Burner Temperature Switch The burner temperature switch is mounted on the burner ass...

Страница 25: ...lubricated by the manufacturer No further lubrication is required Check motor windings for accumulation of dust which may cause overheating Clean as necessary Flame Sensor Qualified Servicer Only Und...

Страница 26: ...ailable from your distributor Functional Parts List Gas Valve Natural Gas Orifice Burner Assembly Hot Surface Igniter Flame Sensor Gas Manifold Ignition Control Blower Mounting Bracket Pressure Sensor...

Страница 27: ...ntegrated Control Module 10 Transformer 11 Blower Door Interlock Switch 12 Circulator Blower Tubular Heat Exchanger Pressure Sensor Assembly Flue Pipe Connection Gas Line Entrance Gas Valve Inducer Ga...

Страница 28: ...o call for heat Correct short at flame sensor or in flame sensor wiring Short to ground in flame sense circuit Lingering burner flame Slow closing gas valve Open fuse Replace fuse Short in low voltage...

Страница 29: ...sor and pressure switch Check Red Black Green harness connections to pressure sensor control board Replace pressure sensor Check Red Black Green harness connections to pressure sensor control board Re...

Страница 30: ...72 1353 1325 1291 1255 1219 SP6 1528 1485 1438 1409 1383 1349 1317 1285 SP7 1619 1579 1551 1523 1495 1463 1430 1402 SP8 1746 1697 1667 1642 1617 1593 1570 1540 SP9 1772 1735 1698 1674 1645 1622 1598 1...

Страница 31: ...1485 30 1438 31 1409 32 1383 32 1349 1317 1285 SP7 1619 27 1579 28 1551 29 1523 29 1495 30 1463 1430 1402 SP8 1746 25 1697 26 1667 27 1642 27 1617 27 1593 1570 1540 SP9 1772 25 1735 26 1698 26 1674 27...

Страница 32: ...9 R233 R243 R245 NTC1 R209 R212 R215 R219 R227 R231 R248 R261 R208 R283 R61 R86 R87 R103 R107 R141 R203 Y1 Y2 R76 R238 R262 R8 R40 R44 R45 R46 R55 R70 R74 R75 R81 CR1 CR8 CR11 CR12 C R15 CR16 CR2 0 CR...

Страница 33: ...lta T Difference between Supply and Return Temperatures DB F GAS PRESSURES Gas Inlet Pressure IN W C Gas Manifold Pressure Low Fire IN W C Gas Manifold Pressure High Fire IN W C Gas Type NG Natural Ga...

Страница 34: ...34 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 35: ...35 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 36: ...rchased to be directed to the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the...

Отзывы: