9

7.  Test for spillage from draft hood appliances at the draft 

hood relief opening after 5 minutes of main burner 

operation. Use the flame of a match or candle. 

8.  If improper venting is observed during any of the 

above tests, the venting system must be corrected in 

accordance with the National Fuel Gas Code ANSI 

Z223.1/NFPA 54 and/or National Gas and Propane 

Installation Code CSA B149.1-15. 

9.  After it has been determined that each appliance con-

nected to the venting system properly vents when test-

ed as outlined above, return doors, windows, exhaust 

fans, fireplace dampers and any other gas burning 

appliance to their previous conditions of use.  

WARNING

Risque D’intoxication Au Monoxyde de Carbone

Si  les  יtapes  dיcrites  ci-dessous  ne  sont  pas  suivies  pour 

chacun des appareils raccordיs au systטme de ventilation

au moment de sa mise en marche, cela peut entraמner une 

intoxication au monoxyde de carbone ou la mort. Les

יtapes suivantes doivent ךtre suivies pour chacun des appa

-

reils raccordיs au systטme de ventilation au moment

de sa mise en marche, alors que tous les autres appareils 

raccordיs au systטme de ventilation ne sont pas en

marche : 

1. 

Sceller toutes les ouvertures inutilisיes du systטme de 

ventilation. 

2. 

Inspecter le systטme de ventilation afin de vיrifier 

si la taille et l’inclinaison par rapport א l’horizontale 

sont conformes aux exigences du National Fuel Gas 

Code, ANSI Z223.1/NFPA 54 ou du Code d’installation 

du gaz naturel et du propane, CSA B149.1 et א ces 

instructions. Vיrifier qu’il n’y a pas d’obstruction ou de 

restriction, de fuite, de corrosion et d’autres problטmes 

qui pourraient entraמner une situation dangereuse.

3. 

Si possible, fermer toutes les portes et fenךtres du bג

timent ainsi que toutes les portes sיparant l’endroit o

ש se trouvent les appareils raccordיs au systטme de 

ventilation et les autres zones du bגtiment.  

4.  Fermer le registre des foyers.

5. 

Mettre les sיcheuses en marche ainsi que tous les 

autres appareils qui ne sont pas raccordיs au systטme 

de ventilation. Mettre en marche tous les ventilateurs 

de tirage, comme celui des hottes de cuisine et des 

salles de bains, et les rיgler א la puissance maximale. 

Ne pas mettre en marche les ventilateurs d’יtי.

6.  Suivre les instructions d’allumage. Mettre en marche 

l’appareil soumis א l’inspection. Rיgler le thermostat de 

maniטre א ce que l’appareil fonctionne en continu.

7. 

Vיrifier la prיsence de fuite au niveau de l’ouverture du 

coupe-tirage des appareils qui en sont dotיs aprטs 5 

minutes de fonctionnement du br leur 

principal. Utiliser 

la flamme d’une allumette ou d’une bougie.

8. 

Si un problטme de ventilation est observי pendant l’un 

des essais dיcrits ci-dessus, des correctifs doivent ך

tre apportיs au systטme de ventilation conformיment 

au National Fuel Gas Code, ANSI Z223.1/NFPA 54 et 

(ou) au National Fuel Gas Code, ANSI Z223.1/NFPA 

54 et (ou) au Code d’installation du gaz naturel et du 

propane, CSA B149.1

9. 

AUne fois qu’il a יtי dיterminי que chaque appareil 

raccordי au systטme de ventilation fonctionne cor

-

rectement au moyen des essais dיcrits ci-dessus, les 

portes, les fenךtres, les ventilateurs, les registres de 

foyer et tous les autres appareils de combustion ali-

mentיs au gaz doivent ךtre remis dans leur יtat initial.

Thermostat Location

In an area having good air circulation, locate the thermostat  

about  five  feet  high  on  a  vibration-free  inside  wall.  Do  not 

install the thermostat where it may be influenced by any of 

the following:

•  Drafts, or dead spots behind doors, in corners, or 

under cabinets.

•  Hot or cold air from registers.

•  Radiant heat from the sun.

• 

Light fixtures or other appliances.

• 

Radiant heat from a fireplace.

•  Concealed hot or cold water pipes, or chimneys.

• 

Unconditioned areas behind the thermostat, such as 

an outside wall.

Consult the instructions packaged with the thermostat for 

mounting instructions and further precautions.

COMBUSTION AND VENTILATION 

REQUIREMENTS

WARNING

To avoid property damage, personal injury or death, 

sufficient fresh air proper combustion and ventilation of 

flue gases must be supplied. Most homes require outside air 

be supplied into the furnace area.

Improved construction and additional insulation in buildings 

have reduced heat loss by reducing air infiltration and escape 

around doors and windows. These changes have helped in 

reducing heating/cooling costs but have created a problem 

supplying  combustion  and  ventilation  air  for  gas  fired  and 

other fuel burning appliances. Appliances that pull air out of 

the house (clothes dryers, exhaust fans, fireplaces, etc.) in

-

crease the problem by starving appliances for air.  

House depressurization can cause back drafting or improper 

combustion of gas-fired appliances, thereby exposing build

-

ing occupants to gas combustion products that could include 

carbon monoxide.

Содержание Amana CES80 Series

Страница 1: ...ces However if there is a direct conflict between existing practices and the content of this manual the precautions listed here take precedence RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION NOTE Please...

Страница 2: ...he Return Air Ductwork 18 SEQUENCE OF OPERATION INTEGRATED IGNITION CONTROL 18 Power Up 18 Heating Mode 18 Cooling Mode 19 Fan Only Mode 19 START UP PROCEDURE AND ADJUSTMENT 19 Furnace Operation 19 Fu...

Страница 3: ...se conditions are listed in the PRODUCT APPLICATION section of this manual WARNING To prevent possible property damage personal injury or death due to electrical shock the furnace must be located to p...

Страница 4: ...a limiting factor in locating the furnace Shipping Inspection All units are securely packed in shipping containers tested according to International Safe Transit Association specifica tions The carton...

Страница 5: ...fied by a qualified person according to these installation instructions Copy of the inspection report issued by carrier s repre sentative at the time damage is reported to carrier The carrier is respo...

Страница 6: ...All venting shall be in accordance with the National Fuel Gas Code ANSI Z223 1 or applicable local building and or air conditioning codes NOTE Furnaces with NOx screens meet the Califor nia NOx emiss...

Страница 7: ...s deicing salts or chemicals carbon tetrachloride halogen type refrigerants cleaning solutions such as perchloroethylene printing inks paint removers varnishes hydrochloric acid cements and glues anti...

Страница 8: ...d will depend on the application and the clearanc es necessary Suspended Furnace Existing Furnace Removal NOTE When an existing furnace is removed from a venting system serving other appliances the ve...

Страница 9: ...inspection R gler le thermostat de mani re ce que l appareil fonctionne en continu 7 V rifier la pr sence de fuite au niveau de l ouverture du coupe tirage des appareils qui en sont dot s apr s 5 minu...

Страница 10: ...y NOTE The vertical height of the Category I venting system must be at least as great as the horizontal length of the venting system WARNING To prevent possible personal injury or death due to asphyxi...

Страница 11: ...ensation damage is best avoided by using masonry chimney as a pathway for properly sized metal liner or Type B metal vent 7 Remove the chimney transition bottom from the transi tion bottom kit 8 Insta...

Страница 12: ...nfigured for a right side electrical connection To make electrical connec tions through the opposite side of the furnace the junction box must be relocated to the left side prior to making elec trical...

Страница 13: ...RNING To prevent personal injury or death due to electric shock disconnect electrical power before installing or servicing this unit 1 Remove both doors from the furnace 2 Remove and save the screws h...

Страница 14: ...s used to share the call for fan operation between furnaces The duration of the pulse width determines the speed that the reading control will energize its blower motor CAUTION To prevent unreliable o...

Страница 15: ...R10 9 R20 9 R100 R 96 R14 3 R20 7 R213 R215 CR1 R1 96 1 C R 1 0 R57 R7 R35 1 R48 R9 4 R6 2 R2 9 R98 R173 R12 2 R139 CR27 CR4 R19 5 R82R1 7 C1 9 C21 R158 C2 3 C1 4 C3 7 C38 R50 C3 6 R164 R172 C31 CR9 3...

Страница 16: ...e resistant to the action of the fuel used Use ground joint unions Install a drip leg to trap dirt and moisture before it can enter the gas valve The drip leg must be a minimum of three inches long In...

Страница 17: ...confined space it is strongly recommended to contact a propane supplier to install a gas detecting warning device in case of a gas leak Since propane gas is heavier than air any leaking gas can settle...

Страница 18: ...the furnace casing and terminating outside the space containing the furnace Filters Read This Section Before Installing The Return Air Ductwork Filters must be used with this furnace Filters do not s...

Страница 19: ...d control module mon itors safety circuits continuously R and G thermostat contacts open completing the call for fan Circulator blower is de energized Electronic air clean er terminals are de energize...

Страница 20: ...repair leaks immediately 13 Turn ON electrical power and gas supply to the system 14 Turn valve switch ON position 8 Replace the door on the front of the furnace 9 Open the manual gas valve external...

Страница 21: ...ivide the number of seconds recorded in step 2 by two 4 Calculate the furnace input in BTUs per hour BTU hr Input equals the installation s gas heating value multiplied by a conversion factor hours to...

Страница 22: ...an the input indi cated on the unit rating plate 5 Turn ON gas and relight appliances turned off in step 1 Ensure all the appliances are functioning properly and that all pilot burners are operating T...

Страница 23: ...external static pressure exceeds the maximum listed on the furnace rating plate check for closed dampers registers undersized and or oversized poorly laid out duct work Digital Manometer Checking Stat...

Страница 24: ...10 K8 K6 K7 1 U1 DS1 OFF O N SW1 OFF ON SW2 1 2 3 4 SW3 CR25 CR29 CR30 CR32 CR17 CR1 1 CR1 0 CR1 2 CR4 0 CR15 CR13 CR7 CR3 CR35 CR19 CR18 CR26 CR34 CR2 1 CR33 Q10 Q12 Q14 Q6 CR4 CR1 CR6 CR9 CR14 CR16...

Страница 25: ...re Switches The pressure switches are normally open negative air pres sure activated switches They monitor the airflow combus tion air and flue products through the heat exchanger via pressure taps lo...

Страница 26: ...isconnect electrical power to the furnace BEFORE removing the filter or performing any other maintenance TROUBLESHOOTING Diagnostic Chart Refer to the troubleshooting chart in the Appendix for assis t...

Страница 27: ...htly orange tips They should not be yellow They should extend directly outward from the burner ports without curling downward floating or lifting off the ports Cleaning Qualified Servicer Only 1 Shut...

Страница 28: ...er Door Interlock Switch 15 Circulator Blower 16 Gas Line Entrance Alternate COMPONENT ID Pressure Switch Tubular Heat Exchanger Flue Pipe Connection Gas Line Entrance Alternate Induced Draft Blower C...

Страница 29: ...ed gas supply lazy burner flames improper gas pressure or restriction in flue and or improper induced draft blower performance Locate and correct gas interruption Replace or realign igniter Check flam...

Страница 30: ...heck burners for proper alignment Check flue for blockage proper length elbows and termination Correct as necessary Check rollout limit Replace if necessary Check induced draft blower for proper perfo...

Страница 31: ...rrect unit ground wire Replace bad integrated control module Turn power OFF prior to repair Replace igniter w proper replacement part Read precautions in Electrostatic Discharge Furnace not operating...

Страница 32: ...N A 1410 1400 1358 OFF ON 1820 N A 1769 N A 1726 N A 1685 N A 1642 N A 1603 1557 1521 DIP SWITCHES S2 1 S2 2 EXTERNAL STATIC PRESSURE INCHES WATER COLUMN 0 1 0 2 0 3 0 4 0 5 801005C 800403A 800603A 80...

Страница 33: ...82 229 197 ON ON ON 784 716 645 583 516 405 334 282 229 197 ON OFF OFF 1295 1252 1203 1153 1114 1071 1022 981 931 883 ON ON OFF 1401 1366 1320 1278 1236 1194 1153 1112 1070 1025 OFF ON OFF 1596 1553 1...

Страница 34: ...11 59 965 61 920 868 818 OFF OFF 743 N A 668 N A 599 N A 522 N A 432 N A 366 312 258 ON OFF 1408 42 1369 43 1319 45 1282 46 1242 48 1219 1193 1150 ON ON 1179 50 1123 53 1073 55 1025 58 972 61 949 924...

Страница 35: ...ON 1402 1358 1317 1274 1234 1195 1154 1113 1069 1033 OFF OFF 743 668 599 522 432 366 312 258 213 158 ON OFF 1408 1369 1319 1282 1242 1193 1150 1109 1069 1025 OFF ON 1574 1521 1481 1439 1398 1374 1335...

Страница 36: ...335 263 232 195 ON ON ON 752 678 608 547 474 403 335 263 232 195 ON OFF OFF 1330 1280 1229 1187 1146 1103 1061 1018 977 936 ON ON OFF 1155 1100 1048 1002 952 907 861 816 789 741 OFF ON OFF 1418 1376...

Страница 37: ...652 466 499 428 346 294 246 202 OFF ON ON 822 754 652 466 499 428 346 294 246 202 ON OFF ON 822 754 652 466 499 428 346 294 246 202 ON ON ON 822 754 652 466 499 428 346 294 246 202 ON OFF OFF 1352 12...

Страница 38: ...agram on the unit for the most up to date wiring MES80 CES80 WIRING DIAGRAM HIGH VOLTAGE D ISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT M ULTIPLE POWER SOURCES MAY BE PRESENT F AILURE...

Страница 39: ...se DB F Delta T Difference between Supply and Return Temperatures DB F GAS PRESSURES Gas Inlet Pressure IN W C Gas Manifold Pressure Low Fire IN W C Gas Manifold Pressure High Fire IN W C Gas Type NG...

Страница 40: ...register their product does not diminsh their warranty rights For Product Registration please register by following this link Goodman Brand Products https www goodmanmfg com product registration Amana...

Отзывы: