Setup
Connections
EPOS4 50/5 Hardware Reference
CCMC | 2022-04 | rel10445
3-45
3.3.9
STO (X9)
The STO (Safe Torque Off) function can be utilized to bring the drive to a torque-free, safe condition via two
independent inputs. The drive output power stage is switched off if either one of the inputs is not powered.
For in-depth details on the STO functionality see separate document
«EPOS4 Application Notes».
Non-certified STO functionality
The implemented STO functionality will not be certified.
Figure 3-35
STO connector X9
Activation of power stage
In order to activate the power stage, either
both
STO inputs must be powered or the «STO Idle Connector»
(
Table 3-47) must be plugged.
Table 3-46
STO connector X9 – Pin assignment
For the matching prefab cable assembly
Table 3-47
STO Idle Connector
Continued on next page.
X9
Head A
Prefab
Cable
Head B
Signal
Description
Pin
Color
Pin
1
white
1
STO-IN1+
Safe Torque Off input 1, positive signal
2
brown
2
STO-IN1
−
Safe Torque Off input 1, negative signal
3
green
3
STO-IN2+
Safe Torque Off input 2, positive signal
4
yellow
4
STO-IN2
−
Safe Torque Off input 2, negative signal
5
grey
5
STO-OUT+
Safe Torque Off output, positive signal
6
pink
6
STO-OUT
−
Safe Torque Off output, negative signal
7
blue
7
GND
Ground
8
red
8
V
STO
Activation voltage for STO inputs (+5 VDC)
Note:
Do not use this voltage for any other purpose
STO Idle Connector (520860)
—included with every delivery—
Plug
Molex CLIK-Mate, single row, 8 poles (502578-0800) with cable bridges