MAXA i-32V504 Скачать руководство пользователя страница 32

i-32V5 

Air/Water heat pumps wih axial fans

32

CAUTION: Do not clean the coil using high-pressure cleaners so as not to apply excessive pressure which could cause irrepa

-

rable damage. Damage caused by cleaning with unsuitable chemical substances or excessively high water pressure will not 

be recognised under warranty.

CAUTION: The aluminium fins are thin and sharp. Pay the utmost attention and use appropriate PPE to avoid cuts and abra

-

sions. Cover your eyes and face appropriately to avoid squirting water and filth while blowing. Wear waterproof shoes or 

boots and clothing covering your entire body.

For units installed in aggressive atmospheres with a high fouling rate, cleaning of the coil must be part of the routine main

-

tenance program. In these types of installations, all of the dust and particulates deposited on the coils must be removed as 

soon as possible through regular cleaning according to the methods shown above.

9.2 

CLEANING OF EXTERNAL SURFACES

The sheets of the outer casing must be properly cleaned to avoid the accumulation of dust / dirt, preventing the onset of corrosion. The painting 

ensures resistance to atmospheric agents but it is good practice to make sure to remove any dirt present, cleaning the surfaces with neutral 

detergent and water, especially if the unit is installed in places with an aggressive atmosphere (high level of pollution, salt, etc.).

9.3 

EXTRAORDINARY MAINTENANCE

All extraordinary maintenance jobs must be carried out by an authorised assistance centre.

10.  DECOMMISSIONING

Once the unit has reached the end of its life cycle and needs to be replaced, the following operations are recommended:

• 

the refrigerant has to be recovered by trained personnel and sent to proper collection centres; according to the procedures indicated in 

Regulation No. 517/2014 on fluorinated greenhouse gases;

• 

any antifreeze additives in the water circuit must be recovered and disposed of properly;

• 

the compressors’ lubricating oil has to be collected and sent to proper collection centres;

• 

the electronic components, such as regulators, driver boards and inverters, must be disassembled and sent to proper collection centres;

• 

The structure and the different components, if unusable, must be scrapped and divided according to their nature; there is especially a good 

amount of copper and aluminium in the machine.

These operations allow easy material recovery and the recycling process, thus reducing the environmental impact in accordance with the provi-

sions of Directive 2012/19 / EU on waste electrical and electronic equipment (RAEE).

The user is responsible for the proper disposal of this product, according to national regulations in the country of destination of the appliance. 

For more information, you should contact the Installation Company or local competent authority.

An incorrect decommissioning of the appliance may create serious environmental damage and endanger people’s safety. 

Therefore, it is recommended that the unit be disposed only by authorised persons with technical training who have attend

-

ed training courses acknowledged by the competent authorities.

It is required to follow the same precautions described in the previous paragraphs.

Pay special attention during disposal of the refrigerant gas.

The illegal disposal of the product by the end user leads to the application of the penalties in accordance with the law in the 

country where the disposal takes place.

The crossed-out bin symbol applied on the appliance indicates that the product, at the end of its useful life, must be collect

-

ed separately from other solid/municipal waste.

The units are manufactured in accordance with the EC directive on waste of electric/electronic equipment and the harmful 

effects of incorrect disposal are provided in the user/installer manual. The manufacturing company or its importer/retailer is 

available to respond to any requests for additional information.

10.1 

RESIDUAL RISKS

This paragraph sets forth any residual risks which cannot be eliminated by the manufacturer in the design stage.

Risk due to:

Precautions/Corrections

Handing

There is always the risk of the unit falling or tipping over during handling. Follow the instructions in the “Handling” 

section and take all of the precautions foreseen according to local regulations.

Installation

Unsuitable installation can cause water leaks, gas leaks, electric shocks, fire hazards, malfunctioning or damage of the 

unit. Only qualified technical personnel can perform installation.

Place the unit in an appropriate area and without the risk of flammable gas leaks. Make the installation zone inacces

-

sible to third parties.

Содержание i-32V504

Страница 1: ...ny installation based on the explanations and or on the technical specifications provided in this manual It is besides forbidden the reproduction under any form of the texts of the figures contained i...

Страница 2: ...i 32V5 Air Water heat pumps wih axial fans 2...

Страница 3: ...09 2020 Updated images chap 5 5 added chap 5 2 and 9 2 updated chap 5 3 5 4 5 7 5 9 9 10 11 1 update refrigerante charges and SCOP values for sizes 04 16 16T 13 02 05 2020 Info deleted ch 5 3 expansio...

Страница 4: ...MINIMUM TECHNICAL CLEARANCES 13 5 5 DIMENSIONS 15 5 5 1 Model i 32V5 04 06 08 SL08 15 5 5 2 Model i 32V5 10 10T 12 SL12 12T SL12T 16 5 5 3 Model i 32V5 14 14T 16 SL16 16T SL16T 18T 17 5 6 ACCESSING TH...

Страница 5: ...corrosion method 31 9 2 CLEANING OF EXTERNAL SURFACES 32 9 3 EXTRAORDINARY MAINTENANCE 32 10 DECOMMISSIONING 32 10 1 RESIDUAL RISKS 32 11 TECHNICAL DATA 37 11 1 STANDARD UNIT TECHNICAL SHEET 37 11 2 S...

Страница 6: ...ncompatible Therefore make sure to use the supplied manual for the installed unit It is recommended to follow the instructions contained in this manual especially those concerning safety and routine m...

Страница 7: ...aning and maintenance which the user is expected to carry out on the unit cannot be done by children without supervision Direct interaction with the unit by persons with electrically controlled medica...

Страница 8: ...on imposes on operators working in installations operating with greenhouse gases to hold a certificate issued or recognised by the competent authority certifying that they have passed an examination a...

Страница 9: ...necessary use a respiratory protection mask and a eye protection gog gles 4 3 SAFETY SIGNS The unit features the following safety signs which must be complied with Generic hazard Dangerous electric vo...

Страница 10: ...e cient air exchange and or suc on the work environments Advice for safe use Do not breath in fumes or aerosol Storage Close carefully and store in a cool dry and well ven lated area Keep in original...

Страница 11: ...formed in accordance with the national regulations in force Specifically according to ADR provisions the total maximum quantity by transport unit in terms of net mass for flammable gases is 333 kg 5 I...

Страница 12: ...close the panels by fixing them with screws 5 2 TRANSPORT AND STORAGE TEMPERATURE LIMITS Minimum storage temperature C 10 C Maximum storage temperature C 50 C 5 3 LIFTING AND HANDLING The handling mus...

Страница 13: ...must not be smooth to avoid water ice deposit as potential sources of danger Unit installation place must be free from foliage dust etc which could clog or cover the coil Installation in areas subject...

Страница 14: ...32V504 mm 500 i 32V506 mm 500 i 32V508 i 32V5SL08 mm 500 i 32V510 i 32V510T mm 500 i 32V512 i 32V5SL12 i 32V512T i 32V5SL12T mm 500 i 32V514 i 32V514T mm 500 i 32V516 i 32V5SL16 i 32V516T i 32V5SL16T...

Страница 15: ...g to the power and sound pressure data reported in the technical data chapter and the sound emission limits according to the installation area of the unit with reference to the DPCM of 14 11 1997 An a...

Страница 16: ...ps wih axial fans 16 828 68 186 190 94 156 377 IN OUT 360 330 924 540 150 154 350 A E E 5 5 2 Model i 32V5 10 10T 12 SL12 12T SL12T IN OUT 1 M G E power supply input 1047 134 673 134 403 87 936 109 17...

Страница 17: ...ps with axial fansi 17 5 5 3 Model i 32V5 14 14T 16 SL16 16T SL16T 18T IN OUT 1 M G E power supply input 73 1409 237 66145 448 106 1044 155 634 156 404 376 418 E A E IN OUT 5 6 ACCESSING THE INNER PAR...

Страница 18: ...0 10T 12 SL12 12T SL12T 1 Remove the cover by undoing the screws number 1 2 3 4 5 6 7 8 2 Undo the screws number 9 10 of the front sheet and then push the panel downwards to remove the tabs Detail A p...

Страница 19: ...larger than 1 mm and a dirt separator on the return pipe from the system labelled WATER INLET If the flow switch is manipulated or altered or if the metal filter and dirt separa tor are missing the wa...

Страница 20: ...ation which could drip from the pipes of the plumbing system Since these pipes are well insulated a minimum amount of condensation is produced anyway and therefore it is not mandatory to connect a dra...

Страница 21: ...advisable to use an external tap to fill the system 5 7 7 Service sleeves In the hydraulic circuit of the unit 2 service sleeves with gap 1 4 G are installed dowstream and upstream of the circulator r...

Страница 22: ...Y CYCLE REVERSING VALVE TE OUTDOOR TEMPERATURE PROBE LR LIQUID RECEIVER TE SD 1 INTAKE LINE TEMPERATURE PROBE F FILTER TE DT 1 COMPRESSOR DISCHARGE TEM PERATURE PROBE SV FILLING CONNECTION PSH C 1 1 A...

Страница 23: ...EVERSING VALVE TE OUTDDOR AIR TEMPERATURE PROBE LR LIQUID RECEIVER TE SD 1 INTAKE LINE TEMPERATURE PROBE F FILTER TE DT 1 COMPRESSOR DISCHARGE TEMPERATURE PROBE SV FILLING CONNECTION PSH C 1 1 AUTOMAT...

Страница 24: ...LE REVERSING VALVE TE OUTDOOR AIR TEMPERATURE PROBE LR LIQUID RECEIVER TE SD 1 INTAKE LINE TEMPERATURE PROBE F FILTER TE DT 1 COMPRESSOR DISCHARGE TEMPERATURE PROBE SV FILLING CONNECTION PSH C 1 1 AUT...

Страница 25: ...CYCLE REVERSING VALVE TE OUTDOOR AIR TEMPERATURE PROBE LR LIQUID RECEIVER TE SD 1 INTAKE LINE TEMPERATURE PROBE F FILTER TE DT 1 COMPRESSOR DISCHARGE TEM PERATURE PROBE SV FILLING CONNECTION PSH C 1...

Страница 26: ...trol panel is connected to the chiller by 4 cables with a cross section of 1 5 mm2 The power cables must be separate from the remote control cables Maximum distance 50 metres ATTENZIONE The remote con...

Страница 27: ...tibility specifications however the designer of the electrical system must fulfil appropriate assessments to ensure the absence of interference 5 9 3 User terminal block The connection terminal block...

Страница 28: ...5 1 X 5 2 X 16 1 X 16 2 X 15 1 X 17 1 X 19 1 X 19 2 X 20 1 X 20 2 X 22 1 X 22 2 X 15 2 X 17 2 F1 X 1 1 X 1 1 L N L N X 10 2 X 9 2 X 6 2 X 11 2 X 14 2 X 10 1 X 9 1 X 11 1 X 6 1 X 14 1 X 4 1 X 5 2 X 16...

Страница 29: ...This must only be done to disconnect the unit from the power supply for long downtimes e g seasonal stops etc Furthermore power is missing the crankcase heaters will not be powered with the risk of br...

Страница 30: ...operations CAUTION it is possible that a certain quantity of oil from the compressor is deposited in the pipes of the refrigeration circuit especially by bends In case of maintenance operations in wh...

Страница 31: ...ly clean the coil follow the instructions below Remove surface dirt Deposits such as leaves fibres etc should be removed using a vacuum cleaner use a brush or other soft accessory and avoid rubbing ag...

Страница 32: ...ust be scrapped and divided according to their nature there is especially a good amount of copper and aluminium in the machine These operations allow easy material recovery and the recycling process t...

Страница 33: ...ormed in order to minimize the risk of igni tion Take the following measures before working on the cooling circuit Measure Completed Notes 1 General working environment Inform the following persons of...

Страница 34: ...e earth connection 8 Repairs on sealed enclosures When carrying out work on sealed components fully isolate the appliance from the power supply also before removing sealed covers If a power supply is...

Страница 35: ...used However it is important that best practice is followed since flammability is a consideration The following pro cedure shall be adhered to remove refrigerant purge the circuit with inert gas evacu...

Страница 36: ...with date and signature Refrigerant is flammable The system has been taken out of use The refrigerant has been removed 17 Recovering When removing refrigerant from a system either for servicing or dec...

Страница 37: ...5 C 55 C Compressor Type Twin Rotary DC Inverter Number of compressors 1 1 1 1 Refrigerant oil type ESTER OIL VG74 Oil charge amount L 0 45 0 67 0 67 1 Refrigerant circuit 1 1 1 1 Refrigerant Type R32...

Страница 38: ...umber of compressors 1 1 1 1 Refrigerant oil type ESTER OIL VG74 Oil charge amount L 1 1 1 1 4 Refrigerant circuits 1 1 1 1 Refrigerant Type R32 R32 R32 R32 Refrigerant charge 7 kg 2 5 2 5 2 5 3 2 Amo...

Страница 39: ...of compressors 1 1 1 1 Refrigerant oil type ESTER OIL VG74 Oil charge amount L 1 4 1 4 1 4 1 4 Refrigerant circuits 1 1 1 1 Refrigerant Type R32 R32 R32 R32 Refrigerant charge 7 kg 3 2 3 5 3 5 3 5 Am...

Страница 40: ...cative data subject to changes For the correct value always refer to the technical label on the unit 8 Sound power level heating mode condition 3 value determined based on measurements made in accorda...

Страница 41: ...35 C 55 C Compressor Type Twin Rotary DC Inverter Number of compressors 1 1 1 1 1 Refrigerant oil type ESTER OIL VG74 Oil charge amount L 0 67 1 1 1 4 1 4 Refrigerant circuits 1 1 1 1 1 Refrigerant Ty...

Страница 42: ...of the antifreeze probe due to the lack of flow but does not guarantee the minimum water flow rate required for correct operation of the unit Model i 32V5 04 06 08 SL08 10 10T 12 SL12 12T SL12T 14 14T...

Страница 43: ...ter Room temperature with water at maximum 39 C Minimum 20 C Maximum 40 C Room temperature with water at maximum 55 C Minimum 10 C Maximum 35 C Outlet water temperature Minimum 25 C Maximum 60 C The f...

Страница 44: ...ete with a display located under a transparent hinged polycarbonate door with IP67 protection rating The interface consists of a variable text part and a series of icons identifying the operation of t...

Страница 45: ...key In the parameter setting mode it allows you to move to a lower menu or to decrease the parameter value In standard operation the display shows the water outlet temperature in tenths of Celsius deg...

Страница 46: ...C 35 0 25 Hea rCoo Mixing valve summer setpoint C 15 0 0 0 80 rHEA Mixing valve winter setpoint C 30 0 0 0 80 If the DHW function is enabled If Gi module is included access is only possible with insta...

Страница 47: ...i 32V5 Air water inverter heat pumps with axial fansi 47...

Страница 48: ...ADVANTIX SpA Via S Giuseppe Lavoratore 24 37040 Arcole VR Italy Tel 39 045 76 36 585 E mail info advantixspa it www maxa it...

Отзывы: