Air/water inverter heat pumps with axial fansi

27

The power cables, electrical protections and line fuses must be sized in accordance with what is reported in the unit's wiring diagram and in the 

electrical data contained in the technical characteristics table

Use a dedicated power line, do not power the appliance through a line to which other users are connected. Fasten the power cables securely and 

make sure they do not come into contact with sharp corners. Use double insulated cables with copper wires.

The ground connection must be carried out first during the connection phase, vice versa it must be removed last when the unit is disconnected. 

In the event of any loosening of the power cable, it must be ensured that the tension of the active conductors takes place before that of the 

ground wire.

A main switch or a disconnection device with adequate breaking capacity must be installed on the power supply line, which has a separation of 

the contacts in all the poles. The differential protection switch must be compatible with inverter appliances, it is recommended to install a type 

B differential switch, the installation of a different type switch could give rise to untimely trips.

The following table shows the recommended cable sections for a maximum length of 30 m. In any case, depending on type of installation, the 

location and the length of the cables (be it less than or greater than 30m), the electrical system designer will make an appropriate choice.

Power supply

Model

Recommended cable section

(max lenght 30 m)

Recommended tightening torque

230V / 1ph

i-32V504

3 x 2,5 mm2

L/N: 3,4 Nm – PE: 1 Nm

230V / 1ph

i-32V506 / i-32V508,

SL08

3 x 4 mm2

L/N: 3,4 Nm – PE: 1 Nm

230V / 1ph

i-32V510 / i-32V512,

SL12

3 x 4 mm2

L/N: 3,4 Nm – PE: 1 Nm

230V / 1ph

i-32V514 / i-32V516,

SL16

3 x 6 mm2

L/N: 3,4 Nm – PE: 1 Nm

400V / 3ph

i-32V510T / i-32V512T,

SL12T

5 x 2,5 mm2

L1/L2/L3: 3,4 Nm – N/PE: 1 Nm

400V / 3ph

i-32V514T / i-32V516T,

SL16T

5 x 2,5 mm2

L1/L2/L3: 3,4 Nm – N/PE: 1 Nm

400V / 3ph

i-32V518T

5 x 4 mm2

L1/L2/L3: 3,4 Nm – N/PE: 1 Nm

The units comply with the electromagnetic compatibility specifications, however the designer of the electrical system must fulfil appropriate 

assessments to ensure the absence of interference.

5.9.3 User terminal block

The connection terminal block is located under the machine cover. The terminal block must be connected respecting the notes below. The con-

nections shown below are standard. Other connections are given in the MCO manual of the on-machine control of the i-32V5 (see "USER AND 

INSTALLER CONFIGURATION TABLES"), according to the configurations adopted.

CAUTION: it is important to keep the high voltage cables separated from the very low voltage ones

TERMINAL

CONNECTION

TYPE

X-1

Connect the ground cable

Inlet for power supply 1-Ph/N/PE,230V, 50Hz

(only for sizes 06/08, SL08/10/12,SL12/14/16, 

SL16

N

Connect the neutral cable from the mains

L

Connect the phase cable from the mains

PE

Connect the earth cable

Input for power supply 3-Ph/N/PE, 400 Vac, 

50Hz.

(only for size 10T,12T,14T,16T,18T, SL12T,16T)

N

Connect the neutral cable from the mains

L1

Connect the phase cable L1 from the mains

L2

Connect the phase cable L2 from the mains

L3

Connect the phase cable L3 from the mains

X-5.2

Connection of modbus RTU for remote keyboard

Modbus communication

X-5.1

Connection of modbus RTU signal – for remote keyboard

X-4.1

Connection of modbus RTU earth reference for remote 

keyboard (GND)

X-12.1

Remote keyboard power supply (12V, 50Hz, 500mA)

Outpu for power supply 12Vac, 50Hz

X-12.2

Remote keyboard power supply (12V, 50Hz, 500mA)

X-17.1/X-17.2

DHW probe (SAN1)

Analogue or digital input

X-19.1/19.2

Plant remote probe (IMP1)

Analogue input

X-20.1/X-20.2

Double set point (Q4)

Analogue input

X-22.2

0-10V (+) signal input to modify set point

Analog input (ST10)

X-22.1

0-10V (-) signal input to modify set point

X-6.1/X-6.2

Plant heater (Rimp)

Output in single phase voltage 230Vac, 50Hz, 

5A resistive, 1A inductive.

Can be used in versions without KA

X-9.1/X-9.2

Exchanger heater (R2)

Output in single phase voltage 230Vac, 50Hz, 

5A resistive, 1A inductive.

Can be used in versions without KA

X-10.1/X-10.2

Base heater (R3)

Output in single phase voltage 230Vac, 50Hz, 

5A resistive, 1A inductive.

X-11.1/X-11.2

Domestic hot water valve outlet (VS1)

Changeover contact, single phase voltage 

230Vac, 50Hz, 5A resistive, 1A inductive.

Содержание i-32V504

Страница 1: ...ny installation based on the explanations and or on the technical specifications provided in this manual It is besides forbidden the reproduction under any form of the texts of the figures contained i...

Страница 2: ...i 32V5 Air Water heat pumps wih axial fans 2...

Страница 3: ...09 2020 Updated images chap 5 5 added chap 5 2 and 9 2 updated chap 5 3 5 4 5 7 5 9 9 10 11 1 update refrigerante charges and SCOP values for sizes 04 16 16T 13 02 05 2020 Info deleted ch 5 3 expansio...

Страница 4: ...MINIMUM TECHNICAL CLEARANCES 13 5 5 DIMENSIONS 15 5 5 1 Model i 32V5 04 06 08 SL08 15 5 5 2 Model i 32V5 10 10T 12 SL12 12T SL12T 16 5 5 3 Model i 32V5 14 14T 16 SL16 16T SL16T 18T 17 5 6 ACCESSING TH...

Страница 5: ...corrosion method 31 9 2 CLEANING OF EXTERNAL SURFACES 32 9 3 EXTRAORDINARY MAINTENANCE 32 10 DECOMMISSIONING 32 10 1 RESIDUAL RISKS 32 11 TECHNICAL DATA 37 11 1 STANDARD UNIT TECHNICAL SHEET 37 11 2 S...

Страница 6: ...ncompatible Therefore make sure to use the supplied manual for the installed unit It is recommended to follow the instructions contained in this manual especially those concerning safety and routine m...

Страница 7: ...aning and maintenance which the user is expected to carry out on the unit cannot be done by children without supervision Direct interaction with the unit by persons with electrically controlled medica...

Страница 8: ...on imposes on operators working in installations operating with greenhouse gases to hold a certificate issued or recognised by the competent authority certifying that they have passed an examination a...

Страница 9: ...necessary use a respiratory protection mask and a eye protection gog gles 4 3 SAFETY SIGNS The unit features the following safety signs which must be complied with Generic hazard Dangerous electric vo...

Страница 10: ...e cient air exchange and or suc on the work environments Advice for safe use Do not breath in fumes or aerosol Storage Close carefully and store in a cool dry and well ven lated area Keep in original...

Страница 11: ...formed in accordance with the national regulations in force Specifically according to ADR provisions the total maximum quantity by transport unit in terms of net mass for flammable gases is 333 kg 5 I...

Страница 12: ...close the panels by fixing them with screws 5 2 TRANSPORT AND STORAGE TEMPERATURE LIMITS Minimum storage temperature C 10 C Maximum storage temperature C 50 C 5 3 LIFTING AND HANDLING The handling mus...

Страница 13: ...must not be smooth to avoid water ice deposit as potential sources of danger Unit installation place must be free from foliage dust etc which could clog or cover the coil Installation in areas subject...

Страница 14: ...32V504 mm 500 i 32V506 mm 500 i 32V508 i 32V5SL08 mm 500 i 32V510 i 32V510T mm 500 i 32V512 i 32V5SL12 i 32V512T i 32V5SL12T mm 500 i 32V514 i 32V514T mm 500 i 32V516 i 32V5SL16 i 32V516T i 32V5SL16T...

Страница 15: ...g to the power and sound pressure data reported in the technical data chapter and the sound emission limits according to the installation area of the unit with reference to the DPCM of 14 11 1997 An a...

Страница 16: ...ps wih axial fans 16 828 68 186 190 94 156 377 IN OUT 360 330 924 540 150 154 350 A E E 5 5 2 Model i 32V5 10 10T 12 SL12 12T SL12T IN OUT 1 M G E power supply input 1047 134 673 134 403 87 936 109 17...

Страница 17: ...ps with axial fansi 17 5 5 3 Model i 32V5 14 14T 16 SL16 16T SL16T 18T IN OUT 1 M G E power supply input 73 1409 237 66145 448 106 1044 155 634 156 404 376 418 E A E IN OUT 5 6 ACCESSING THE INNER PAR...

Страница 18: ...0 10T 12 SL12 12T SL12T 1 Remove the cover by undoing the screws number 1 2 3 4 5 6 7 8 2 Undo the screws number 9 10 of the front sheet and then push the panel downwards to remove the tabs Detail A p...

Страница 19: ...larger than 1 mm and a dirt separator on the return pipe from the system labelled WATER INLET If the flow switch is manipulated or altered or if the metal filter and dirt separa tor are missing the wa...

Страница 20: ...ation which could drip from the pipes of the plumbing system Since these pipes are well insulated a minimum amount of condensation is produced anyway and therefore it is not mandatory to connect a dra...

Страница 21: ...advisable to use an external tap to fill the system 5 7 7 Service sleeves In the hydraulic circuit of the unit 2 service sleeves with gap 1 4 G are installed dowstream and upstream of the circulator r...

Страница 22: ...Y CYCLE REVERSING VALVE TE OUTDOOR TEMPERATURE PROBE LR LIQUID RECEIVER TE SD 1 INTAKE LINE TEMPERATURE PROBE F FILTER TE DT 1 COMPRESSOR DISCHARGE TEM PERATURE PROBE SV FILLING CONNECTION PSH C 1 1 A...

Страница 23: ...EVERSING VALVE TE OUTDDOR AIR TEMPERATURE PROBE LR LIQUID RECEIVER TE SD 1 INTAKE LINE TEMPERATURE PROBE F FILTER TE DT 1 COMPRESSOR DISCHARGE TEMPERATURE PROBE SV FILLING CONNECTION PSH C 1 1 AUTOMAT...

Страница 24: ...LE REVERSING VALVE TE OUTDOOR AIR TEMPERATURE PROBE LR LIQUID RECEIVER TE SD 1 INTAKE LINE TEMPERATURE PROBE F FILTER TE DT 1 COMPRESSOR DISCHARGE TEMPERATURE PROBE SV FILLING CONNECTION PSH C 1 1 AUT...

Страница 25: ...CYCLE REVERSING VALVE TE OUTDOOR AIR TEMPERATURE PROBE LR LIQUID RECEIVER TE SD 1 INTAKE LINE TEMPERATURE PROBE F FILTER TE DT 1 COMPRESSOR DISCHARGE TEM PERATURE PROBE SV FILLING CONNECTION PSH C 1...

Страница 26: ...trol panel is connected to the chiller by 4 cables with a cross section of 1 5 mm2 The power cables must be separate from the remote control cables Maximum distance 50 metres ATTENZIONE The remote con...

Страница 27: ...tibility specifications however the designer of the electrical system must fulfil appropriate assessments to ensure the absence of interference 5 9 3 User terminal block The connection terminal block...

Страница 28: ...5 1 X 5 2 X 16 1 X 16 2 X 15 1 X 17 1 X 19 1 X 19 2 X 20 1 X 20 2 X 22 1 X 22 2 X 15 2 X 17 2 F1 X 1 1 X 1 1 L N L N X 10 2 X 9 2 X 6 2 X 11 2 X 14 2 X 10 1 X 9 1 X 11 1 X 6 1 X 14 1 X 4 1 X 5 2 X 16...

Страница 29: ...This must only be done to disconnect the unit from the power supply for long downtimes e g seasonal stops etc Furthermore power is missing the crankcase heaters will not be powered with the risk of br...

Страница 30: ...operations CAUTION it is possible that a certain quantity of oil from the compressor is deposited in the pipes of the refrigeration circuit especially by bends In case of maintenance operations in wh...

Страница 31: ...ly clean the coil follow the instructions below Remove surface dirt Deposits such as leaves fibres etc should be removed using a vacuum cleaner use a brush or other soft accessory and avoid rubbing ag...

Страница 32: ...ust be scrapped and divided according to their nature there is especially a good amount of copper and aluminium in the machine These operations allow easy material recovery and the recycling process t...

Страница 33: ...ormed in order to minimize the risk of igni tion Take the following measures before working on the cooling circuit Measure Completed Notes 1 General working environment Inform the following persons of...

Страница 34: ...e earth connection 8 Repairs on sealed enclosures When carrying out work on sealed components fully isolate the appliance from the power supply also before removing sealed covers If a power supply is...

Страница 35: ...used However it is important that best practice is followed since flammability is a consideration The following pro cedure shall be adhered to remove refrigerant purge the circuit with inert gas evacu...

Страница 36: ...with date and signature Refrigerant is flammable The system has been taken out of use The refrigerant has been removed 17 Recovering When removing refrigerant from a system either for servicing or dec...

Страница 37: ...5 C 55 C Compressor Type Twin Rotary DC Inverter Number of compressors 1 1 1 1 Refrigerant oil type ESTER OIL VG74 Oil charge amount L 0 45 0 67 0 67 1 Refrigerant circuit 1 1 1 1 Refrigerant Type R32...

Страница 38: ...umber of compressors 1 1 1 1 Refrigerant oil type ESTER OIL VG74 Oil charge amount L 1 1 1 1 4 Refrigerant circuits 1 1 1 1 Refrigerant Type R32 R32 R32 R32 Refrigerant charge 7 kg 2 5 2 5 2 5 3 2 Amo...

Страница 39: ...of compressors 1 1 1 1 Refrigerant oil type ESTER OIL VG74 Oil charge amount L 1 4 1 4 1 4 1 4 Refrigerant circuits 1 1 1 1 Refrigerant Type R32 R32 R32 R32 Refrigerant charge 7 kg 3 2 3 5 3 5 3 5 Am...

Страница 40: ...cative data subject to changes For the correct value always refer to the technical label on the unit 8 Sound power level heating mode condition 3 value determined based on measurements made in accorda...

Страница 41: ...35 C 55 C Compressor Type Twin Rotary DC Inverter Number of compressors 1 1 1 1 1 Refrigerant oil type ESTER OIL VG74 Oil charge amount L 0 67 1 1 1 4 1 4 Refrigerant circuits 1 1 1 1 1 Refrigerant Ty...

Страница 42: ...of the antifreeze probe due to the lack of flow but does not guarantee the minimum water flow rate required for correct operation of the unit Model i 32V5 04 06 08 SL08 10 10T 12 SL12 12T SL12T 14 14T...

Страница 43: ...ter Room temperature with water at maximum 39 C Minimum 20 C Maximum 40 C Room temperature with water at maximum 55 C Minimum 10 C Maximum 35 C Outlet water temperature Minimum 25 C Maximum 60 C The f...

Страница 44: ...ete with a display located under a transparent hinged polycarbonate door with IP67 protection rating The interface consists of a variable text part and a series of icons identifying the operation of t...

Страница 45: ...key In the parameter setting mode it allows you to move to a lower menu or to decrease the parameter value In standard operation the display shows the water outlet temperature in tenths of Celsius deg...

Страница 46: ...C 35 0 25 Hea rCoo Mixing valve summer setpoint C 15 0 0 0 80 rHEA Mixing valve winter setpoint C 30 0 0 0 80 If the DHW function is enabled If Gi module is included access is only possible with insta...

Страница 47: ...i 32V5 Air water inverter heat pumps with axial fansi 47...