warranty and could considerably shorten the service life of your product.

OPERAZION

month

months

months

12 

months

Filling the water circuit.

x

Presence of bubbles in the water circuit.

x

Check the proper working of the safety and control devices.

x

Check that there are no oil leaks from the compressor.

x

Check if there is a possible water leakage from the water circuit.

x

Check that the flow switch works properly.

x

Check that the crankcase heaters are powered and running.

x

Clean the metal filters of the water circuit.

x

Clean the finned coil with compressed air or water jet

x

Check that the electric terminals both inside the electric panel and in the terminal blocks of the 

compressor are well tightened.

x

Tightening of plumbing connections.

x

Check fixing and balancing of the fans.

x

Clean the air filters in the electrical panel or replace them if necessary (when present).

x

Correct electric voltage and phase imbalance (without load and under load).

x

Correct absorption.

x

Check the refrigerant charge and eventual leaks

x

Check the operating pressure, superheating and sub-cooling

x

Circulation pump efficiency.

x

If the unit should be out of service for a long period, drain water from the pipes and from the heat 

exchanger. This operation is necessary if, during seasonal stoppages, ambient temperature is expect-

ed to go down below the freezing point of the employed fluid.

x

Check for corrosion/oxidation

x

Check panel fastening

x

Check the water quality (see chapter Characteristics of the system water) and the possible concen-

tration of glycol

x

Check the pressure drops of any filter driers on the liquid line

x

Check the hydronic side safety valve

x

9.1 

CLEANING THE FINNED COIL

To correctly clean the coil, follow the instructions below:

• 

Remove surface dirt. Deposits such as leaves, fibres etc. should be removed using a vacuum cleaner (use a brush or other soft accessory 

and avoid rubbing against metal or abrasive parts). If compressed air is used, care must be taken to keep the airflow perpendicular to the 

surface of the battery to avoid bending the aluminium fins. Pay attention not to bend the fins with the nozzle of the compressed air lance.

• 

Rinse. Rinse with water. It is possible to use chemical substances (specific detergents for finned coils). Rinse the coils by letting the water run 

inside each individual passage of the fins, until they are perfectly clean. Pay attention to direct the water jet perpendicular to the surface 

of the coil in order not to bend the aluminium fins. Do not strike the coil with the water hose. Apply your thumb at the end of the hose to 

increase the pressure of the water jet instead of using specific nozzles which could damage the coil.

9.1.1 Cleaning the finned coils treated with the anti-corrosion method

The anti-corrosion treatment applied to the finned coils (available as an alternative to the standard coils) guarantees protection against aggres-

sive atmospheres.

 The frequency of cleaning depends on the environmental conditions and is left to the common sense of the maintenance staff. When oxidizing 

dust or grease particles are observed on the battery surface, cleaning is recommended. In general, in a slightly polluted atmosphere, it is recom-

mended to carry out the cleaning treatment every three months.

Washing should be carried out with preferably hot water (40-60 ° C) and detergent with neutral pH, while rinsing is carried out with abundant 

fresh water (50 l / m2).

If the maintenance staff observes a lack of protective cover on the edge of the fins, it is necessary to contact the nearest service center to pro-

ceed with a new application of the cover and completely restore the protection against corrosion.

Содержание i-32V504

Страница 1: ...ny installation based on the explanations and or on the technical specifications provided in this manual It is besides forbidden the reproduction under any form of the texts of the figures contained i...

Страница 2: ...i 32V5 Air Water heat pumps wih axial fans 2...

Страница 3: ...09 2020 Updated images chap 5 5 added chap 5 2 and 9 2 updated chap 5 3 5 4 5 7 5 9 9 10 11 1 update refrigerante charges and SCOP values for sizes 04 16 16T 13 02 05 2020 Info deleted ch 5 3 expansio...

Страница 4: ...MINIMUM TECHNICAL CLEARANCES 13 5 5 DIMENSIONS 15 5 5 1 Model i 32V5 04 06 08 SL08 15 5 5 2 Model i 32V5 10 10T 12 SL12 12T SL12T 16 5 5 3 Model i 32V5 14 14T 16 SL16 16T SL16T 18T 17 5 6 ACCESSING TH...

Страница 5: ...corrosion method 31 9 2 CLEANING OF EXTERNAL SURFACES 32 9 3 EXTRAORDINARY MAINTENANCE 32 10 DECOMMISSIONING 32 10 1 RESIDUAL RISKS 32 11 TECHNICAL DATA 37 11 1 STANDARD UNIT TECHNICAL SHEET 37 11 2 S...

Страница 6: ...ncompatible Therefore make sure to use the supplied manual for the installed unit It is recommended to follow the instructions contained in this manual especially those concerning safety and routine m...

Страница 7: ...aning and maintenance which the user is expected to carry out on the unit cannot be done by children without supervision Direct interaction with the unit by persons with electrically controlled medica...

Страница 8: ...on imposes on operators working in installations operating with greenhouse gases to hold a certificate issued or recognised by the competent authority certifying that they have passed an examination a...

Страница 9: ...necessary use a respiratory protection mask and a eye protection gog gles 4 3 SAFETY SIGNS The unit features the following safety signs which must be complied with Generic hazard Dangerous electric vo...

Страница 10: ...e cient air exchange and or suc on the work environments Advice for safe use Do not breath in fumes or aerosol Storage Close carefully and store in a cool dry and well ven lated area Keep in original...

Страница 11: ...formed in accordance with the national regulations in force Specifically according to ADR provisions the total maximum quantity by transport unit in terms of net mass for flammable gases is 333 kg 5 I...

Страница 12: ...close the panels by fixing them with screws 5 2 TRANSPORT AND STORAGE TEMPERATURE LIMITS Minimum storage temperature C 10 C Maximum storage temperature C 50 C 5 3 LIFTING AND HANDLING The handling mus...

Страница 13: ...must not be smooth to avoid water ice deposit as potential sources of danger Unit installation place must be free from foliage dust etc which could clog or cover the coil Installation in areas subject...

Страница 14: ...32V504 mm 500 i 32V506 mm 500 i 32V508 i 32V5SL08 mm 500 i 32V510 i 32V510T mm 500 i 32V512 i 32V5SL12 i 32V512T i 32V5SL12T mm 500 i 32V514 i 32V514T mm 500 i 32V516 i 32V5SL16 i 32V516T i 32V5SL16T...

Страница 15: ...g to the power and sound pressure data reported in the technical data chapter and the sound emission limits according to the installation area of the unit with reference to the DPCM of 14 11 1997 An a...

Страница 16: ...ps wih axial fans 16 828 68 186 190 94 156 377 IN OUT 360 330 924 540 150 154 350 A E E 5 5 2 Model i 32V5 10 10T 12 SL12 12T SL12T IN OUT 1 M G E power supply input 1047 134 673 134 403 87 936 109 17...

Страница 17: ...ps with axial fansi 17 5 5 3 Model i 32V5 14 14T 16 SL16 16T SL16T 18T IN OUT 1 M G E power supply input 73 1409 237 66145 448 106 1044 155 634 156 404 376 418 E A E IN OUT 5 6 ACCESSING THE INNER PAR...

Страница 18: ...0 10T 12 SL12 12T SL12T 1 Remove the cover by undoing the screws number 1 2 3 4 5 6 7 8 2 Undo the screws number 9 10 of the front sheet and then push the panel downwards to remove the tabs Detail A p...

Страница 19: ...larger than 1 mm and a dirt separator on the return pipe from the system labelled WATER INLET If the flow switch is manipulated or altered or if the metal filter and dirt separa tor are missing the wa...

Страница 20: ...ation which could drip from the pipes of the plumbing system Since these pipes are well insulated a minimum amount of condensation is produced anyway and therefore it is not mandatory to connect a dra...

Страница 21: ...advisable to use an external tap to fill the system 5 7 7 Service sleeves In the hydraulic circuit of the unit 2 service sleeves with gap 1 4 G are installed dowstream and upstream of the circulator r...

Страница 22: ...Y CYCLE REVERSING VALVE TE OUTDOOR TEMPERATURE PROBE LR LIQUID RECEIVER TE SD 1 INTAKE LINE TEMPERATURE PROBE F FILTER TE DT 1 COMPRESSOR DISCHARGE TEM PERATURE PROBE SV FILLING CONNECTION PSH C 1 1 A...

Страница 23: ...EVERSING VALVE TE OUTDDOR AIR TEMPERATURE PROBE LR LIQUID RECEIVER TE SD 1 INTAKE LINE TEMPERATURE PROBE F FILTER TE DT 1 COMPRESSOR DISCHARGE TEMPERATURE PROBE SV FILLING CONNECTION PSH C 1 1 AUTOMAT...

Страница 24: ...LE REVERSING VALVE TE OUTDOOR AIR TEMPERATURE PROBE LR LIQUID RECEIVER TE SD 1 INTAKE LINE TEMPERATURE PROBE F FILTER TE DT 1 COMPRESSOR DISCHARGE TEMPERATURE PROBE SV FILLING CONNECTION PSH C 1 1 AUT...

Страница 25: ...CYCLE REVERSING VALVE TE OUTDOOR AIR TEMPERATURE PROBE LR LIQUID RECEIVER TE SD 1 INTAKE LINE TEMPERATURE PROBE F FILTER TE DT 1 COMPRESSOR DISCHARGE TEM PERATURE PROBE SV FILLING CONNECTION PSH C 1...

Страница 26: ...trol panel is connected to the chiller by 4 cables with a cross section of 1 5 mm2 The power cables must be separate from the remote control cables Maximum distance 50 metres ATTENZIONE The remote con...

Страница 27: ...tibility specifications however the designer of the electrical system must fulfil appropriate assessments to ensure the absence of interference 5 9 3 User terminal block The connection terminal block...

Страница 28: ...5 1 X 5 2 X 16 1 X 16 2 X 15 1 X 17 1 X 19 1 X 19 2 X 20 1 X 20 2 X 22 1 X 22 2 X 15 2 X 17 2 F1 X 1 1 X 1 1 L N L N X 10 2 X 9 2 X 6 2 X 11 2 X 14 2 X 10 1 X 9 1 X 11 1 X 6 1 X 14 1 X 4 1 X 5 2 X 16...

Страница 29: ...This must only be done to disconnect the unit from the power supply for long downtimes e g seasonal stops etc Furthermore power is missing the crankcase heaters will not be powered with the risk of br...

Страница 30: ...operations CAUTION it is possible that a certain quantity of oil from the compressor is deposited in the pipes of the refrigeration circuit especially by bends In case of maintenance operations in wh...

Страница 31: ...ly clean the coil follow the instructions below Remove surface dirt Deposits such as leaves fibres etc should be removed using a vacuum cleaner use a brush or other soft accessory and avoid rubbing ag...

Страница 32: ...ust be scrapped and divided according to their nature there is especially a good amount of copper and aluminium in the machine These operations allow easy material recovery and the recycling process t...

Страница 33: ...ormed in order to minimize the risk of igni tion Take the following measures before working on the cooling circuit Measure Completed Notes 1 General working environment Inform the following persons of...

Страница 34: ...e earth connection 8 Repairs on sealed enclosures When carrying out work on sealed components fully isolate the appliance from the power supply also before removing sealed covers If a power supply is...

Страница 35: ...used However it is important that best practice is followed since flammability is a consideration The following pro cedure shall be adhered to remove refrigerant purge the circuit with inert gas evacu...

Страница 36: ...with date and signature Refrigerant is flammable The system has been taken out of use The refrigerant has been removed 17 Recovering When removing refrigerant from a system either for servicing or dec...

Страница 37: ...5 C 55 C Compressor Type Twin Rotary DC Inverter Number of compressors 1 1 1 1 Refrigerant oil type ESTER OIL VG74 Oil charge amount L 0 45 0 67 0 67 1 Refrigerant circuit 1 1 1 1 Refrigerant Type R32...

Страница 38: ...umber of compressors 1 1 1 1 Refrigerant oil type ESTER OIL VG74 Oil charge amount L 1 1 1 1 4 Refrigerant circuits 1 1 1 1 Refrigerant Type R32 R32 R32 R32 Refrigerant charge 7 kg 2 5 2 5 2 5 3 2 Amo...

Страница 39: ...of compressors 1 1 1 1 Refrigerant oil type ESTER OIL VG74 Oil charge amount L 1 4 1 4 1 4 1 4 Refrigerant circuits 1 1 1 1 Refrigerant Type R32 R32 R32 R32 Refrigerant charge 7 kg 3 2 3 5 3 5 3 5 Am...

Страница 40: ...cative data subject to changes For the correct value always refer to the technical label on the unit 8 Sound power level heating mode condition 3 value determined based on measurements made in accorda...

Страница 41: ...35 C 55 C Compressor Type Twin Rotary DC Inverter Number of compressors 1 1 1 1 1 Refrigerant oil type ESTER OIL VG74 Oil charge amount L 0 67 1 1 1 4 1 4 Refrigerant circuits 1 1 1 1 1 Refrigerant Ty...

Страница 42: ...of the antifreeze probe due to the lack of flow but does not guarantee the minimum water flow rate required for correct operation of the unit Model i 32V5 04 06 08 SL08 10 10T 12 SL12 12T SL12T 14 14T...

Страница 43: ...ter Room temperature with water at maximum 39 C Minimum 20 C Maximum 40 C Room temperature with water at maximum 55 C Minimum 10 C Maximum 35 C Outlet water temperature Minimum 25 C Maximum 60 C The f...

Страница 44: ...ete with a display located under a transparent hinged polycarbonate door with IP67 protection rating The interface consists of a variable text part and a series of icons identifying the operation of t...

Страница 45: ...key In the parameter setting mode it allows you to move to a lower menu or to decrease the parameter value In standard operation the display shows the water outlet temperature in tenths of Celsius deg...

Страница 46: ...C 35 0 25 Hea rCoo Mixing valve summer setpoint C 15 0 0 0 80 rHEA Mixing valve winter setpoint C 30 0 0 0 80 If the DHW function is enabled If Gi module is included access is only possible with insta...

Страница 47: ...i 32V5 Air water inverter heat pumps with axial fansi 47...

Страница 48: ...ADVANTIX SpA Via S Giuseppe Lavoratore 24 37040 Arcole VR Italy Tel 39 045 76 36 585 E mail info advantixspa it www maxa it...

Отзывы: