Anti-Seize Timer

With

DIP Switch 4 

set to “On”, the Anti-seize timer will automatically run the pump for 6 seconds, every 7 days. This 

pump operation will completely override all inputs including the low level (if enabled). This feature will only run the pump

set in Auto A pump that has been locked out due to a fault will not run.  

Manual Mode Timeout

With

 DIP Switch 5

 set to “On” the pump will only remain in Manual Mode for 5 minutes, after which time, it

automatically reverts to Auto. 

High Level Alarm Reset

With

DIP Switch 6

 set to “Off”, the High Level Alarm will automatically reset once the High Level input opens circuit. The 

controller will also use the alternate High Level Alarm Delay. Typically used for Storm Water applications. High Level Alarm 

delay in this mode is 15 minutes.
Setting this DIP Switch to “On”, will cause the High level Alarm to remain active until the controller is reset. The High 

Level Alarm will use the standard High Level Alarm activation delay. Typically used for Sewerage applications. High Level 

Alarm delay in this mode is 5 minutes.

Audible and Visual Alarm Test

By pressing the

 Mute/Reset 

button on the Keypad continuously for a period of 5 seconds, the Strobe, Siren and

indicator Lights will be powered for inspection.

Fault Reset

To reset all faults on the controller, press and old the

Mute/Reset

 button on the Keypad continuously for a period of 3

seconds until an acknowledgement beep is heard.

Pump Fault

A Pump Fault is indicated for two types of faults. A Thermal Overload will be indicated by way of a steady Fault Indicator 

Light when the overload opens the contact for 3 seconds. Prime loss will be indicated by flashing the pump fault light slowly.

Level Alarms

A High Level Alarm is indicated by way of a steady Level Alarm Indicator Light.

A Low Level/Low pressure Alarm is indicated by way of a Flashing Level Alarm Light.

lly 

Auto Silencing Alarm Feature

The audible Alarm is programmed to sound for 5 minutes continuously, unless muted and will thereafter automatica

In pressure pump mode some of the optional features are disabled, including maximum run alternation, anti-seize and 

maximum idle timers.

Mode ‘Current Loop’: Level Transducer (4-20mA) Configuration

In order to activate current loop mode the enclosure must be opened and jumper J10 moved to the “current loop 

enabled” position (as shown in the following picture). By selecting current loop input mode the pump start input can be 

connected to a 4-20mA loop powered pressure transducer. The pump start, stop and high level signals can then be 

received from the pressure transmitter instead of float switches. In this mode the pump stop float switch input will be 

ignored however the high level input will still operate as per normal so that a float switch can be used as backup if 

desired.
The start, stop and high level current set points will be pre-programmed into the software and therefore cannot be 

adjusted. The levels for a 0-4m transducer are Stop= 300mm, Start= 600mm and High= 1000mm.

Figure 1: APC6 PCB Layout and Current Loop Jumper 

 

 

Current Loop

Enable Jumper

 

Dip Switch Setting

Ensure dip switch 1 and 2 are down 

in mode A for transducer operation 

Содержание FPC-15205

Страница 1: ...DOC FPC 15205 REVISED 072415 OFF ON MAIN ISOLATOR Single Pump Controller Installation and Operating Instructions P U M P C O N T R O L OWNER S OPERATION MANUAL MODEL FPC 15205...

Страница 2: ...you the owner operator of many years of functional reliable and user friendly operation Please read this manual prior to installation and operation of the controller GETTING STARTED 4 Operations Featu...

Страница 3: ...SUIT PUMP NOTE Electrician CONNECTION MOUNTING INSTALLATION OFF ON MAIN ISOLATOR SUPPLY Input 4 High Level Input 3 Start Level Input 2 Stop Level Input 1 Low Level INPUT SWITCHES 12Vdc Connections VOL...

Страница 4: ...active Low Level input The Low Level input must be closed for Pump Start and Pump Stop inputs to function The High Level input however will still override the Low Level and run the pump Input function...

Страница 5: ...w Level Low Level High Level after Timeout Input Function Input 1 Prime Loss Input 2 Pump Stop Input 3 Pump Start Input 4 High Level Input Function Input 1 Prime Loss BRIDGE IF NOT REQUIRED Input 2 Le...

Страница 6: ...pes of faults A Thermal Overload will be indicated by way of a steady Fault Indicator Light when the overload opens the contact for 3 seconds Prime loss will be indicated by flashing the pump fault li...

Страница 7: ...h Level 240VAC Pump P1 1 2 Main Isolator MSW1 ME 20 BMS SIGNAL IN POWER IN 9 12V DC AC PUMP 2 FAULT PUMP 1 FAULT HIGH LEVEL POWER VOLTAGE FREE CONTACTS PCB BMS 1 Common C1 Aux NO C1 Power On High Leve...

Страница 8: ...A low level alarm is present ON STEADY A pump fault overload has occured FLASHING A prime loss fault has occured ON STEADY Pump switched on to run DISTRIBUTED BY 8 INSTALLATION DATE SERIAL NUMBER AT A...

Отзывы: