OPERATION

4

This controller can perform control functions for most Single Pump  pumping applications. It is more than likely that the con-

There are 6 DIP switches located on the lower side of the control module, which allows for selecting “mode” and “feature” 

options, as per the following table:

Start/Stop/High Level operation. When the Pump Start input is closed contact (triggered), the Duty Pump will be turned on. 

The pump will remain on until both the Pump Start and Pump Stop Inputs have turned off (Open Circuited). Upon High Level, 

the pump will run until the Pump Stop Input turns off.

In addition to this, there is a maximum idle timer, which will trigger a Pump Start condition, if the pump has not run for 4 

hours, and the Stop Float Contacts are closed. The pump will continue to run until the Stop Float Contacts open. Input

functions are as follows:

As per Mode A, except it has an active Low Level input. The Low Level input must be closed, for Pump Start and Pump Stop 

inputs to function. The High Level input however, will still override the Low Level and run the pump. Input functions are as 

follows:

      

Position

Off/Off

Off/On

On/Off

On/On

Off

On

Off

On

Off

On

Off

On

Function

Mode A:

Mode B:

Mode C:

Mode D:

Operating Pump alternates each time a pump start is triggered, or after 30 minutes continuous 

running.

Operating Pump alternates after 6 hours continuous running.

Anti-seize Timer disabled

Anti-seize Timer 6 seconds every 7 days enabled

When placed in Manual Mode, pump remains in Manual Mode

When placed in Manual Mode after 5 minutes the pump will revert to Auto

High Level Alarm automatically resets upon open circuit of high level input. High Level alarm 

has 15 minute delay.

High Level Alarm can only be reset manually. High Level Alarm has 5 minute delay. 

DIP Switch

1/2

3

4

5

6

Input        Function

Input 1     Not used

Input 2     Pump Stop

Input 3     Pump Start

Input 4     High Level

Input         Function

Input 1      Low Level

Input 2      Pump Stop

Input 3      Pump Start

Input 4      High Level

Содержание FPC-15205

Страница 1: ...DOC FPC 15205 REVISED 072415 OFF ON MAIN ISOLATOR Single Pump Controller Installation and Operating Instructions P U M P C O N T R O L OWNER S OPERATION MANUAL MODEL FPC 15205...

Страница 2: ...you the owner operator of many years of functional reliable and user friendly operation Please read this manual prior to installation and operation of the controller GETTING STARTED 4 Operations Featu...

Страница 3: ...SUIT PUMP NOTE Electrician CONNECTION MOUNTING INSTALLATION OFF ON MAIN ISOLATOR SUPPLY Input 4 High Level Input 3 Start Level Input 2 Stop Level Input 1 Low Level INPUT SWITCHES 12Vdc Connections VOL...

Страница 4: ...active Low Level input The Low Level input must be closed for Pump Start and Pump Stop inputs to function The High Level input however will still override the Low Level and run the pump Input function...

Страница 5: ...w Level Low Level High Level after Timeout Input Function Input 1 Prime Loss Input 2 Pump Stop Input 3 Pump Start Input 4 High Level Input Function Input 1 Prime Loss BRIDGE IF NOT REQUIRED Input 2 Le...

Страница 6: ...pes of faults A Thermal Overload will be indicated by way of a steady Fault Indicator Light when the overload opens the contact for 3 seconds Prime loss will be indicated by flashing the pump fault li...

Страница 7: ...h Level 240VAC Pump P1 1 2 Main Isolator MSW1 ME 20 BMS SIGNAL IN POWER IN 9 12V DC AC PUMP 2 FAULT PUMP 1 FAULT HIGH LEVEL POWER VOLTAGE FREE CONTACTS PCB BMS 1 Common C1 Aux NO C1 Power On High Leve...

Страница 8: ...A low level alarm is present ON STEADY A pump fault overload has occured FLASHING A prime loss fault has occured ON STEADY Pump switched on to run DISTRIBUTED BY 8 INSTALLATION DATE SERIAL NUMBER AT A...

Отзывы: