background image

5

The basic logic on which a High or Low Level Alarm is determined, is set out in the Table below:

If there is a Low Level Alarm, then the pump will be locked out until the alarm is manually reset. This lockout will only be 

over ridden upon a High Level condition where both the Pump Start and High level inputs are closed.

Note that after a High level is triggered, the pump will run until the Pump Start and Stop inputs are opened.

is running, the Prime Loss input opens, for a continuous 2 minute period, a fault is immediately triggered and the pump

power down functions are as follows:       

Input functions are as follows:

Input 2

Pump Stop

Open/Closed
Open/Closed
Open/Closed
Open/Closed
Open/Closed
Open/Closed
Open/Closed
Open/Closed

Input 1

Low Level

Closed
Closed
Closed
Closed

Open
Open
Open
Open

Input 3

Pump Start

Open

Closed
Closed

Open
Open

Closed

Open

Closed

Input 4

High Level

Open
Open

Closed
Closed

Open
Open

Closed
Closed

Pump

State

Off
On

Both On
Both On

Off
Off
Off

Both On

Alarm

-
-

High Level (after Timeout)
High Level (after Timeout)

-

Low Level
Low Level

High Level (after Timeout)

Input         Function

Input 1      Prime Loss

Input 2      Pump Stop

Input 3      Pump Start

Input 4      High Level

Input

Function

Input 1      Prime Loss (BRIDGE IF NOT REQUIRED)

Input 2      Lead Pump Pressure Switch (set at say 350kPa)

not used

Input 3

Input 4      Low Pressure Switch (set at say 200kPa)

 

Pressure drops to 400kPA. Pump cuts in.

 

Pressure increases and Pump cuts out

 

Cycle continues 

 

The controller has inbuilt timers for “Delayed” Start and Stop to obviate pump chatter. Upon Input 1 contact closure, the 

pump will not start (delay start) for 1 second and will not stop (minimum run time) for 10 seconds (or 11 seconds from close 

of Input contacts). This “run on” occurs even if Pressure switch contacts open during this initial period. If however run time 

exceeds 11 seconds, the pump will stop immediately upon “open circuit” occurring.

 

If the Pressure Switch Input closes circuit as well as the Low Pressure Switch Input, a low pressure timer will begin counting. 

If this condition exists for a period of 60 seconds, then both pumps are shut down and the system signals a level alarm. This 

would be typical of a Loss of Prime or Burst Main situation

 

Pressure switches are normally closed and open on High pressure

Typical operation for Mode D:

Содержание FPC-15205

Страница 1: ...DOC FPC 15205 REVISED 072415 OFF ON MAIN ISOLATOR Single Pump Controller Installation and Operating Instructions P U M P C O N T R O L OWNER S OPERATION MANUAL MODEL FPC 15205...

Страница 2: ...you the owner operator of many years of functional reliable and user friendly operation Please read this manual prior to installation and operation of the controller GETTING STARTED 4 Operations Featu...

Страница 3: ...SUIT PUMP NOTE Electrician CONNECTION MOUNTING INSTALLATION OFF ON MAIN ISOLATOR SUPPLY Input 4 High Level Input 3 Start Level Input 2 Stop Level Input 1 Low Level INPUT SWITCHES 12Vdc Connections VOL...

Страница 4: ...active Low Level input The Low Level input must be closed for Pump Start and Pump Stop inputs to function The High Level input however will still override the Low Level and run the pump Input function...

Страница 5: ...w Level Low Level High Level after Timeout Input Function Input 1 Prime Loss Input 2 Pump Stop Input 3 Pump Start Input 4 High Level Input Function Input 1 Prime Loss BRIDGE IF NOT REQUIRED Input 2 Le...

Страница 6: ...pes of faults A Thermal Overload will be indicated by way of a steady Fault Indicator Light when the overload opens the contact for 3 seconds Prime loss will be indicated by flashing the pump fault li...

Страница 7: ...h Level 240VAC Pump P1 1 2 Main Isolator MSW1 ME 20 BMS SIGNAL IN POWER IN 9 12V DC AC PUMP 2 FAULT PUMP 1 FAULT HIGH LEVEL POWER VOLTAGE FREE CONTACTS PCB BMS 1 Common C1 Aux NO C1 Power On High Leve...

Страница 8: ...A low level alarm is present ON STEADY A pump fault overload has occured FLASHING A prime loss fault has occured ON STEADY Pump switched on to run DISTRIBUTED BY 8 INSTALLATION DATE SERIAL NUMBER AT A...

Отзывы: