7. STORAGE AND CARE
If necessary, use a soft clean cloth to clean the MLI Ultra. Never use any liquids or acids.
The battery should be stored in a dry and well-ventilated environment. The rate of self-discharge is less
than 3% per month. High or low ambient temperature affects the self-discharge rate of the batteries and
natural aging.
If the battery will not be used for a period exceeding 3 months, we advise the following:
•
If external AC power is available switch off all loads and switch on the charger. Apply a float voltage
as specified in the following table.
Model Float voltage setting
12V
13.5V
24V
27.0V
•
If no external AC power is available:
-
Charge the battery to > 80% of its capacity before storage.
-
Long press the Battery switch-button to open the safety relay, see page 7.
-
Make sure MasterBus powering is not set to "Always on" (see Configuration tab in MasterAdjust).
CAUTION!
In this setup the batteries can be kept at least 6 months without maintenance. However, it is
highly recommended to charge the battery to over 80% of its capacity every 100 days.