The Configured Battery Cluster Topology window appears.
7. Enter the number of batteries in series (S). If there are no batteries in series, enter 1.
8. Enter the number of batteries in parallel (P). If there are no batteries in parallel, enter 1.
9. To activate voltage balancing of all cells in series, select ON from the Series Balancing drop-down
list.
10. Click the
OK
button to return to the Advanced Settings window.
11. Click the
OK
button to return to the Module Modifications window and then click the
Alarm/Switch
Settings
button.
12. The Battery Alarm/Switch Settings window appears. To copy these settings from the Primary
battery to all secondary batteries, tick
Apply to cluster
.
13. Keep clicking
OK
until all dialog windows have disappeared.
14. Write the configuration to the network to use the new configuration.
To identify the Primary battery, go to the Meters tab. The battery with two DC instances is the Primary
battery.