REMEDY
1..Check. voltage. to. electrical.
outlet.. If. voltage. is. good,.
check.heater.power.cord.for.
breaks
2..Adjust. thermostat. to. higher.
setting
3..Wait.for.ambient.temperature.
to.decrease
4..Replace.motor..See.
Motor and
Blower Assembly
,.page.13
1..Repeat. installation. and. op-
eration. instructions.. See.
Installation
,. page. 10. and.
Operation
,.page.11
2.
. A).Check.ignitor.wire..Tighten.
or.reattach.loose.ignitor.wire.
B) Assure gap between ignitor
electrode.and.burner.deck.is.
0.13"/0.15".(3.3/3.8.mm)..Do.
not.bend.electrode..Doing.so.
may.cause.it.to.break
. C). Replace. ignitor. elec-
trode.. See.
Replacing Ig
-
nitor
,.page.15
. D). Replace. spark. trans-
former..See.
Replacing DSI
Control
,.page.15
3..Clean.tubing
POSSIbLE CAUSE
1..No.electrical.power.to.heater
2..Thermostat.set.too.low
3..Ambient. temperature. is. too.
high.. Thermostat. is. satis-
fied
4..Defective.motor
1..User.did.not.follow.installa-
tion.or.operation.instructions.
properly
2..No. spark. at. ignitor.. To. test.
for.spark,.follow.step.5.under.
Replacing Ignitor
,.page.15..If.
you.see.spark.at.ignitor,.have.
heater serviced by qualified
service. person.. If. no. spark.
seen:
. A). Loose. or. disconnected.
ignitor.wire
B) Wrong spark gap
C) Bad ignitor electrode
D) Bad spark DSI
3..Air.proving.switch.blocked
ObSERVED FAULT
Fan. does. not. turn. when.
switch(s).1.or.2.are.pressed.
to.ON
Heater.will.not.ignite
TroUBLeSHooTing
WARNING: Never service heater while it is plugged in, connected
to propane supply, operating, or hot. Severe burns and electrical
shock can occur.