54
User Manual
55
User Manual
Menu
Level 1
Default
Selection
Comment
Menu
Level 2
Menu
Level 3
Menu
Level 4
Menu
Level 5
Menu
Level 6
Shows the user what was
generated today.
Shows the user what was
generated this month.
Shows the user what was
generated this year.
Shows the user what has
been generated sinced the
system was installed.
PV: xx kWh
Meter: xx kWh
Grid: xx kWh
Load: xx kWh
Charge: xx kWh
Discharge: xx kWh
PV: xx kWh
Meter: xx kWh
Grid: xx kWh
Load: xx kWh
PV: xx kWh
Meter: xx kWh
Grid: xx kWh
Load: xx kWh
PV: xx kWh
Meter: xx kWh
Grid: xx kWh
Load: xx kWh
Charge: xx kWh
Discharge: xx kWh
E-Today
E-Month
E-Year
E-Total
5 Battery storage and recharging
5.1 Battery storage requirements
1. Storage environment requirements:
•
Ambient temperature: 0°C ~ 40°C; recommended storage temperature: 20°C ~ 30°C.
•
Relative humidity: 0% RH ~ 90% RH.
•
In a dry, ventilated and clean place.
•
No contact with corrosive organic solvents, gases and other substances.
•
No direct sunlight.
•
Less than 2 meters from any heat source.
5.2 Storage expiration
In principle, it is not recommended to store the battery for a long time. Be sure to use it in time. The
stored batteries should be disposed according to the following requirements.
Table 5.2 Stored lithium battery recharging interval
1.
If a battery is deformed, broken or leaking, discard it immediately regardless of its storage time.
2.
The allowable maximum stored battery recharging period is 3 years and the allowable maximum
stored battery recharging times is 3. For example, if recharging is performed once every 8
months, the allowable maximum recharging times is 3 times; if recharging is performed once
every 12 months, the allowable maximum recharging times is 3 times; if the allowable maximum
stored battery recharging period or times is exceeded, it is recommended to discard the battery.
3.
A lithium battery will have its capacity decreasing after being stored for a long time, and typically
will have its capacity irreversibly decreasing by 3%–10% after being stored at the recommended
storage temperature for 12 months. If the customer conducts the discharge test and acceptance
according to the specification, there is a risk that the battery with a capacity less than 100%
after being stored will fail the test.
5.3 Inspection before battery recharging
Before recharging a battery, check its appearance: Deformation/Shell damage/Leakage.
0°C ~ +40°C
Required Storage Temperature
Actual Storage Temperature
Recharge Interval
0°C
≤ T ≤ 30
°C
30°C
< T ≤ 40
°C
12 months
8 months