38
Step 1
- Turn on the battery switch on the battery pack.
Step 2
- Press power button on all the batteries until the indicator lights turn on.
Step 3
- Turn on the external PV switch.
Step 4
- Turn on the external grid switch.
Step 5
- If backup load is applied, turn on the external Backup switch.
NOTE:
The Backup switch is only used when a backup load is applied.
Step 6
- Open the battery switch cover and turn on the battery switch on the cable box of inverter.
Step 7
- Close the battery switch cover and the outer shell of the cable box.
NOTE:
If PV = 0V under sunshine, please check whether PV is connected reversely or whether the
circuit is normal.
NOTE:
Appliances such as air conditioner are required at least 2-3 minutes to restart because it is
required to have enough time to balance refrigerant gas inside of circuit. If a power shortage
occurs and recovers in short time, it will cause damage to your connected appliances. To
prevent this kind of damage, please check manufacturer of air conditioner if it is equipped with
time-delay function before installation. Otherwise, this inverter will trigger overload fault and
cut off output to protect your appliance but sometimes it still causes internal damage to the air
conditioner.
3.2 Switch O
ff
Step 1
- Open cable box outer shell on the inverter, open the battery switch cover and turn off the
battery switch.
Step 2
- Turn off the external grid switch.
Step 3
- If backup load is applied, turn off the external backup switch.
Step 4
- Turn off the external PV switch on the cable box.
Step 5
- Open cable box outer shell beside the battery pack, open the battery switch cover and turn
off the battery switch.
Step 6
- Press the power button on all the batteries, till the lights turn off.
Step 7
- Close the battery switch cover and the outer shell of cable box.
3.3 Emergency Procedure
When the GreenE 8K/10K/12K energy storage system appears to be running abnormally, you can turn
off the grid-connected main switch that directly feeding the BESS, and turn off all load switches within
User Manual
39
the BESS, turn off the battery switch at the same time. To prevent a potentially fatal personal injury, if
you want to repair or open the machine after the power is switched off, please measure the voltage at
the input terminals with a suitably calibrated voltage tester. Before working on this equipment, please
confirm that there is no grid electric supply to the BESS! The upper cover plate cannot be opened until
the DC-link capacitance inside the battery modules discharges completely about 15 minutes later.
3.3.1 Emergency Handling Plan
1. Disconnect the AC breaker.
2. Check the control power supply. If it is OK, return the power supply to find out the reason.
3. Please record every detail related to the fault, so Company can analyse and solve the fault. Any
operation of equipment during a fault is strictly forbidden, please contact Company as soon as
possible.
4. As battery cells contain a little Oxygen inside and all cells have got explosion-proof valves, explosion
hardly happens.
5. When the indicator light on the battery shows a red fault, check the fault type through the
communication protocol, and contact our after-sales service personnel for advice.
3.3.2 Hazards
If the battery pack leaks electrolyte, avoid contact with the leaking liquid or gas. If one is exposed to
the leaked substance, immediately perform the actions described below:
Inhalation:
Evacuate the contaminated area, and seek medical attention.
Eye contact:
Rinse eyes with running water for 5 minutes, and seek medical attention.
Contact with skin:
Wash the affected area thoroughly with soap and water, and seek medical
attention.
Ingestion:
Induce vomiting and seek medical attention.
3.3.3 Fire
If a fire breaks out in the place where the battery pack is installed, perform the following countermeasures:
Fire extinguishing media
During normal operation, no respirator is required. Burning batteries can’t be extinguished with a
regular fire extinguisher, this requires special fire extinguishers such as the Noves 1230, the FM-200
or a dioxin extinguisher. If the fire is not from a battery, normal ABC fire extinguishers can be used for
extinguishing.
Fire -fighting instructions
1. If fire occurs when charging batteries, if it is safe to do so, disconnect the battery pack circuit
breaker to shut off the power to charge.
2. If the battery pack is not on fire yet, extinguish the fire before the battery pack catches fire.
3. If the battery pack is on fire, do not try to extinguish but evacuate people immediately.
There may be a possible explosion when batteries are heated above 150°C. When the battery
pack is burning, it leaks poisonous gases. Do not approach.