Model: PM-2160-A
Doc. Ref. no. : - m20Aom201
Issue no. 02
Page 7 of 36
User’s Manual
2. SPECIFICATIONS
System type
3Ph4W/ 3Ph3W (Site selectable)
Input
Voltage
Direct Voltage
20 to 350V (L-N) or 34V to 620V (L-L)
@ 240V Nominal Voltage
PT Secondary
(Nominal Voltage)
64V L-N, 110V L-N, 120V L-N or 240V L-N (Site selectable)
Configurable for 3Ph3W or 3Ph4W system
Measurement Method
True RMS
Burden
<0.2VA per phase
Wire gauge
16 AWG
PT Ratio
1 to 9999.999 Programmable
Overload
1.2 x Nominal Voltage (Continuous)
Current
Secondary Current
1A or 5A (Site selectable)
Measurement Method
True RMS
Burden
<0.2VA per phase
Wire gauge
16 AWG
CT Ratio
1 to 9999.999 Programmable
Overload
For 5A CT: 8A Continuous/ 20A for 1Sec
For 1A CT: 2A Continuous/ 20A for 1Sec
Starting current
0.1% of Nominal Current (class 0.5)
Frequency
45 to 65Hz
Display
LED
4 line 4 digit 0.4” [10mm] 7-segment Display
[3 line 4 digit in Red & 1 line 4 digit in Green]
3mm Round LED for Parameter Indication
Bar type LED for „-„ indication & % Load
LCD Panel
Large multi-line backlit LCD Panel
3 lines of 7 digits
– Height: 9.1 x Width: 5.15 mm
last line of 9 digits
– Height: 7 x Width: 3.97 mm
Bar Graph for % Load for each phase
Measured Parameters
Voltage
L1-L2, L2-L3, L1-L3 and Average (3Ph3W & 3Ph4W)
L1-N, L2-N, L3-N & average (1Ph & 3Ph4W)
Current
All phase currents & their average (mA, A, KA)
Frequency
System Frequency
Power Factor
Phase wise PF & Average PF
Power
(Phase wise & Total)
Active Power (W, KW & MW)
Reactive Power (VAR, KVAR & MVAR)
Apparent Power (VA, KVA & MVA)
Energy
(Phase wise & Total)
Active Energy for Import & Export (Separate)
(WH, KWh, MWh&GWh)
Reactive Energy for Import & Export (Separate)
(VARh, KVARh, MVARh&GVARh)
Apparent Energy (VAh, KVAh, MVAh&GVAh)
Demand
Maximum Demand on KW/KVA (Block/Sliding for 15/30 minutes
window)
Power Quality
Harmonics for each Voltage and Current (3rd to 15th odd)
THD for Voltage & Current (Phase wise)