background image

Model: PM-2160-A 

 

 

Doc. Ref. no. : m20Aom201 
Issue no. 02 
 

 
User’s Manual                                                                                                               

Page 34 of 36 

Energy Calculation 

Below formula used for finding the Total Active Energy Import. 
 

Total Active Energy = [Running Active Energy (Import) + (WH-I Ov.count * 400G)] 
(Import)

 

 

 

Example

Let‟s   WH-I Ov.count = 5, Active[Im] = 20.3268 GWh then 
 
Actually measured Total Active Energy (Import)  = [20.3268 G + (5 * 400G)] 
                                                                        = 2020.3268 GWh 

 

Above  calculation  is  same  for  other  energy  (Active  Export,  Reactive  Import,  Reactive 
Export,  and  Apparent  Energy)  can  be  find  out  using  respective  Ov.count  and  running 
energy. 

 

Energy Overflow Time Calculation 

 

When data type selected for modbus is FLOAT, Total apparent Energy will overflow from 
400GVAhr  then  auto  reset  Apparent  Energy,  but  when  the  ov.count  of  this  energy  (VA 
Ov.count  >  99)  then  meter  will  auto  reset  all  energy  parameter.  This  includes  Active 
import and export energy, Reactive Import and Export energy and apparent energy. Such 
condition of overflow occurrence is depending on CT ratio and PT ratio. 

Example

For 110V V rated, and 1 A I rated multifunction meter is set for 100A and 66KV line with 
CT Ratio of 100 and PT Ratio of 600. 

 

PT Primary = 66KV, PT Secondary = 110V Therefore select Vrated = 110V.  

PTR

 = 66KV/110V=600 select. 

CT Primary=100A, CT Secondary=1A Therefore select Irated = 1A.  

CTR

 = 100A/1A=100 select in meter. 

 

Energy consumed per hour will be 66kV X 100Amps = 6600KVAHr. 

 

Time to overflow in Hr. = 400GVAhr / 6600KvaHr = 60606 Hr 

 

Days = 60606 /24 = 2525 Days 

 

Years = 2525 / 365 = 6.91 Years / Total of Three Phase. 

 

But our Apparent Energy Overflow Count Range are 1 to 99, therefore 

 

Total Time to overflow in Years = 6.91*99 = 684.09 Years / Total of Three Phase. 

 

User has to manually reset 

All Regs Rst, 

when installing the meter first time. 

 

As above for 100A and 66KV line, PT Primary = 66KV, PT Secondary = 110V   Therefore          
Vrated = 110V select. PTR = 66KV/110V=600 select. 

 

CT Primary=100A, CT Secondary=1A Therefore Irated = 1A select. CTR = 100A/1A=100   
select in meter. 
 

Energy Resolution on Modbus 

 

Resolution  of  the  energy  parameter  on  the  Modbus  when  data  is  transmitted  in  LONG 
format  is  100VAhr/Whr/VARhr  rather  than  1VAhr/Whr/VARhr,  which  is  possible  when 
FLOAT  data  type  is  used.  Because  of  the  limitation  of  the  Long  Data  type  and  to  avoid 
frequent reset, Data is transmitted in with above-mentioned resolution. 

 

Due to this resolution on display of the Meter will not be same as ON ModBus data, when 
data is transmitted in LONG format. Multiplication factor given on master side is 0.0001. 

 

Example

 

Lets say on modbus data transmitted is 20098798 then on the master side it will be 

 

20098798 * 0.0001 = 2009.8798 MWhr/MVAhr/MVARhr. 

 

Which 

gives 

the 

resolution 

of 

the 

0.1KWhr/KVAhr/KVARhr 

as 

described                                               

above. 

 

 

 

Содержание PM2160-A

Страница 1: ...B 30 GIDC Electronics Estate Sector 25 Gandhinagar 382044 Gujarat India 91 79 23287275 79 91 79 23287281 82 Email support masibus com Web www masibus com User s Manual M MU UL LT TI IF FU UN NC CT TI...

Страница 2: ...el Picture 12 3 2 Rear Panel Picture 13 4 TERMINAL CONNECTIONS 14 4 1 Rear Panel Terminal Connections 14 5 MECHANICAL GUIDELINE 15 5 1 Front Bezel Diagram 15 5 2 Panel Cutout Diagram 15 6 INSTALLATION...

Страница 3: ...no m20Aom201 Issue no 02 Page 3 of 36 User s Manual Display Details for Run Mode and Configuration Mode 36 1 Annexure A2 Display Details for LED based PM2160 A 36 2 Annexure A3 Display Details for LCD...

Страница 4: ...hout notice as a result of continuous improvements to the instrument s performance and functions This manual describes the functions of this product MASIBUS does not guarantee the application of these...

Страница 5: ...eature even after Power On Off Light weight Rugged Reliable Safe for User Aux powered uses Switch mode power supply 4 lines 4 digit high visibility LED display 0 4 10mm to display various parameters O...

Страница 6: ...manual 1 Safety Precautions The product and the instruction manual describe important information to prevent possible harm to users and damage to the property and to use the product safely Understand...

Страница 7: ...D 4 line 4 digit 0 4 10mm 7 segment Display 3 line 4 digit in Red 1 line 4 digit in Green 3mm Round LED for Parameter Indication Bar type LED for indication Load LCD Panel Large multi line backlit LCD...

Страница 8: ...2 of FS 0 5 of reading 0 02 of FS 1 0 of reading 0 02 of FS Active Energy Class 0 2s as per IS14697 IEC 62053 22 Class 0 5s as per IS14697 IEC 62053 22 Class 1 0 as per IS13779 IEC 62053 21 Reactive E...

Страница 9: ...M 100KWh X XXX G 1MWh XX XX G 10MWh XXX X G 100MWh Sys Energy Resolution Display Format Unit Last Digit Resolution X XXXXX K 0 01Wh XX XXXXX K 0 01Wh XXX XXXXX K 0 1Wh X XXXXXXX M 1Wh XX XXXXXX M 1Wh...

Страница 10: ...K 0 01Wh XXX XXXX K 0 1Wh X XXXXXX M 1Wh XX XXXXX M 10Wh XXX XXXX M 100Wh X XXXXXX G 1KWh XX XXXXX G 10KWh XXX XXXX G 100KWh Sys Energy Resolution Display Format Unit Last Digit Resolution X XXXXX K 0...

Страница 11: ...emand with Date Time Rising Demand Harmonics THD Harmonics Up to 15th Odd C Hour ON Hour Load Hour RUN Hour Total Idle Hour C Load Hour RUN Hour Import Load Hour RUN Hour Export Power Interruption Pow...

Страница 12: ...even Segment LED Display For LCD Panel Display Fig 3 1 Detail of front panel PGM ENT key RUN mode Key press is used to enter into PGM mode view mode PGM mode On key press If in view mode goes into edi...

Страница 13: ...in edit mode used to shift to the next digit UP INCREMENT key RUN mode Key press is used to move from one frame to the other vertically up PGM mode Increment value in edit mode Move UP to next configu...

Страница 14: ...2 RS 485 B 3 IB Current In B Phase Three Phase Current Inputs 4 IB Current Out B Phase 5 IY Current In Y Phase 6 IY Current Out Y Phase 7 IR Current In R Phase 8 IR Current Out R Phase 9 L Line Aux Po...

Страница 15: ...Model PM 2160 A Doc Ref no m20Aom201 Issue no 02 Page 15 of 36 User s Manual 5 MECHANICAL GUIDELINE 5 1 Front Bezel Diagram 5 2 Panel Cutout Diagram All Dimensions are in mm...

Страница 16: ...he instrument to the power source check the labels on the instrument to ensure that your instrument is equipped with the appropriate power supply voltage input voltages and currents Failure to do so m...

Страница 17: ...as excessive shock vibration dirt moisture corrosive gases or rain The ambient temperature of the areas should not exceed the maximum rating specified 6 2 Common Wiring with RS 485 Connections Recomm...

Страница 18: ...M 2160 A Doc Ref no m20Aom201 Issue no 02 User s Manual Page 18 of 36 6 3 1 Three Phase Four Wire System a 4 Wire Wye 3 Element Connection Using 3PTs 3CTs b 4 Wire Wye 3 Element Direct Connection Usin...

Страница 19: ...Model PM 2160 A Doc Ref no m20Aom201 Issue no 02 Page 19 of 36 User s Manual c 4 Wire Direct Connection 6 3 2 Three Phase Three Wire System a 3 Wire 2 Element Open Delta Connection Using 2PTs 2CTs...

Страница 20: ...s Manual Page 20 of 36 b 3 Wire 2 Element Direct Connection Using 2CTs 6 3 3 Single Phase Two Wire Configuration Note For Single Phase Two Wire system should be 3P4W and Do not consider Average Voltag...

Страница 21: ...poor accuracy and phase characteristics Ensure that the CT primary rating has been selected so that your normal load variation lies between 40 and 80 of its full scale If your CT is over rated say if...

Страница 22: ...ple of 2 as all data are of 4 Bytes Long Real Enter only Even value data word length Response 0 x Slave Id 0 x Fun Code Byte count Data High Data Low Data High Data Low 0 x CRC Low 0 x CRC High Data F...

Страница 23: ...7 3 Varh Export 2 0 1 45 30089 T Varh Export 2 0 1 46 30091 1 Vah 2 0 1 47 30093 2 Vah 2 0 1 48 30095 3 Vah 2 0 1 49 30097 T Vah 2 0 1 50 30099 Rising Demand 2 0 1 51 30101 Real Date 2 52 30103 Real T...

Страница 24: ...01 14 30226 13th VyHar 2 0 01 15 30228 15th VyHar 2 0 01 16 30230 Total Vythd 2 0 01 17 30232 3rd VbHar 2 0 01 18 30234 5th VbHar 2 0 01 19 30236 7th VbHar 2 0 01 20 30238 9th VbHar 2 0 01 21 30240 1...

Страница 25: ...of 2 as all data are of 4 Bytes Long Real Enter only Even value data word length Data Format long Real S No Address Measured parameter words Multiplication Factor if data type is long 1 30350 Power O...

Страница 26: ...31 30061 Reserved 32 30063 3_2 Wh Import 2 0 1 33 30065 T Wh Import 2 0 1 34 30067 1_2 Wh Export 2 0 1 35 30069 Reserved 36 30071 3_2 Wh Export 2 0 1 37 30073 T Wh Export 2 0 1 38 30075 1_2 Varh Impor...

Страница 27: ...1 11 32021 S Var S Var 2 1 12 32023 S VA S VA 2 1 13 32025 T Wh Import T Wh Import 2 0 1 14 32027 T Wh Export T Wh Export 2 0 1 15 32029 T Varh Import T Varh Import 2 0 1 16 32031 T Varh Export T Var...

Страница 28: ...2 0 01 24 30246 Total Vbthd 2 0 01 25 30248 3rd IrHar 2 0 01 26 30250 5th IrHar 2 0 01 27 30252 7th IrHar 2 0 01 28 30254 9th IrHar 2 0 01 29 30256 11th IrHar 2 0 01 30 30258 13th IrHar 2 0 01 31 3026...

Страница 29: ...us master Note Energy will be in Kilo for Real data type and for Long data type multiply with constant stated to get energy in Kilo unit Note Ignore address which are not mentioned in the memory map a...

Страница 30: ...PF3 type read only value 1 0 2 9 40109 Total PF type read only value 1 0 2 10 40110 2 CT Ratio High byte 1 11 40111 2 CT Ratio low byte 1 12 40112 2 PT Ratio high byte 1 13 40113 2 PT Ratio low byte 1...

Страница 31: ...four byte D687 at 40111 and higher four byte 0012 at 40110 addresses respectively PF type has three options 0 Unity 1 Lag 2 Lead NOTE MODBUS Time out 4 Sec or more 7 4 Exception Responses Exception re...

Страница 32: ...ave address etc you have to use function code 03 Here the addressing allows up to Maximum 24 registers Words to be obtained at each request 7 4 2 Preset Single Register Function Code 06 Function 06 wi...

Страница 33: ...D IDLE Display two quantity Hours and Minute Power Interruption Count Number of Supply Outages means the number of Auxiliary Supply interruptions If the meter Auxiliary Supply is from a UPS then the I...

Страница 34: ...Secondary 1A Therefore select Irated 1A CTR 100A 1A 100 select in meter Energy consumed per hour will be 66kV X 100Amps 6600KVAHr Time to overflow in Hr 400GVAhr 6600KvaHr 60606 Hr Days 60606 24 2525...

Страница 35: ...ed for Multifunction meter setup parameters CT and PT ratings System Type Incorrect voltage inputs Check Multifunction meter voltage input terminals to verify that adequate voltage is present Multifun...

Страница 36: ...Ref no m20Aom201 Issue no 02 User s Manual Page 36 of 36 Display Details for Run Mode and Configuration Mode 1 Annexure A2 Display Details for LED based PM2160 A 2 Annexure A3 Display Details for LCD...

Отзывы: