Model: PM-2160-A
Doc. Ref. no. : - m20Aom201
Issue no. 02
Page 27 of 36
User’s Manual
61
30121
Reserved
2
0.01
Modbus map for 3P4W & 3P3W:
Function Code
= 0X04
Address
– between 32001 to 32033
No. of data word
≤ 34 & in multiple of 2 as all data are of 4 Bytes [Long & Real].
[Data Format:
long & Real
]
S. No.
Address
Measured parameter
words
Multiplication Factor
3P4W
3P3W
(if data type is long)
1
32001
Frequency
Frequency
2
0.01
2
32003
1. Vrms
Vrms 1*2
2
0.1
3
32005
2. Vrms
Vrms 3*1
2
0.1
4
32007
3. Vrms
Vrms 2*3
2
0.1
5
32009
A. Vrms
A_Vrms
2
0.1
6
32011
1. Irms
1. Irms
2
0.001
7
32013
2. Irms
Reserved
2
0.001
8
32015
3. Irms
3. Irms
2
0.001
9
32017
A. Irms
A. Irms
2
0.001
10
32019
S. Watt
S. Watt
2
1
11
32021
S. Var
S. Var
2
1
12
32023
S. VA
S. VA
2
1
13
32025
T. Wh-Import
T. Wh-Import
2
0.1
14
32027
T. Wh-Export T. Wh-Export
2
0.1
15
32029
T. Varh-
Import
T. Varh-
Import
2
0.1
16
32031
T. Varh-
Export
T. Varh-
Export
2
0.1
17
32033
T. Vah
T. Vah
2
0.1
Energy Overflow Count:
Function Code
= 0X04
Address
– between 30150 to 30154
No. of data word
≤ 5 & in multiple of 1 as all data are of 2 Bytes [Decimal].
[Data Format:
Only in Decimal
]
S. No.
Address Measured parameter
words
Multiplication Factor
(if data type is long)
1
30150
Wh I -ovcnt
1
-
2
30151
Wh E-ovcnt
1
-
3
30152
VARh I-ovcnt
1
-
4
30153
VARh E-ovcnt
1
-
5
30154
VAh -ovcnt
1
-
Harmonics:
Function Code
= 0X04
Address
– between 30200 to 30294
No. of data word
≤ 96 & in multiple of 2 as all data are of 4 Bytes [Long & Real].
[Data Format:
long & Real
]
S. No.
Address Measured parameter
words
Multiplication Factor
(if data type is long)
1
30200
3rd VrHar
2
0.01