background image

Model: PM-2160-A 

 

 

Doc. Ref. no. : m20Aom201 
Issue no. 02 
 

 
User’s Manual                                                                                                               

Page 32 of 36 

Example  

Query Message 

 SLAVE 
ADDR 

FUNCTION 
CODE 

H.O 
START 
ADDR 

L.O 
START 
ADDR 

H.O  NO 
OF REG 

L.O  NO 
OF REG 

ERROR 
CHECK 
FIELD 

ERROR 
CHECK 
FIELD 

0x0A 

0x01 

0x00 

0x24 

0x00 

0x02 

0xFC 

0xBB 

The query requests the status of  input 0036 in slave no. 10. Since the function is an invalid function 
for 2160-A, so the following error response will be generated. 

Response Message 

SLAVE 
ADDR 

FUNCTION 
CODE 

EXCEPTION 
CODE 

ERROR 
CHECK 

ERROR 
CHECK 

0x0A 

0x81 

0x01 

0xF0 

0x52 

 
The  function  field  is  the  original  function  code  with  the  high  order  bit  set  and  exception  code  01 
indicates an illegal function field. 

When  slave  device  that  is  Multifunction  meter  is  in  the  PROGRAM  mode,  a  busy  state  is 
transmitted indicating that slave device is busy and the master should retransmit the message 
later when the slave is free. So here exception code 0x06 is transmitted. Response message is 
shown below. 

 

 

Response Message 

 

SLAVE 
ADDR 

FUNCTION 
CODE 

EXCEPTION 
CODE 

ERROR 
CHECK 

ERROR 
CHECK 

Device ID 

Fun.  Code 
+ 0x80 

    0x06 

0xC3 

0x02 

7.4.1 Read Holding Register (Function Code 03) 

 

To  get  value  of  configuration  parameters  (CT  Ratio,  PT  Ratio,  Pls/KWh,  Baud,  Slave  address  etc.), 
you have to use function code 

03. 

Here the addressing allows up to Maximum 

24 

registers (Words) to 

be obtained at each request. 

7.4.2 Preset Single Register (Function Code 06) 

 

Function (06) will overwrite controller memory. 
 
Function (06) allows the user to modify the contents of a holding register for configuration parameter. 
The  values  are  provided  in  binary,  up  to  the  maximum  capacity  of  the  controller  and  unused  higher 
bits must be set to zero. 

Example 

 

This example will set the CT Ratio value in slave number 17. Here CT Ratio and PT ratio requires 2 
integer  register  for  each.  So  you  should  write  higher  integer  and  lower  integer  value  to  get  whole 
Ratio value. Suppose you want to write CT RATIO = 5,then you have to take 5000 to write because in 
unit side this 5000 will be divided by 1000 i.e. you will get 5.Now Hex value of 5000 is 0x1388,so you 
will  take  0x00  for  higher  integer  register  and  0x1388  for  lower  integer  register.  The  address  of  CT 
Higher integer is 0x6D and value to be programmed is 0x0000. 
 
Similarly you can do for lower integer and also for PT RATIO. The normal response to a preset single 
register request is to transmit the query message after the register has been altered, 
 
If  the  value  is  an  illegal  value  then  the  response  message  will  be  an  exception  response  (Error 
Message). For the details of maximum and minimum values of any parameter refer to manual. 

 

 

Содержание PM2160-A

Страница 1: ...B 30 GIDC Electronics Estate Sector 25 Gandhinagar 382044 Gujarat India 91 79 23287275 79 91 79 23287281 82 Email support masibus com Web www masibus com User s Manual M MU UL LT TI IF FU UN NC CT TI...

Страница 2: ...el Picture 12 3 2 Rear Panel Picture 13 4 TERMINAL CONNECTIONS 14 4 1 Rear Panel Terminal Connections 14 5 MECHANICAL GUIDELINE 15 5 1 Front Bezel Diagram 15 5 2 Panel Cutout Diagram 15 6 INSTALLATION...

Страница 3: ...no m20Aom201 Issue no 02 Page 3 of 36 User s Manual Display Details for Run Mode and Configuration Mode 36 1 Annexure A2 Display Details for LED based PM2160 A 36 2 Annexure A3 Display Details for LCD...

Страница 4: ...hout notice as a result of continuous improvements to the instrument s performance and functions This manual describes the functions of this product MASIBUS does not guarantee the application of these...

Страница 5: ...eature even after Power On Off Light weight Rugged Reliable Safe for User Aux powered uses Switch mode power supply 4 lines 4 digit high visibility LED display 0 4 10mm to display various parameters O...

Страница 6: ...manual 1 Safety Precautions The product and the instruction manual describe important information to prevent possible harm to users and damage to the property and to use the product safely Understand...

Страница 7: ...D 4 line 4 digit 0 4 10mm 7 segment Display 3 line 4 digit in Red 1 line 4 digit in Green 3mm Round LED for Parameter Indication Bar type LED for indication Load LCD Panel Large multi line backlit LCD...

Страница 8: ...2 of FS 0 5 of reading 0 02 of FS 1 0 of reading 0 02 of FS Active Energy Class 0 2s as per IS14697 IEC 62053 22 Class 0 5s as per IS14697 IEC 62053 22 Class 1 0 as per IS13779 IEC 62053 21 Reactive E...

Страница 9: ...M 100KWh X XXX G 1MWh XX XX G 10MWh XXX X G 100MWh Sys Energy Resolution Display Format Unit Last Digit Resolution X XXXXX K 0 01Wh XX XXXXX K 0 01Wh XXX XXXXX K 0 1Wh X XXXXXXX M 1Wh XX XXXXXX M 1Wh...

Страница 10: ...K 0 01Wh XXX XXXX K 0 1Wh X XXXXXX M 1Wh XX XXXXX M 10Wh XXX XXXX M 100Wh X XXXXXX G 1KWh XX XXXXX G 10KWh XXX XXXX G 100KWh Sys Energy Resolution Display Format Unit Last Digit Resolution X XXXXX K 0...

Страница 11: ...emand with Date Time Rising Demand Harmonics THD Harmonics Up to 15th Odd C Hour ON Hour Load Hour RUN Hour Total Idle Hour C Load Hour RUN Hour Import Load Hour RUN Hour Export Power Interruption Pow...

Страница 12: ...even Segment LED Display For LCD Panel Display Fig 3 1 Detail of front panel PGM ENT key RUN mode Key press is used to enter into PGM mode view mode PGM mode On key press If in view mode goes into edi...

Страница 13: ...in edit mode used to shift to the next digit UP INCREMENT key RUN mode Key press is used to move from one frame to the other vertically up PGM mode Increment value in edit mode Move UP to next configu...

Страница 14: ...2 RS 485 B 3 IB Current In B Phase Three Phase Current Inputs 4 IB Current Out B Phase 5 IY Current In Y Phase 6 IY Current Out Y Phase 7 IR Current In R Phase 8 IR Current Out R Phase 9 L Line Aux Po...

Страница 15: ...Model PM 2160 A Doc Ref no m20Aom201 Issue no 02 Page 15 of 36 User s Manual 5 MECHANICAL GUIDELINE 5 1 Front Bezel Diagram 5 2 Panel Cutout Diagram All Dimensions are in mm...

Страница 16: ...he instrument to the power source check the labels on the instrument to ensure that your instrument is equipped with the appropriate power supply voltage input voltages and currents Failure to do so m...

Страница 17: ...as excessive shock vibration dirt moisture corrosive gases or rain The ambient temperature of the areas should not exceed the maximum rating specified 6 2 Common Wiring with RS 485 Connections Recomm...

Страница 18: ...M 2160 A Doc Ref no m20Aom201 Issue no 02 User s Manual Page 18 of 36 6 3 1 Three Phase Four Wire System a 4 Wire Wye 3 Element Connection Using 3PTs 3CTs b 4 Wire Wye 3 Element Direct Connection Usin...

Страница 19: ...Model PM 2160 A Doc Ref no m20Aom201 Issue no 02 Page 19 of 36 User s Manual c 4 Wire Direct Connection 6 3 2 Three Phase Three Wire System a 3 Wire 2 Element Open Delta Connection Using 2PTs 2CTs...

Страница 20: ...s Manual Page 20 of 36 b 3 Wire 2 Element Direct Connection Using 2CTs 6 3 3 Single Phase Two Wire Configuration Note For Single Phase Two Wire system should be 3P4W and Do not consider Average Voltag...

Страница 21: ...poor accuracy and phase characteristics Ensure that the CT primary rating has been selected so that your normal load variation lies between 40 and 80 of its full scale If your CT is over rated say if...

Страница 22: ...ple of 2 as all data are of 4 Bytes Long Real Enter only Even value data word length Response 0 x Slave Id 0 x Fun Code Byte count Data High Data Low Data High Data Low 0 x CRC Low 0 x CRC High Data F...

Страница 23: ...7 3 Varh Export 2 0 1 45 30089 T Varh Export 2 0 1 46 30091 1 Vah 2 0 1 47 30093 2 Vah 2 0 1 48 30095 3 Vah 2 0 1 49 30097 T Vah 2 0 1 50 30099 Rising Demand 2 0 1 51 30101 Real Date 2 52 30103 Real T...

Страница 24: ...01 14 30226 13th VyHar 2 0 01 15 30228 15th VyHar 2 0 01 16 30230 Total Vythd 2 0 01 17 30232 3rd VbHar 2 0 01 18 30234 5th VbHar 2 0 01 19 30236 7th VbHar 2 0 01 20 30238 9th VbHar 2 0 01 21 30240 1...

Страница 25: ...of 2 as all data are of 4 Bytes Long Real Enter only Even value data word length Data Format long Real S No Address Measured parameter words Multiplication Factor if data type is long 1 30350 Power O...

Страница 26: ...31 30061 Reserved 32 30063 3_2 Wh Import 2 0 1 33 30065 T Wh Import 2 0 1 34 30067 1_2 Wh Export 2 0 1 35 30069 Reserved 36 30071 3_2 Wh Export 2 0 1 37 30073 T Wh Export 2 0 1 38 30075 1_2 Varh Impor...

Страница 27: ...1 11 32021 S Var S Var 2 1 12 32023 S VA S VA 2 1 13 32025 T Wh Import T Wh Import 2 0 1 14 32027 T Wh Export T Wh Export 2 0 1 15 32029 T Varh Import T Varh Import 2 0 1 16 32031 T Varh Export T Var...

Страница 28: ...2 0 01 24 30246 Total Vbthd 2 0 01 25 30248 3rd IrHar 2 0 01 26 30250 5th IrHar 2 0 01 27 30252 7th IrHar 2 0 01 28 30254 9th IrHar 2 0 01 29 30256 11th IrHar 2 0 01 30 30258 13th IrHar 2 0 01 31 3026...

Страница 29: ...us master Note Energy will be in Kilo for Real data type and for Long data type multiply with constant stated to get energy in Kilo unit Note Ignore address which are not mentioned in the memory map a...

Страница 30: ...PF3 type read only value 1 0 2 9 40109 Total PF type read only value 1 0 2 10 40110 2 CT Ratio High byte 1 11 40111 2 CT Ratio low byte 1 12 40112 2 PT Ratio high byte 1 13 40113 2 PT Ratio low byte 1...

Страница 31: ...four byte D687 at 40111 and higher four byte 0012 at 40110 addresses respectively PF type has three options 0 Unity 1 Lag 2 Lead NOTE MODBUS Time out 4 Sec or more 7 4 Exception Responses Exception re...

Страница 32: ...ave address etc you have to use function code 03 Here the addressing allows up to Maximum 24 registers Words to be obtained at each request 7 4 2 Preset Single Register Function Code 06 Function 06 wi...

Страница 33: ...D IDLE Display two quantity Hours and Minute Power Interruption Count Number of Supply Outages means the number of Auxiliary Supply interruptions If the meter Auxiliary Supply is from a UPS then the I...

Страница 34: ...Secondary 1A Therefore select Irated 1A CTR 100A 1A 100 select in meter Energy consumed per hour will be 66kV X 100Amps 6600KVAHr Time to overflow in Hr 400GVAhr 6600KvaHr 60606 Hr Days 60606 24 2525...

Страница 35: ...ed for Multifunction meter setup parameters CT and PT ratings System Type Incorrect voltage inputs Check Multifunction meter voltage input terminals to verify that adequate voltage is present Multifun...

Страница 36: ...Ref no m20Aom201 Issue no 02 User s Manual Page 36 of 36 Display Details for Run Mode and Configuration Mode 1 Annexure A2 Display Details for LED based PM2160 A 2 Annexure A3 Display Details for LCD...

Отзывы: