Model: DDU-24/26
Doc. Ref. no. : - m06bom101
Issue no. 09
Page 28 of 51
User’s Manual
If DDU-24/26 is in sync using Serial [RS232/RS485] than do not use Serial
[RS232/RS485] for Retransmission.
6.2.3.15
Slave ID configuration:
Press Enter Key to Enter in Slave ID configuration, it will enter in View mode and shows
Current Slave ID of Unit.
Press Enter in View mode to enter in Edit mode, in Edit mode set Slave ID using INC
and SHIFT Keys, Press Enter key to set Slave ID.
6.2.3.13 Set Default Configuration (STDF):
Press Enter Key to set the default parameters and Default parameter as per below.
Display Type : Time Display
Time Format
: Hour Time Format 24
Date Format
: DD.MM
Time Zone Offset : 05:30
Applicable for Serial Input Model:
Baud Rate
: 9600
Stop Bit
: 1
Parity Bit
: None
Applicable for Wireless Input Model:
RFM Receive Channel
: 0
Display Unlock Blink
: BL.10
Password
: 0001
Retransmission : No
Slave ID
:XXXX[Between 0001 to 9998]
6.2.3.14 Set Ethernet Parameter Default Configuration of Ethernet (STDF):
Press Enter Key to set the default parameters of Ethernet and Default parameter as per
below.
Default Ethernet configuration(For NTP or NTP + PoE Input Model)
IP Address
: 192.168.100.032
Subnet mask
: 255.255.255.000
Gateway
: 192.168.100.001
Primary Server IP Address
: 192.168.100.153
Secondary Server IP Address
: 192.168.100.154
Query Interval Time [When Querying NTP Server] : 0016
Query Request Time out
: 02
Query Retry Interval
: 02
Number of Time outs before switching Servers
: 03
Secondary Server Option for NTP
: Disable
Note:
-
1. Default Setting of DDU-26 Same as above configuration but only change in Date Format. In
DDU-26 date Format is DD.MM.YY by Default.
2. Default Setting of DDU-24/26 with NTP or NTP +PoE Same as above configuration but only
change in Display Unlock Blink and Retransmission. In Display Unlock Blink is BLON. Slave ID,
Wirless configuration and Retransmission Features not available. Please ignore the Serial
Parameter in Default configuration menu if DDU-24/26 has order with only NTP or PoE option.
The configuration can be done through Telnet for this Option.
3. Ethernet Default configuration available for NTP or NTP + PoE model only.
4. Slave ID of Unit is set in Factory once. You can set Slave Id by Entering in Configuration Menu.
Slave ID will not change in Default Condition.