Model: CDU-LCD
Doc. Ref. no.:- mMP/om/601
Issue no.00.06
User’s Manual
Page 22 of 32
Table 8
8.4 Humidity
40021
Set Point
High
Adjust SET POINT High value
0 to 100 For %RH - 1% Resolution
55
40022
Set Point
Low
Adjust SET POINT Low value
0 to 100 For %RH -1% Resolution
30
40023
Alarm High
Set Alarm Type for Alarm HIGH
0 : HI(High)
1 : LOW(Low)
2 : DIS(Disable)
HIGH
40024
Alarm Low
Set Alarm Type for Alarm LOW
0 : HI(High)
1 : LOW(Low)
2 : DIS(Disable)
LOW
40028
Band
Set band for data logging
0 to 10 For %RH
– 1% Resolution
1
40033
Sensor
Break
Set Sensor Break Value
0 : MIN
(Display minimum value of humidity range)
1 : LAST
(Display Last value of parameter in CDU)
2 : MAX
(Display Maximum Value of humidity range)
LAST
Table 9
8.5 Differential Pressure
40041
Set Point
High
Adjust SET POINT High value
-990 to 5000 For Pa
– 0.1 Pascal Resolution
50
40042
Set Point
Low
Adjust SET POINT Low value
-990 to 5000 For Pa
– 0.1 Pascal Resolution
0
40043
Alarm High
Set Alarm Type for Alarm HIGH
0 : HI(High)
1 : LOW(Low)
2 : DIS(Disable)
HIGH
Break
0 : MIN
(Display minimum value of temperature range)
1 : LAST
(Display Last value of parameter in CDU)
2 : MAX
(Display Maximum Value of temperature range)