Strain Guage Indicator: 409-W
REF NO: m59A/om/501
Issue NO: 03
Page 10 of 34
0.001
to
0.255
Resolution = 0.000
0.0001
to
0.0255
Resolution = 0.0000
OPES
(
opes
)
OPEN Sensor
Status
Set Control O/P & Retransmission state when Input OPEN
condition.
0 :
UP
1 :
DOWN
U P
ST-1
(
st-1
)
Set Point 1
Range Depending on PV sensor type selected
1 0.0
ST-2
(
st-2
)
Set Point 2
Range Depending on PV sensor type selected
1 0.0
RDLY
(
rdLY
)
Relay Delay
(For Relay)
Relay Delay is amount of time (in sec), that Relay will wait
before getting ON after the ON condition occurs.
0
to
9999
sec
0 se c
CTRl
(
CTRL
)
Control Relay
Select Control Relay Status
0 :
ON
1 :
OFF
O FF
COM
Communication
SRNO
(
srno
)
Serial No
Unit ID for Modbus-RS485 Communication
1
to
247
1
BAUD
(
baud
)
Baud Rate
Set Modbus RS485 Communication Baud Rate
0 :
4800
(4800 bps)
1 :
9600
(9600 bps)
2 :
19.2K
(19200bps)
3 :
38.4K
(38400bps)
9600
PRST
(
PRST
)
Parity/Stop bit
Set Parity and Stop bit
0 :
PNS1
1 :
PNS2
2 :
POS1
3 :
POS2
4 :
PES1
5 :
PES2
PnS
1
FLTR
(
fltr
)
Filter
Filter is time (in sec), that PV will wait before getting to its
value after filter set.
0-60
sec
0
BRHT
Brightness
Adjust Brightness of the 7-segment Display.
100