Temperature Indicator : 409-4IN
REF NO: m47/om/201
Issue NO: 04
Page 27 of 34
*Alarm status1, *Alarm status2 gives status of abnormal condition only. Address
1006- 1016 for future use only
*Input type: 0 = Etc, 1 = Jtc, 2 = Ktc, 3 = Ttc,4 =Btc,5 =Rtc, 6 = Stc, 7= pt-100,8 = 0-
400Ω, 9 =0-6000Ω, 10 = ±10V, 11 = 0-10V, 12 = 0-5V, 13 = 1-5V,14 = 0-2V,15 = 0.4-
2V, 16 = -10-20mV, 17 = ±75mV, 18 = 0-75mV,22=Serial, 23=4-20mA,24=0-20mA
*Baud rate: 0 = 4800, 1 = 9600, 2 = 19200, 3 = 38400
*Alarm Latch: 0 = YES, 1 = NO
Alarm sensor: 0 =UP, 1=DOWN
*Relay control: 0 = ON, 1=OFF
*Alarm logic type: 0 = HH, 1 = HL, 2 = LL.
*Alarm 1: 0 = Alarm, 1 = Trip
*Alarm 2: 0 = Alarm, 1 = Trip.
Values when OPEN:
– 32767, UNDER: – 32765, OVER: – 32766.
*Decimal point: 0=0, 1= .0, 2=.00, 3=.000, 4=.0000
*Sqrt: 0 = YES, 1 = NO
*Filt: 0 = No Filter, 1-60 = Filter used.
*
Retransmission o/p: 0 = 0-5V, 1 = 1-5V , 2 = 0-10V , 3 = 4-20mA , 4 = 0-20mA
8.1.2 Parameter Address Details For
Mtyp
:
b
(405-4IN)
Sr.
No.
Analog
Param eters
Absolute
Address
T ype of
Access
T ype
Value
Applicable
1*
Process Value
40001
R/*W
Int
As Perspc. Table Of I/P
T ype Range
2
Set Value-1
40002
R/W
Int
Conf. Zero To Conf. Span
3
Setvalue-2
40003
R/W
Int
4
Set Value-1
Hysteresis
40004
R/W
Int
0
– 255 Count
5
Set Value-2
Hysteresis
40005
R/W
Int
6
Engineering Zero
40006
R/W
Int
Max Value As Perspc.
Table Of I/P T ype Range
7
Engineering Span
40007
R/W
Int
8
Decim al Position
40008
R/W
Unsigned
char
0 To 3
Table 13
* Absolute Address 40001 is Read/Write only if Serl prompt is made ‘YES’(Only serial
input). If Serl prompt is made ‘NO’ then absolute address 40001 is Read only.