Temperature Indicator : 409-4IN
REF NO: m47/om/201
Issue NO: 04
Page 17 of 34
Process value greater then maximum value of zero/span then display will show OPEN
message. Retransmission o/p will follow 5% of display range and then it will give fixed
o/p depending up on OPEN sensor selection. In case of linear inputs scaling is applied
then during OPEN sensor condition it may not show OPEN message instead it will
show either OVER/UNDER.
Retransmission output during OPEN sensor/Diode Open condition
I/P
0-20 mA O/P
4-20 mA O/P
UP Scale O/P
DW Scale O/P
UP Scale O/P DW Scale O/P
*TC
21.00
0.0
20.8
3.2
Pt-100
21.00
0.0
20.8
3.2
0~5V
21.00
0.0
3.2
3.2
1~5V
21.00
0.0
20.8
3.2
±75mV
21.00
0.0
20.8
3.2
0~75mV
21.00
0.0
20.8
3.2
0~10V
Random
Random
Random
Random
*±10V
Random
Random
Random
Random
0~2V
21.00
0.0
20.8
3.2
0.4~2V
21.00
0.0
20.8
3.2
-10~20mV
21.00
0.0
20.8
3.2
0~6000Ω
21.00
0.0
20.8
3.2
0~400Ω
21.00
0.0
20.8
3.2
Serial
21.00
0.0
20.8
3.2
4-20mA
21.00
0.0
20.8
3.2
0-20mA
21.00
0.0
3.2
3.2
Table 5A