Temperature Indicator: 409-4IN
REF NO: m47/om/201
Issue NO: 04
Page 12 of 34
Alrm
/
Trip
0 : ALRM
1 : TRIP
ATYP
(
ATYP
)
Alarm Type
Set which Set Point to shown in SV display in RUN
mode while device is in Auto Mode
HH
/
HL
/
LL
0 : HH
1 : HL
2 : LL
0
(HH )
RDLY
(
rdLY
)
Relay Delay
(For Relay)
Relay Delay is amount of time (in sec), that Relay
will wait before getting ON after the ON condition
occurs.
1 to 9999 sec
0 sec
HYST
(
HyST
)
Hysteresis
(For Relay)
Hysteresis Value (in °C) for Relay
1 to 255
TC & RTD Input
0.1 to 25.5
RTD.1 Input
1 to 255
Linear Input with DP=0
0.1 to 25.5
Linear Input with DP=1
0.01 to 2.55
Linear Input with DP=2
0.001 to 0.255
Linear Input with DP=3
0 .1
LACH
(
LACH
)
Latch
Enable or Disable Latch
yes
/
no
0 : YES
1 : NO
1
(NO )
CTRl
(
CTRL
)
Control Relay
Select Control Relay Status
on
/
off
0 : ON
1 : OFF
0
(O F F )
SRNO
(
srno
)
Serial No.
Unit ID for Modbus-RS485 Communication
1 to 247
1
BAUD
(
baud
)
Baud Rate
Set Modbus RS485 Communication Baud Rate
4800
/
9600
/
19.2k
/
38.4k
0 : 4800 (4800 bps)
1 : 9600 (9600 bps)
2 : 19.2K (19200 bps)
3 : 38.4K (38400 bps)
1
(9600)
MTYP
(
mtyp
)
Modbus Type
Enable or Disable Latch
A
/
B
0 : A
1 : B
0
(A )
TOUT
(
TOUT
)
Time Out
Time Out is time (in sec), For Display PV
1-32 sec
1
Only in SERL
input
RETR
(
rETR
)
Retransmission
Retransmission Output Type
This output is according to PV input.
Zero & Span acts as Min & Max value of
retransmission o/p scale respectively.
0-5v
/
1-5v
/
0-10v
/
4-20
/
0-20
0 : 0-5V
1 : 1-5V
2 : 0-10V
3 : 4-20mA
4 : 0-20mA
Voltage or Current is Jumper Selectable from the Hardware.
3
(4-20mA)