6.4 Oil filter
Clean the oil filter (Fig.3, Ref.4) every 200 hours of
operation or every 6 months.
Replace it every 400 hours of operation or every 12
months.
The oil filter is accessed by removing the filter cap (Fig.3,
Ref.4.)
6.5 Air filter
For proper functioning and a long life of the engine it is
important to periodically clean and replace the air filter.
An inefficient filter may cause loss of engine power and
excessive smoke at the exhaust.
To replace the air filter (Fig. 4, Ref. 1), carry out the
following operations:
- to unhook the levers to rubber band(Fig. 4, Ref. 2)
- Remove the filter, extracting it from its housing and
clean or replace it;
- The paper element is cleaned with a blast of dry air,
from the inside to the outside, with a pressure not
exceeding 2 bar. Should it be very dirty or have holes,
replace it.
- Remount the cover and fix it with the external butterfly
screw.
Replace the air filter for the first time after 50 hours
of operation, then every 200 hours of operation.
Reduce the intervals if the generator operates in
particularly dusty environments.
Never turn on the engine without the air filter, since
this would cause serious damage to the engine.
6.6 Fuel filter
For the engine to deliver full power the filter must be
clean.
Clean the fuel filter (Fig.3, Ref.1) every 200 hours of
operation (or every 3 months) and replace it every 400
hours (or every 6 months).
Follow the instructions described in the use and
maintenance manual of the engine to properly clean
and replace the fuel filter.
Wash the fuel filter with diesel fuel.
6.7 Battery check
Periodically check the electrolyte level in the battery and
cleanliness and integrity of the connection cables to the
positive and negative terminals.
Normally, the acid level must be within the level lines
shown on the battery body.
When the MIN level is reached, top up the cells taking
care not to exceed the MAX level indicated on the battery
case.
If necessary, top up with distilled water.
6.8 Troubleshooting
The starter motor turns but the main engine does
not start
- Check that there is fuel in the tank (fill up)
- Check that the stop electromagnet valve is powered.
(consult Service Centre)
The generator switches off during the operating
period
- Check if the low oil level protection has been activated.
(Top up if necessary)
- Check that the stop electromagnet valve is powered.
(consult an authorised Service Centre )
- Check if there is fuel in the tank (fill up)
There is high smoke emission from the exhaust.
- Check that the oil level does not exceed the MAX notch.
(Fill up)
- Check the state of the air filter. (clean or replace)
- Check the calibration of the injector (consult Service
Centre)
The alternator voltage is too low.
- Check the engine rpm without applied loads, both 3150
(consult Service Centre)
- Check the state of the air filter. (replace)
- Check the calibration of the injector (consult Service
Centre)
Starter battery flat.
- Check the electrolyte level in the battery. (fill up)
- Check the battery charging device. (replace)
- Check integrity of the battery
The engine runs irregularly
- Check the fuel filter. (clean or replace)
- Check the calibration of the injector (consult an
authorised Service Centre)
The generator does not deliver power to the outlets
but the voltmeter indicates that voltage is present.
- Check that the magnetothermal differential switch is
in the ON position.
The generator does not deliver power to the outlets
and the voltmeter does not indicate that voltage is
present.
- Likely alternator fault. (consult Service Centre)