
IS 2.7 B
- 26
GB
GB
1
2
3
4
6
3.7 E
LECTRICAL
CONNECTIONS
3.7.1 B
ATTERY
CONNECTION
Use a 12V stand-alone battery to start the generator.
Connect it to the generator terminals using cables of
25mm
2
cross-section for a distance up to 5m
(16.4ft)
or cables of 35mm
2
cross-section for longer distances,
following this sequence of operations:
- First connect the positive pole (
+
) of the battery to
the terminal marked
+
on the generator (
ref.1
).
- Then connect the negative pole (
-
) of the battery to
the terminal marked
-
on the generator (
ref.2
).
- Spread some specific mineral grease on the
connectors in order to reduce oxidation or corrosion.
The generator is equipped with an automatic electronic
recharging device for the starter battery, able to deliver
10A at a voltage of 12V.
Install the battery in a ventilated housing separate
from the generator and any device which may cause
heat or sparks. Periodically check the state of the
terminal connections and the battery liquid level. If
necessary, disconnect the cables working in reverse
order from connection.
Do not invert the polarities of the connection cables,
as the generator and the battery may be seriously
damaged.
Do not connect any other loads to the battery.
In order to minimise galvanic currents, the (-) of the
generator battery must not be connected to the (-) of
the other batteries on board.
3.7.2
CONTROL
PANEL
CONNECTION
Connect the cable to connector (
ref.3
) using the cable
provided already connected to the control panel. Insert
the control panel cable through the hole (
ref.4
).
On control panel (
ref.6
) there is a display and buttons
for starting, stopping and menu navigation.
Control panel must be absolutely installed because
it’s essential for generator functioning. Do not use
different devices other that the supplied one, as they
can not be compatible with generator.
Remove battery connection before installing control
panel.
Control panel is supplied with a 10 meters length
cable.
Do not modify this cable as it may cause
improper functioning of the panel circuit.
Содержание IS 2.7 B
Страница 2: ...IS 2 7 B 2 GB GB...