4.6 Locations for Vent Pipe Terminator
Description
US Direct Vent Instal-
lations
Canadian Direct Vent
Installations
A
Clearance above grade, veranda, porch, deck, or balcony
12 in (30 cm)
12 in (30 cm)
B
Clearance to window or door that may be opening
12 in (30 cm)
36 in (91 cm)
C
Clearance to permanently closed window
*
*
D
Vertical clearance to ventilated soffit located above the terminal
within
a horizontal distance of 2 feet from the center line of the terminal
*
*
E
Clearance to unventilated soffit
*
*
F
Clearance to outside corner
*
*
G
Clearance to inside corner
*
*
H
Clearance to each side of center line extended above meter/
regulator assembly
*
3 ft (91 cm) within a
height 15 ft above the
meter/regulator as-
sembly
I
Clearance to service regulator vent outlet
*
3 ft (91 cm)
J
Clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other appliance
12 in (30 cm)
36 in (91 cm)
K
Clearance to a mechanical air supply inlet
3 ft (91 cm) above if
within 10 ft (3 m) hori-
zontally
6 ft (1.83 m)
L
Clearance above paved sidewalk or paved driveway located on
public property
*
7 ft (2.13 m)
M
Clearance under veranda, porch, deck, or balcony
*
12 in (30 cm)
* For clearances not specified in ANSI Z224.1 / NFPA 54 or CAN/CSA-B 149.1, please use clearances in
accordance with local installation codes and the requirement of the gas supplier.
4.6.1 Direct Venting Clearances
Table 4.
Direct Vent Clearances
Содержание MSTWW
Страница 38: ...LAARS Heating Systems Page 36 4 19 Wiring Diagram Figure 3 Wiring Diagram...
Страница 39: ...Mascot ST Tankless Water Heater Page 37 4 20 Ladder Diagram Figure 4 Ladder Diagram...
Страница 52: ...LAARS Heating Systems Page 50 1 Flame Detection 6 2 Fault Tree Analysis Section 6 Error Codes 2 Gas Detection...
Страница 63: ...Mascot ST Tankless Water Heater Page 61 Cover Assembly...
Страница 66: ...LAARS Heating Systems Page 64 Notes...
Страница 67: ...Mascot ST Tankless Water Heater Page 65 Notes...