Operation
PROFILER ST
EN
NOTICE
Loss of position correction values from deleting or over-
writing!
The
Position Correction
menu is not write-protected. If re-
quired, protect the
Setup
menu using a password against
unauthorised access.
»
Chapter 6.7.2 System, page 138
X
Configuring the position correction
1
Configure the following settings to determine the machine
zero for all connected incremental measuring systems type
1Vss
oder
TTL (RS-422)
:
•
In the
Origin
menu, enable the desired function for each
axis to determine the machine zero.
»
Chapter 6.7.3 Origin, page 140
•
If needed, enter a value for the
Offset from machine
zero
on the affected axes in the
Origin
menu.
•
Save your entries with
.
Note:
For absolute measuring systems (encoder type
SSI
)
the machine zero is set by hardware and not configurable.
2
In the
Encoder
menu, enable the check box
REF
for all axes
whose machine zero you would like to set by reference
mark.
Note:
The signals of reference marks from absolute mea-
suring systems (encoder type
SSI
) are not evaluated by the
PROFILER ST. The position correction is always done with
respect to the hardware set machine zero.
3
Save your entries with
.
4
Switch to the position display.
Содержание PROFILER ST
Страница 2: ......
Страница 3: ...Betriebsanleitung Operating Manual PROFILER ST ...
Страница 72: ...72 Reinigung Betriebsanleitung DE 9 Wartung Der PROFILER ST ist wartungsfrei ...
Страница 98: ...98 Betriebsanleitung DE Notizen Notizen ...
Страница 166: ...166 Cleaning Operating Manual EN 9 Maintenance The PROFILER ST is maintenance free ...
Страница 192: ...192 Operating Manual EN Notes Notes ...
Страница 193: ......
Страница 194: ......
Страница 195: ......