Temperature Setpoint Is Not Maintained
• Select Occupied mode from the Home Menu—
see
H/C, Fan, Occupancy, and Override on
.
• Override the fan to On from the Home
• Check that the appropriate application is
selected—see
(Advanced) Application Options
• Check that room temperature is being sensed
.
CO
2
Level Seems Incorrect
• After power is first applied or the FlexStat is
restarted, the sensor goes through a
warm-up
for approximately half a minute. During the
time the sensor count will be 0 ppm.
• Check the remote CO
2
sensor setup (if
applicable). For both internal and external
sensors, the
highest
of the two readings will
be used to control ventilation. The CO
2
ppm
display (if enabled) also shows the highest of
the two levels.
• To reduce nuisance complaints by occupants
of levels being “too high,” turn off the
visibility of the CO
2
level rotation in the
display. See
(Advanced) User Interface (UI) on
.
MS/TP Communication Issues
• Check MAC address and device instance
numbers (especially for duplicate
numbers on the network)—see
Communications (BACnet) on page 10
.
• Check that EOL switches are fully latched in
Of-Line) Termination on page 5
).
• Check baud rate—see
Communications (BACnet) on page 10
.
• Reduce the Max Master number down to
the minimum needed for that network—see
(Advanced) Communications (BACnet) on
.
• See
.
Output, Fan, and Relay Issues
Fan Does Not Run
NOTE: The animated fan icon is coupled with
BV18 in the packaged programming (not
the actual fan output terminal).
• Select Occupied mode from the Home
• Override the fan to On from the Home
• See
• Check that the appropriate application
.
• Check the fan configuration—see
.
• Restart the MAR7000.
After a low limit alarm
is generated, the fan will not run until after
the MAR7000 is restarted. (See
.)
Relay (Internal) Does Not Work
CAUTION
Relays are for Class-2 voltages (24 VAC) only.
Do not connect line voltage to the relays!
NOTE: Max. output current is
1 A for
individual relays @ 24 VAC/VDC or
a total of 1.5 A per bank of 3 relays
(relays 1–3 and 4–6). Do not attach a
device that draws current that exceeds
the corresponding value. Relays are NO,
SPST (Form “A”).
• Check current draw of load. Substitute an
output device that draws less current.
• Check that the output is on.
• See
.)
• If Restore Factory has just been performed, see
.