![Marvair MAR7000 Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/marvair/mar7000/mar7000_product-data-sheet_1734160012.webp)
MAR7000
12
1/2013, P/N 01757 Rev. B
(Advanced) Security Levels and Passwords
SECURITY
ACCESS LEVELS
PASSWORDS
ACCESS LEVELS
SETPOINT ADJ:
MAIN MENU: ADMIN
SYSTEM MODE: OPER
OCC OVERRIDE: USER
FAN OCC/UNOCC: OPER
NONE
PASSWORDS
USER:
OPERATOR:
ADMIN:
1 0 0 0
1 2 3 4
5 6 7 8
Access to the Main Menu, Setpoint Adjust, and
System/Occupancy/Fan settings have a default
password level of User. This level can be changed
for each function to None, Operator, or Adminis-
trator through the Access Levels menu. Passwords
are set in the Passwords menu.
Any person can view the display but might not
be able to change any settings without logging in
with one of the three levels of passwords:
• None (Level “0”): No password is required
(everyone has access). (For example, anyone
can adjust a setpoint with Access Level None
even if all other functions require a password.)
• User (Level 1): See the Menu Items Access
Levels chart on the next page.
• Operator (Level 2): See the Menu Items Access
Levels chart.
• Administrator (Level 3):
Can access all menus
and change all editable values.
DO NOT
FORGET THIS PASSWORD!
NOTE: Setting a password to (the default)
0000 eliminates the password prompt
and allows full access for that level.
If no password is set for ADMIN, no
password prompt will occur. If any
password is set for ADMIN, the menu
items accessible at the various levels
are shown in the following chart.
NOTE: Changes in security levels and/or
passwords take effect when the current
Administrator log-in has timed out.
Log-ins last until 60 seconds (default)
after the last button press. Desired length
of inactivity time-out can be changed in
the Systems submenu.
NOTE: When setting a password, the
Up
button
increases the alphanumeric value (0
through 9 and then A through Z).
(Advanced) Inputs
INPUTS
1: SPACE TEMP
2: FAN STATUS SENSOR
3: AI_03
4: OUTSIDE AIR TEMP
5: SPACE HUMIDITY
7:
8: REMOTE MOTION SENSOR
DISCHARGE AIR TEMP
INPUT #7
DISCH AIR TEMP
VALUE: 60.0° F
CAL. OFFSET: 0.0
OUT-OF-SERVICE: FALSE
FILTER WEIGHT: 6
SENSOR:
10K TYPE III
Inputs vary according to model, selected applica-
tion, and selected application options. See
vanced) Application Options on page 8
Value will show a temperature reading or a volt-
age (0.0 to 3.0), depending on the sensor.
Analog sensors can be calibrated changing the
value in
Calibration Offset
.
“
Out-of-Service
: False” means the input is active
(
not
out of service). If it is “true,” the input is inac-
tive. The menu only shows the status.
(Advanced) Temp. Setpoint Limits
LIMITS
OCC MIN CLG:
OCC MAX HTG: 80° F
UNOCC MIN CLG: 66° F
UNOCC MAX HTG: 80° F
MIN SETPT DIFF: 5° F
66° F
This menu permits changes to the minimum and
maximum allowed user/operator setpoint values.
(
Colder
Room Temperature
Warmer
)
Cooling
Setpoint
Heating
Setpoint
Proportional
Band
Proportional
Band
Minimum
Setpoint
Differential