MAR7000 

1/2013, P/N 01757 Rev. B

MS/TP Network End-Of-Line Termination

(3 Input Models)

Network Wiring

For

 MS/TP 

communications, connect the EIA-485 

wiring to –A and +B terminals on the backplate. 

Connect the –A terminals in parallel with all other 

–A terminals on the network and the +B terminals 

in parallel with all other +B terminals. (See 

MS/TP 

Network End-Of-Line Termination on page 5

 and 

Terminals and Connections on page 6

.) Connect 

the shields of the cable (Belden cable #82760 or 

equivalent) together at each device with a wire 

nut or equivalent.
For 

Ethernet or IP

 communications, plug an 

Ethernet cable directly into the RJ-45 jack on the 

back of the MAR7000.

MS/TP EOL (End-Of-Line) Termination

The controllers/thermostats on the physical ends 

of the EIA-485 wiring segment must have end-

of-line termination installed for proper network 

operation. (See 

MS/TP Network End-Of-Line 

Termination

 and 

EOL and Pull-Up Switch 

Resistor Positions on page 5

.) If an MAR7000 is at 

the physical end of the MS/TP network line, set 

both

 the EOL termination switches to 

On

 (to the 

right/up

) on the back of the circuit board. If not 

on the end, ensure that both switches are Off (left/

down).

10K 

0-12 V

Input Pull-Up Switches

EOL

Switches

ON

OFF

Pushed Left 

Pushed Right 

IN2

IN3

IN4

IN7

IN8

IN9

1
2
3
4
5
6

3
4

3
4

IN4 = 

5
6

10K 

0-12 V

5
6

IN3 = 

7
8

7
8

IN2 = 

7
8

EOL = 

Pushed Left 

Pushed Right 

1
2

ON

OFF

1
2

10K 

0-12 V

10K 

0-12 V

EOL: On

On

Off

Off

Off

MS/TP Network

EOL and Pull-Up Switch Resistor Positions

(6 Input Models)

10K Ohm

0-12 VDC

Input Pull-Up Switches

EOL

Switches

ON

OFF

Switch Pushed Up 

Pushed Down 

IN2

IN3

IN4

IN7

IN8

IN9

(CO

2

 Models)

Input Connections

Passive input devices require pull-up resistors in 

the circuit. For 

passive

 input devices (e.g., switch 

contacts and Type III 10K ohm thermistors) on 

the external inputs, set the pull-up switches on 

the back of the circuit board to the 

10K

 position. 

For 

active

 voltage devices, set the switches to the 

0–12 VDC

 position. (See 

EOL and Pull-Up Switch 

Resistor Positions on page 5 

and 

Terminals and 

Connections on page 6

.)

NOTE:  Unlike the EOL switch pairs, the 

INPUT switch pairs must NOT have 

both switches set in the same direction

ALL the input pull-up resistor switch 

pairs must be fully latched in either 

10K Ohm or 0–12 VDC position even if 

a switch pair has no input connected!

 

A single incorrect switch position may 

cause errors in multiple inputs.

NOTE:  Inputs do not support 1K ohm RTDs.
NOTE:  IN1 is the room temperature sensor AI1.

Содержание MAR7000

Страница 1: ...r data selection and entry Built in factory tested libraries of configurable application control sequences Integral energy management control with deadband heating and cooling set points and other adv...

Страница 2: ...backplates at a later time if desired Attractive white plastic case Supply Voltage 24 VAC 20 15 Class 2 Supply Power 13 VA not including relays Connections Wire clamp type terminal blocks 14 22 AWG c...

Страница 3: ...utes operational and 10 minutes maximum accuracy This model uses Automatic Background Calibration Logic or ABC Logic a patented self calibration technique designed to be used in applications where con...

Страница 4: ...wall and away from heat sources sunlight windows air vents and air circulation obstructions e g curtains or furniture Install it where the motion sensor will have unobstructed view of the most typica...

Страница 5: ...both switches are Off left down 10K 0 12 V Input Pull Up Switches EOL Switches ON OFF Pushed Left Pushed Right IN2 IN3 IN4 IN7 IN8 IN9 1 2 3 4 5 6 3 4 3 4 IN4 5 6 10K 0 12 V 5 6 IN3 7 8 7 8 IN2 7 8 E...

Страница 6: ...he MAR7000 s output capacity Maximum output current is 1 A for individual relays 24 VAC VDC or a total of 1 5 A per bank of 3 relays relays 1 3 and 4 6 Relays are NO SPST Form A B A IN4 IN3 GND IN2 Co...

Страница 7: ...permanently change the setpoint for occupied mode go to the Setpoints section under the Main Menu In the Setpoints menu heating cooling setpoints setbacks and deadband can be changed with if required...

Страница 8: ...d Menu ADVANCED APPLICATION CB PROGRAMS COMMUNICATION DATE TIME DEVICE INPUTS LIMITS The Advanced Menu displays various submenus Not all submenus can be seen on the screen at one time Scroll up or dow...

Страница 9: ...ll window To change the schedule with the default setting after an initial detection motion must also be detected at least once during the second quarter of the window approximately minutes 8 15 third...

Страница 10: ...will attempt to locate when polling for master devices on the local network To avoid possible communication issues with the network the Max Master number should be the lowest number needed for that ne...

Страница 11: ...Viewer on page 16 The CO2 models have a patented self calibration technique designed to be used in applications where concentrations will drop to outside ambi ent conditions approximately 400 ppm at l...

Страница 12: ...menu items accessible at the various levels are shown in the following chart NOTE Changes in security levels and or passwords take effect when the current Administrator log in has timed out Log ins l...

Страница 13: ...Trend Logs TRUE TREND LOGS TREND 1 TREND 2 TRUE TREND 3 FALSE TREND 4 FALSE TREND 5 FALSE TREND 6 FALSE TREND 7 FALSE TREND 1 SPACE TEMPERATURE LOG OBJECT REF AI1 LOG ENABLE TRUE INTERVAL MINS 10 STO...

Страница 14: ...are Fahrenheit tem perature values on the display change in whole degree increments by default and Celsius values change in 0 5 increments Changing the default No to Yes will show tenths of a degree v...

Страница 15: ...y separately in the Individual Days menu five entries NOTE The last overlapping entry overrides any other For example suppose the WEEKDAYS menu is used to set all weekdays for 7 00 AM ON and 5 00 PM O...

Страница 16: ...eduled setpoint When the time is set to 0 the override state will last until the next schedule change Motion Override on this menu is the amount of time in minutes detected motion will temporar ily pl...

Страница 17: ...ing the pointed object into the socket from the back side can be helpful When installing the cover it may be helpful to ap ply more pressure toward the bottom of the cover Replace the backplate NOTE W...

Страница 18: ...al power up or restart the motion occupancy sensor requires about 30 seconds before it will begin responding to motion The motion occupancy sensor initiates override only during off times in the sched...

Страница 19: ...e 5 Check baud rate see Advanced Communications BACnet on page 10 Reduce the Max Master number down to the minimum needed for that network see Advanced Communications BACnet on page 10 See Wiring Issu...

Страница 20: ...No voltage may indicate a bad connection or simply no active network NOTE Wiring must be adequate to avoid excessive voltage drop on long runs Allow plenty of cushion in measurements A meter may be t...

Страница 21: ...urns all object values to their relinquished defaults until they are updated by the MAR7000 s programs restarts the controller s Control Basic programs and leaves configuration and programming intact...

Страница 22: ...ion and Basic Operation 7 Home Main Menu and Override Screens 7 Navigation 7 Room Temp Setpoint Adjustment 7 Main Menu and Settings 7 H C Fan Occupancy and Override 7 Configuration General 8 Advanced...

Отзывы: