Display Freezes (Buttons Have No Effect)

•  Carefully remove the MAR7000 cover from 

the backplate and ensure the WD (watch dog) 

jumper is installed on the two pins toward the 

center of the board. The jumper is temporarily 

removed during a firmware installation/

update and should be reinstalled when the 

process is completed. Reinstalling the cover on 

the backplate will restart the MAR7000.

Display Keeps Resetting

•  Carefully remove the MAR7000 cover from 

the backplate, check pins and connectors, and 

reinsert. (See 

Cover Binds on Backplate on 

page 17

.)

•  Check for proper supply voltage from the 

transformer and that the transformer has 

enough capacity (VA) for all connected 

devices. (See their respective specifications.)

NOTE:  Wiring must be adequate to avoid 

excessive voltage drop on long 

runs! Allow plenty of “cushion” in 

measurements A meter may be too 

slow to register transient dips or peaks 

during startup. 

See 

Wiring Issues on 

page 20

.

•  Put the MAR7000 on a backplate connected 

to a (test) transformer with short wiring and 

no other connected devices. If the MAR7000 

works with the test transformer, the wiring 

and/or transformer in its previous location is 

inadequate. If it does not work with the test 

transformer, replace the MAR7000.

•  Put another MAR7000 on the installed 

backplate, and if the second MAR7000 

functions properly, replace the first MAR7000.

•  Check that the correct input type is selected 

on the Inputs screen. A Type III thermistor is 

the default for external inputs. See 

(Advanced) 

Inputs on page 12

.

•  Check input wiring. See 

Wiring Issues on page 

20

.

•  Check connected sensors.
•  Restore the MAR7000 to factory settings 

(see 

Resetting the MAR7000 on page 21

)

 and 

reconfigure.

Motion/Occupancy Sensor Does Not Work

•  After an initial power-up or restart, the 

motion/occupancy sensor requires about 30 

seconds before it will begin responding to 

motion.

•  The motion/occupancy sensor initiates 

override only during “off” times in the 

schedule. See 

Schedules on page 15

.

•  Check that the motion sensor is enabled and 

detects motion. See 

Motion Sensor on page 9

.

•  The MAR7000 must be installed where there 

is a clear view of typical traffic area (reliable 

range is out to about 33 feet). Remove or move 

obstacles. Reinstall the MAR7000 in a more 

optimal location if necessary.

Temperature Reading Is Incorrect

•  Check that the correct °F/°C temperature 

scale is selected—see 

(Advanced) Application 

Options on page 8

.

•  After applying power for the first time (or 

after an outage), allow the MAR7000 to self-

calibrate a few minutes before verifying 

temperature reading.

•  If the discrepancy is small, adjust the 

calibration offset—see 

(Advanced) Inputs on 

page 12

.

•  Check that the MAR7000 is 

NOT

 mounted 

on an exterior wall, mounted on or near 

a large thermal mass (e.g., concrete block 

wall), blocked from normal air circulation by 

obstructions, exposed to heat sources (e.g., 

lights, computers, copiers, coffee makers) or to 

sunlight (at 

any

 time of the day), exposed to 

drafts from windows or air vents, or exposed 

to air flow through the conduit from leaks 

in plenum ducts (put plumber’s putty inside 

conduit to block air leaks).

•  See also 

Input Values Are Outside Expected 

Range on page 18

.

Input, Sensor, and Value Issues

Input Values Are Outside Expected Range

•  Check that 

ALL

 the input pull-up resistor 

switches are fully latched in the correct 

positions. (See 

Input Connections on page 

5

.) 

A single incorrect switch position may 

affect multiple inputs. All input switches 

must be latched in either 10K Ohm or 0–12 

VDC positions even if no input is connected! 

Input switch pairs (3-4, 5-6, and 7-8) must 

never have both switches set in the same 

direction—if switch 3 is set to the left, for 

example, 4 must be set to the right (or vice 

versa).

Содержание MAR7000

Страница 1: ...r data selection and entry Built in factory tested libraries of configurable application control sequences Integral energy management control with deadband heating and cooling set points and other adv...

Страница 2: ...backplates at a later time if desired Attractive white plastic case Supply Voltage 24 VAC 20 15 Class 2 Supply Power 13 VA not including relays Connections Wire clamp type terminal blocks 14 22 AWG c...

Страница 3: ...utes operational and 10 minutes maximum accuracy This model uses Automatic Background Calibration Logic or ABC Logic a patented self calibration technique designed to be used in applications where con...

Страница 4: ...wall and away from heat sources sunlight windows air vents and air circulation obstructions e g curtains or furniture Install it where the motion sensor will have unobstructed view of the most typica...

Страница 5: ...both switches are Off left down 10K 0 12 V Input Pull Up Switches EOL Switches ON OFF Pushed Left Pushed Right IN2 IN3 IN4 IN7 IN8 IN9 1 2 3 4 5 6 3 4 3 4 IN4 5 6 10K 0 12 V 5 6 IN3 7 8 7 8 IN2 7 8 E...

Страница 6: ...he MAR7000 s output capacity Maximum output current is 1 A for individual relays 24 VAC VDC or a total of 1 5 A per bank of 3 relays relays 1 3 and 4 6 Relays are NO SPST Form A B A IN4 IN3 GND IN2 Co...

Страница 7: ...permanently change the setpoint for occupied mode go to the Setpoints section under the Main Menu In the Setpoints menu heating cooling setpoints setbacks and deadband can be changed with if required...

Страница 8: ...d Menu ADVANCED APPLICATION CB PROGRAMS COMMUNICATION DATE TIME DEVICE INPUTS LIMITS The Advanced Menu displays various submenus Not all submenus can be seen on the screen at one time Scroll up or dow...

Страница 9: ...ll window To change the schedule with the default setting after an initial detection motion must also be detected at least once during the second quarter of the window approximately minutes 8 15 third...

Страница 10: ...will attempt to locate when polling for master devices on the local network To avoid possible communication issues with the network the Max Master number should be the lowest number needed for that ne...

Страница 11: ...Viewer on page 16 The CO2 models have a patented self calibration technique designed to be used in applications where concentrations will drop to outside ambi ent conditions approximately 400 ppm at l...

Страница 12: ...menu items accessible at the various levels are shown in the following chart NOTE Changes in security levels and or passwords take effect when the current Administrator log in has timed out Log ins l...

Страница 13: ...Trend Logs TRUE TREND LOGS TREND 1 TREND 2 TRUE TREND 3 FALSE TREND 4 FALSE TREND 5 FALSE TREND 6 FALSE TREND 7 FALSE TREND 1 SPACE TEMPERATURE LOG OBJECT REF AI1 LOG ENABLE TRUE INTERVAL MINS 10 STO...

Страница 14: ...are Fahrenheit tem perature values on the display change in whole degree increments by default and Celsius values change in 0 5 increments Changing the default No to Yes will show tenths of a degree v...

Страница 15: ...y separately in the Individual Days menu five entries NOTE The last overlapping entry overrides any other For example suppose the WEEKDAYS menu is used to set all weekdays for 7 00 AM ON and 5 00 PM O...

Страница 16: ...eduled setpoint When the time is set to 0 the override state will last until the next schedule change Motion Override on this menu is the amount of time in minutes detected motion will temporar ily pl...

Страница 17: ...ing the pointed object into the socket from the back side can be helpful When installing the cover it may be helpful to ap ply more pressure toward the bottom of the cover Replace the backplate NOTE W...

Страница 18: ...al power up or restart the motion occupancy sensor requires about 30 seconds before it will begin responding to motion The motion occupancy sensor initiates override only during off times in the sched...

Страница 19: ...e 5 Check baud rate see Advanced Communications BACnet on page 10 Reduce the Max Master number down to the minimum needed for that network see Advanced Communications BACnet on page 10 See Wiring Issu...

Страница 20: ...No voltage may indicate a bad connection or simply no active network NOTE Wiring must be adequate to avoid excessive voltage drop on long runs Allow plenty of cushion in measurements A meter may be t...

Страница 21: ...urns all object values to their relinquished defaults until they are updated by the MAR7000 s programs restarts the controller s Control Basic programs and leaves configuration and programming intact...

Страница 22: ...ion and Basic Operation 7 Home Main Menu and Override Screens 7 Navigation 7 Room Temp Setpoint Adjustment 7 Main Menu and Settings 7 H C Fan Occupancy and Override 7 Configuration General 8 Advanced...

Отзывы: