-34-
11. Communication Port
The communication port is for the monitoring software. A USB port
and an intelligent slot are provided.
11.1 USB
The USB port is compliance with USB 1.1 protocol.
11.2 AS400 Interface (Option)
Except for the communication protocol as mentioned above, this
series UPS has AS400 card (an optional accessory) for AS400
communication protocol. Please contact yo ur local distributor for
details. The following is the pin assignment and description of DB-9
connector in AS400 card.
Pin #
Description
I/O
Pin #
Description
I/O
1
UPS Fail
Output
6
Bypass
Output
2
Summary Alarm Output
7
Battery Low
Output
3
GND
Input
8
UPS ON
Output
4
Remote
Shutdown
Input
9
Line Loss
Output
5
Common
Input
DB-9 Interface of AS400 communication protocol
-5-
1.6 Standards
* Safety
IEC/EN 62040-1
* EMI
Conducted Emission.................................:IEC/EN 62040-2
Category C1
Radiated Emission....................................:IEC/EN 62040-2
Category C1
Harmonic Current....................................:IEC/EN 61000-3-2
Voltage Fluctuation and Flicker...............:IEC/EN 61000-3-3
*EMS
ESD........................................................:IEC/EN 61000-4-2
Level 4
RS..........................................................:IEC/EN 61000-4-3
Level 3
EFT.........................................................:IEC/EN 61000-4-4
Level 4
SURGE..................................................:IEC/EN 61000-4-5
Level 4
CS………………………………….....…...:IEC/EN 61000-4-6
Level 3
MS………………………………....……..: IEC/EN 61000-4-8
Level 3
Voltaje Dips………………………...…...: IEC/EN 61000-4-11
Low Frequency Signals..........................:IEC/EN 61000-2-2