-16-
5.7 Audible alarm mute function:
If the alarm is too annoying in battery mode, yo u may press “I” button
continuously for more than 1 second to clear it. Moreover, the alarm
will be enabled when the battery is low to remind you to shutdown the
load soon.
If the alarm is too annoying in bypass mode, you may press “ “button
continuously for more than 1 second to clear it. The action doesn’t
affect the warning and fault alarm.
5.8 Operation procedure of external battery for long backup
time model (“
L
” model)
(1) Use the battery pack with voltage: 36VDC for 1KL (3 pcs of 12V
batteries), 96VDC for 2KL/ 3KL (8 pcs of 12V batteries).
Connection of batteries more than or less than required will cause
abnormality or permanent damage.
(2) One hard wiring type battery terminal on the rear panel is used for
connecting the battery pack.
(3) The battery connection procedure is very important. Any
incompliance may result in the risk of electric shock. Therefore,
the following steps must be strictly complied with.
(4) Make sure the mains input is cut off, if there is a battery breaker
then turn it off first.
(5) Remove the small cover of terminal block, prepare the battery
cable which should be able to carry the current of >30A for 1KVA,
>22A for 2KVA, >33A for 3KVA, the cross section area should be
great than 4
mm
2
for all model. And battery wire color is
recommended as following:
GND
Red wire
Green/Yellow wire
Black wire
(6) The red wire is connected to the "+" terminal of the battery. The
-23-
2) It is attentio n that the transfer time of UPS output from ECO mode
to battery mode is less than 10ms. But it is still too long for some
sensitive load.
6.7 Converter mode
In converter mode, on LCD display, the mode code is “6”.
The UPS would free run with fixed output frequency (50Hz or 60Hz)
in converter mode. Once the mains is loss or abnormal, the UPS
would transfer to battery mode and the load is supplied continuously
by the battery.
1) It could be enabled through the LCD setting or the software
(Winpower, etc.).
2) The load should be derating to 60% in converter mode.
6.8 Abnormal mode
In abnormal mode such as Bus fault etc., the corresponding fault
code would be shown to indicate the operating mode of the UPS.
And some warning words could also be shown, for example “short!”
would be shown when the load or the UPS output is short and the
UPS is in inverter fault mode.