Table 2:  HG Electric Heat Electrical Data - H

Z

/HE

Table 1:  HG Electric Heat Ratings and Compatibility

HG Series

Supply

Heater Amps

Min Circ Ampacity

Max Fuse

Supply Wire

Electric Heat Model

Circuit

240V

208V

240V

208V

240V

208V

Min AWG

Max Ft

HGM5

Single

20.0

17.3

25.0

21.6

25

25

10

70

HGM8

Single

31.7

27.5

39.6

34.4

40

35

8

70

HGM10

Single

40.0

34.7

50.0

43.4

50

45

6

90

Single

47.5

41.2

59.4

51.5

60

60

6

70

HGM12

Dual - L1/L3

31.7

27.5

39.6

34.4

40

35

8

70

Dual - L2/L4

15.8

13.7

19.8

17.1

20

20

12

50

HGL10

Single

40.0

34.7

50.0

43.4

50

45

6

80

Single

60.0

52.0

75.0

65.0

80

70

6

50

HGL15

Dual - L1/L3

40.0

34.7

50.0

43.4

50

45

6

80

Dual - L2/L4

20.0

17.3

25.0

21.6

25

25

10

70

Single

80.0

69.3

100.0

86.6

100

90

2

100

HGL20

Dual - L1/L3

40.0

34.7

50.0

43.4

50

45

6

80

Dual - L2/L4

40.0

34.7

50.0

43.4

50

45

6

80

All heaters rated single phase 208-240V  60 Hz

Wire length based on one way measurement with 2% voltage drop

Wire size based on 60°C copper conductor

All models 12kW or larger feature internal circuit breakers

All fuses UL Class K general purpose

HGM4

Single

15.8

14.0

19.8

17.1

20

20

12

130

Heater 

Model

HT Series

HP Series

HE Series

WDG Series kW Rating Btuh Rating Minimum

CFM 

Required

24 36 48 60 70 18 24 30 36 42 48 60 24 30 36 42 48 60 24 36 48 60 240V 208V 240V 208V

HGM4A X

3.8

2.9 13000 9900

500

HGM5A X

4.8

3.6 16300 12300

500

HGM8A X

7.6

5.7 25900 19400

650

HGM10A X

9.6

7.2 32700 24600

650

HGM12A

11.4

8.6 38900 29200

750

HGM4B

3.8

2.9 13000 9900

500

HGM5B

4.8

3.6 16300 12300

500

HGM8B

7.6

5.7 25900 19400

650

HGM10B

9.6

7.2 32700 24600

650

HGM12B

11.4

8.6 38900 29200

750

HGM4C

3.8

2.9 13000 9900

500

HGM5C

4.8

3.6 16300 12300

500

HGM8C

7.6

5.7 25900 19400

650

HGM10C

9.6

7.2 32700 24600

650

HGL10A

X

X

X

X

9.6

7.2 32700 24600

1300

HGL15A

X

X

X

X

14.4

10.8 49100 36900

1350

HGL20A

X

X

X

19.2

14.4 65500 49200

1350

HGL10C

X

X

X

9.6

7.2 32700 24600

1300

HGL15C

X

X

X

14.4

10.8 49100 36900

1350

HGL20C

X

X

19.2

14.4 65500 49200

1350

  Shaded areas denote compatibility

Internal mounted heaters are rated for zero clearance (unit and duct). External mounted heaters require 1” clearance for first three feet of duct.

Heater 

Model

HZ Series

HE Series

WDG Series kW Rating

Btuh Rating

Minimum 

CFM 

Required

24 36 48 60 70 24 30 36 42 48 60 24 36 48 60 240V 208V 240V

208V

HGM4

3.8

2.9 13000 9900

500

HGM5

4.8

3.6 16300 12300

500

HGM8

7.6

5.7 25900 19400

650

HGM10

9.6

7.2 32700 24600

650

HGM12

11.4 8.6 38900 29200

750

HGM4

3.8

2.9 13000 9900

500

HGM5

4.8

3.6 16300 12300

500

HGM8

7.6

5.7 25900 19400

650

HGM10

9.6

7.2 32700 24600

650

HGM12

11.4 8.6 38900 29200

750

HGM4

3.8

2.9 13000 9900

500

HGM5

4.8

3.6 16300 12300

500

HGM8

7.6

5.7 25900 19400

650

HGM10

9.6

7.2 32700 24600

650

HGL10

9.6

7.2 32700 24600

1300

HGL15

14.4 10.8 49100 36900

1350

HGL20

19.2 14.4 65500 49200

1350

HGL10

9.6

7.2 32700 24600

1300

HGL15

14.4 10.8 49100 36900

1350

HGL20

19.2 14.4 65500 49200

1350

Содержание Comfort-Aire Century HG Series

Страница 1: ...the screws Flanges will be packaged loose inside the blower compartment of vertical upflow units and will be factory installed on horizontal units downflow units have none HE036 and 042 units require...

Страница 2: ...on or consult factory if they do not match 5 Re install blower assembly on to electric heater using pins and bolts as before Check blower electrical wiring for proper connection and remedy any pinched...

Страница 3: ...ectric heat model from Table 1 Low speed blower not allowed with electric heat Field supplied disconnect Refer to local codes Electric Heat Assembly Disconnect optional refer to local code Field suppl...

Страница 4: ...h setting Momentarily short the test pins do not jumper the test pins of the DXM control to place it in test mode to reduce time delays Unit will require 15 20 seconds before engaging emergency heat m...

Страница 5: ...500 HGM8A X 7 6 5 7 25900 19400 650 HGM10A X 9 6 7 2 32700 24600 650 HGM12A 11 4 8 6 38900 29200 750 HGM4B 3 8 2 9 13000 9900 500 HGM5B 4 8 3 6 16300 12300 500 HGM8B 7 6 5 7 25900 19400 650 HGM10B 9 6...

Страница 6: ...40 34 7 7 0 59 52 60 60 HGL15 DUAL L1 L2 40 34 7 0 0 50 43 50 45 L3 L4 20 17 3 7 0 34 30 35 30 HGL20 DUAL L1 L2 40 34 7 0 0 50 43 50 45 L3 L4 40 34 7 7 0 59 52 60 60 All heaters rated single phase 208...

Страница 7: ...n HGL Large Electric Heat Option 14 7 Control box Element cover 10 3 15 5 16 8 8 1 3 13 3 13 5 2 15 1 12 Discharge Air Opening Discharge Air Opening 14 7 Control box Element cover 10 3 15 5 16 8 8 1 3...

Страница 8: ...WDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQFH DQG FHUWLILFDWLRQ OO SURGXFWV PHHW DSSOLFDEOH UHJXODWLRQV LQ HIIHFW RQ GDWH RI PDQXIDFWXUH KRZHY...

Отзывы: