Page 4

Figure 6:  Staging Dip Switches

Figure 5b:  Power Wiring, Single Circuit, 12, 15, 20kw

Figure 5c:  Power Wiring, 4, 5, 8, and 10kw

ON

OFF

ON

OFF

1

2

3

4

P1

In 15 and 20 kW units 

two power circuits are 

employed to reduce wires 

size and cost of breakers

L1

L2

L3

L4

P2

Conduit

Auxiliary Electric Heat Start-up

Put thermostat in emergency heat mode (or jumper t-stat 

input R to W and R to G) and setpoint to high setting. 

Momentarily short the test pins (do not jumper the test 

pins) of the 

D

XM control to place it in test mode to 

reduce time delays. Unit will require 15-20 seconds 

before engaging emergency heat mode stage 1 (W1) and 

then another 15-20 seconds to engage stage 2 (W2) when 

in ‘Test mode’. Verify proper electric heat operation.

Figure 5a:  Power Wiring, Dual Circuits, 12, 15, 20kw

In 12, 15 and 20 kW units, optional single power circuit is employed to reduce the 

number of wires needed. Optional single unit adapter kit part number 16B0002N02.

ER1

ER2

ER1

ER2

ER3

ER4

For HGM/L 4, 5, 8, 10kW.

For HGL 12, 15, and 20kW.

Содержание Comfort-Aire Century HG Series

Страница 1: ...the screws Flanges will be packaged loose inside the blower compartment of vertical upflow units and will be factory installed on horizontal units downflow units have none HE036 and 042 units require...

Страница 2: ...on or consult factory if they do not match 5 Re install blower assembly on to electric heater using pins and bolts as before Check blower electrical wiring for proper connection and remedy any pinched...

Страница 3: ...ectric heat model from Table 1 Low speed blower not allowed with electric heat Field supplied disconnect Refer to local codes Electric Heat Assembly Disconnect optional refer to local code Field suppl...

Страница 4: ...h setting Momentarily short the test pins do not jumper the test pins of the DXM control to place it in test mode to reduce time delays Unit will require 15 20 seconds before engaging emergency heat m...

Страница 5: ...500 HGM8A X 7 6 5 7 25900 19400 650 HGM10A X 9 6 7 2 32700 24600 650 HGM12A 11 4 8 6 38900 29200 750 HGM4B 3 8 2 9 13000 9900 500 HGM5B 4 8 3 6 16300 12300 500 HGM8B 7 6 5 7 25900 19400 650 HGM10B 9 6...

Страница 6: ...40 34 7 7 0 59 52 60 60 HGL15 DUAL L1 L2 40 34 7 0 0 50 43 50 45 L3 L4 20 17 3 7 0 34 30 35 30 HGL20 DUAL L1 L2 40 34 7 0 0 50 43 50 45 L3 L4 40 34 7 7 0 59 52 60 60 All heaters rated single phase 208...

Страница 7: ...n HGL Large Electric Heat Option 14 7 Control box Element cover 10 3 15 5 16 8 8 1 3 13 3 13 5 2 15 1 12 Discharge Air Opening Discharge Air Opening 14 7 Control box Element cover 10 3 15 5 16 8 8 1 3...

Страница 8: ...WDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQFH DQG FHUWLILFDWLRQ OO SURGXFWV PHHW DSSOLFDEOH UHJXODWLRQV LQ HIIHFW RQ GDWH RI PDQXIDFWXUH KRZHY...

Отзывы: