Basic Installation and Configuration 
Guidelines

Use minimum 6AWG copper conductors only.

Torque field connections between 21 and 23 in
lbs.

Readily accessible disconnecting means to be
provided at time of installation.

Permanently connected power supply.

Connect only to a circuit protected by a Class A
Ground Fault Circuit Interrupter (GFCI) or Resid-
ual Current Device (RCD) mounted at least 5’
(1.52M) from the inside walls of the spa/hot tub
and in line of sight from the equipment compart-
ment.

CSA enclosure: Type 2

Refer to Wiring Diagram inside the cover of the
control enclosure.

Refer to Installation and Safety Instructions
provided by the spa manufacturer.

Warning:

 People with infectious diseases should 

not use a spa or hot tub.

Warning:

 To avoid injury, exercise care when enter-

ing or exiting the spa or hot tub.

Warning: 

Do not use a spa or hot tub immediately 

following strenuous exercise.

Warning:

 Prolonged immersion in a spa or hot tub 

may be injurious to your health.

Warning:

 Maintain water chemistry in accordance 

with the manufacturers instructions.

Warning: 

The equipment and controls shall be 

located not less than 1.5 meters horizontally from the 
spa or hot tub.

Warning! GFCI or RCD Protection.

The Owner should test and reset the GFCI or RCD 
on a regular basis to verify its function.

Warning! Shock Hazard!
No User Serviceable Parts.

Do not attempt service of this control system. 
Contact your dealer or service organization for 
assistance. Follow all owner’s manual power 
connection instructions. Installation must be 
performed by a licensed electrician and all grounding 
connections must be properly installed.

CSA Compliance/Conformité
Caution:

Test the ground fault circuit interrupter before
each use of the spa.

Read the instruction manual.

Adequate drainage must be provided if the
equipment is to be installed in a pit.

For use only within an enclosure rated CSA
Enclosure 3.

Connect only to a circuit protected by a Class A
ground fault circuit interrupter or residual current
device.

To ensure continued protection against shock
hazard, use only identical replacement parts
when servicing.

Install a suitably rated suction guard to match the
maximum flow rate marked.

Warning:

Water temperature in excess of 100.4°F or 38°C
may be injurious to your health.

Disconnect the electrical power before servicing.

Attention:

Toujours verifier l’efficacite du disjoncteur differ-
entiel avant d’utiliser differentiel avant d’utiliser le
bain.

Lire la notice technique.

Lorsque l’appareillage est installe dans une fosse,
on doit assurer un drainage adequat.

Employer uniquement a l’interieur d’une cloture
CSA Enclosure 3.

Connecter uniquement a un circuit protege par
un disjoncteur differentiel de Class A.

Afin d’assurer une protection permanente contre
le danger de shockelectrique, lors de l’entretien
employer seulement des pieces de rechange
identiques.

Les prises d’aspiration doivent etre equipees de
grilles convenant au debit maximal indique.

Avertissement:

Des temperatures de l’eau superieures a 38°C
peuvent presenter un danger pour la sante.

Deconnecter du circuit d’alimentation electrique
avante l’entretien.

Warning/Advertissement:

Disconnect the electric power before servicing.
Keep access door closed.

Deconnecter du circuit d’alimentation electrique
avant l’entretien.

Garder la porte fermer.

Warning! Qualified Technician Required for Service and Installation

18

Содержание spaTouch2

Страница 1: ...ent Control Icon will spin when a pump is in operation ICON Specifications 1 H High Temperature Range 2 R Ready Mode 3 F1 Filter Cycle 1 Running 4 O3 Ozone Running 5 C Cleanup Cycle 6 Wi Fi Signal Ind...

Страница 2: ...Call for Service text as it requires a service technician to fix the problem Touching the Error Warning Reminder Info Icon on the Message Screen will take you to the System Information Screen to allo...

Страница 3: ...rtain times an indicator may appear showing that a message is waiting Touch this indicator to go to the Message Display Screen On that Screen some of the messages can be dismissed A Warning Message is...

Страница 4: ...allation The icon buttons are used to select and control individual devices Some devices like pumps may have more than one ON state so the icon will change to reflect the state of the equipment Below...

Страница 5: ...iting Screens Use the Back button to go back or exit The Back button is on every screen except the Main Screen the Priming Mode Screen or the Message Display Screen When you see only the Back button o...

Страница 6: ...Down button is shown and pressed when on a page with a text list the list can be scrolled a page at a time Page Up Page Down THE SETTINGS SCREEN Programming Etc The Settings Screen is where all progr...

Страница 7: ...low speed and high speed but you cannot turn the heater pump off Circulation Mode See Pumps for other circulation modes If the spa is configured for 24HR circulation the heater pump generally runs co...

Страница 8: ...lowing from the jets in the spa do not allow the pumps to continue to run Turn off the pumps and repeat the process Note Turning the power off and back on again will initiate a new pump priming sessio...

Страница 9: ...erence and usage patterns Setting the filtration cycles for late at night can avoid higher electrical rate costs as an example If you live in a climate that is seasonally hot running the filtration cy...

Страница 10: ...be maintained for several days ADJUSTING FILTRATION Main Filtration Using the same adjustment as Setting the Time Filter Cycles are set using a start time and a duration Each setting can be adjusted...

Страница 11: ...fic Buttons for Specific Devices If the spa has an Auxiliary Panel installed pressing buttons on that panel will activate the device indicated for that button These dedicated buttons will operate just...

Страница 12: ...FCI configured in one of three ways 1 GFCI test is not enabled 2 Manual GFCI test is enabled but automatic GFCI test is not enabled 3 Both manual and automatic GFCI tests are enabled The automatic tes...

Страница 13: ...ticular system System Model Displays the Model Number of the System Panel Version Displays a number of the software in the topside control panel Software ID SSID Displays the software ID number for th...

Страница 14: ...Screen takes you to the GFCI Test screen The installer can cause the GFCI Trip Test to occur sooner by pressing Test on the GFCI Test screen The GFCI should trip within several seconds and the spa sh...

Страница 15: ...cted or the Aux Freeze Switch has closed All water devices are activated In some cases pumps may turn on and off and the heater may operate during Freeze Protection This is an operational message not...

Страница 16: ...in the heater to start it The spa is shut down After the problem has been resolved you must reset the message to restart heater See Flow Related Checks below The heater is too hot M030 One of the wate...

Страница 17: ...m and requires a service call The settings have been reset Persistent Memory Error M021 Contact your dealer or service organization if this message appears on more than one power up The clock has fail...

Страница 18: ...tions must be properly installed CSA Compliance Conformit Caution Test the ground fault circuit interrupter before each use of the spa Read the instruction manual Adequate drainage must be provided if...

Страница 19: ...2 3 4 Messages 1 2 3 Message Waiting Indicator 1 2 Music 1 2 3 N Navigation 3 Normal Error 2 O Ozone 2 9 P Page Up Down 6 Panel Version 13 Polling 7 9 Press and Hold 3 Priming Mode 5 8 12 Programming...

Отзывы: