Basic Installation and Configuration
Guidelines
•
Use minimum 6AWG copper conductors only.
•
Torque field connections between 21 and 23 in
lbs.
•
Readily accessible disconnecting means to be
provided at time of installation.
•
Permanently connected power supply.
•
Connect only to a circuit protected by a Class A
Ground Fault Circuit Interrupter (GFCI) or Resid-
ual Current Device (RCD) mounted at least 5’
(1.52M) from the inside walls of the spa/hot tub
and in line of sight from the equipment compart-
ment.
•
CSA enclosure: Type 2
•
Refer to Wiring Diagram inside the cover of the
control enclosure.
•
Refer to Installation and Safety Instructions
provided by the spa manufacturer.
Warning:
People with infectious diseases should
not use a spa or hot tub.
Warning:
To avoid injury, exercise care when enter-
ing or exiting the spa or hot tub.
Warning:
Do not use a spa or hot tub immediately
following strenuous exercise.
Warning:
Prolonged immersion in a spa or hot tub
may be injurious to your health.
Warning:
Maintain water chemistry in accordance
with the manufacturers instructions.
Warning:
The equipment and controls shall be
located not less than 1.5 meters horizontally from the
spa or hot tub.
Warning! GFCI or RCD Protection.
The Owner should test and reset the GFCI or RCD
on a regular basis to verify its function.
Warning! Shock Hazard!
No User Serviceable Parts.
Do not attempt service of this control system.
Contact your dealer or service organization for
assistance. Follow all owner’s manual power
connection instructions. Installation must be
performed by a licensed electrician and all grounding
connections must be properly installed.
CSA Compliance/Conformité
Caution:
•
Test the ground fault circuit interrupter before
each use of the spa.
•
Read the instruction manual.
•
Adequate drainage must be provided if the
equipment is to be installed in a pit.
•
For use only within an enclosure rated CSA
Enclosure 3.
•
Connect only to a circuit protected by a Class A
ground fault circuit interrupter or residual current
device.
•
To ensure continued protection against shock
hazard, use only identical replacement parts
when servicing.
•
Install a suitably rated suction guard to match the
maximum flow rate marked.
Warning:
•
Water temperature in excess of 100.4°F or 38°C
may be injurious to your health.
•
Disconnect the electrical power before servicing.
Attention:
•
Toujours verifier l’efficacite du disjoncteur differ-
entiel avant d’utiliser differentiel avant d’utiliser le
bain.
•
Lire la notice technique.
•
Lorsque l’appareillage est installe dans une fosse,
on doit assurer un drainage adequat.
•
Employer uniquement a l’interieur d’une cloture
CSA Enclosure 3.
•
Connecter uniquement a un circuit protege par
un disjoncteur differentiel de Class A.
•
Afin d’assurer une protection permanente contre
le danger de shockelectrique, lors de l’entretien
employer seulement des pieces de rechange
identiques.
•
Les prises d’aspiration doivent etre equipees de
grilles convenant au debit maximal indique.
Avertissement:
•
Des temperatures de l’eau superieures a 38°C
peuvent presenter un danger pour la sante.
•
Deconnecter du circuit d’alimentation electrique
avante l’entretien.
Warning/Advertissement:
•
Disconnect the electric power before servicing.
Keep access door closed.
•
Deconnecter du circuit d’alimentation electrique
avant l’entretien.
•
Garder la porte fermer.
Warning! Qualified Technician Required for Service and Installation
18