Series 500 Ceiling Mounted 

Fan Forced Heater

Electrical Accessories

Installation Instructions

SAVE THESE INSTRUCTIONS

INSTALLATION OF POWER DISCONNECT SWITCH (DS)

Surface Mount and Recessed Mount Except T-Bar
Mounting:

1. Install disconnect switch in the surface mounting plate or

recess box as shown in the heater installation instructions
and Figure 1 with the terminals marked L1, L2 and L3 toward
the knockout.

2. Remove and discard the wire from the terminal marked T3 on

the disconnect switch if the power supply is single phase.

3. Install field wiring to the disconnect switch terminals marked

L1 and L2 (and L3 for three phase). 

4. Install heater as shown in the heater installation instructions.

5. Remove wiring cover from front of heater and wire T1 and T2

(and T3 for three phase) from the disconnect switch to the
power block on the heater.  (See Wiring Diagram, Figure 3).

6. Turn disconnect switch clockwise to energize circuit.

T-Bar Mounting:

1. Install disconnect switch in the recess box as shown in the

heater installation instructions and Figure 1 with the terminals
marked L1, L2, and L3 toward the knockout.

2. Remove and discard the wire from the terminal marked T3 on

the disconnect switch if the power supply is single phase.

CAT. NO.

ACCESSORY

ELECTRICAL RATING

REMARKS

T

Single Pole Internal Thermostat;

25A; 120-277 VAC Res.

-

Temp Range:  40°F - 95°F

720 Pilot Duty

24R

Control Relay; 24 VAC Holding Coil

Inductive Amps:  7.0 @ 120 - 277 VAC.

Time Delay:  45 - 60 sec.;

Resistive Amps:  25 @ 120 - 277 VAC.

to close when energized.

R12

Control Relay; 120 VAC Holding Coil

Inductive Amps:  7.0 @ 120 - 277 VAC.

Time Delay:  45 - 60 sec.;

Resistive Amps:  25 @ 120 - 277 VAC.

to close when energized.

DS

Supply Power Disconnect Switch

30A (MAX Load 24A) 208 - 600 VAC, 3 Pole, 10

-

TR4

Transformer and Relay

Transformer:  208/240 VAC primary; 24 VAC 

Time Delay:  45 - 60 sec.;

secondary. - Relay:  24 VAC Holding Coil

to close when energized.

TR7

Transformer and Relay

Transformer:  277 VAC primary; 24 VAC

Time Delay:  45 - 60 sec.;

secondary. - Relay:  24 VAC Holding Coil

to close when energized.

WARNING

!

THIS INSTRUCTION SHEET CONTAINS VITAL INFORMATION

FOR  THE  PROPER  INSTALLATION,  USE  AND  EFFICIENT

OPERATION OF THE HEATER.  CAREFULLY READ THE MAN-

UAL  BEFORE  INSTALLATION,  OPERATION,  OR  CLEANING

OF THE  HEATER.    FAILURE TO ADHERE TO THE  INSTRUC-

TIONS COULD RESULT IN FIRE, ELECTRIC SHOCK, DEATH,

SERIOUS PERSONAL INJURY OR PROPERTY DAMAGE.  

WARNING

!

MAKE  SURE  ALL  POWER  IS  DISCONNECTED  AT  SUPPLY

BEFORE INSTALLING.

Figure 1

40485

03/15

5200-2070-004

Содержание Series 500

Страница 1: ... the wire from the terminal marked T3 on the disconnect switch if the power supply is single phase CAT NO ACCESSORY ELECTRICAL RATING REMARKS T Single Pole Internal Thermostat 25A 120 277 VAC Res Temp Range 40 F 95 F 720 Pilot Duty 24R Control Relay 24 VAC Holding Coil Inductive Amps 7 0 120 277 VAC Time Delay 45 60 sec Resistive Amps 25 120 277 VAC to close when energized R12 Control Relay 120 VA...

Страница 2: ...e 4 NOTE Be sure that the tab on the control relay plate is securely engaged in the large hole in the mounting bracket 2 To wire the relay refer to the wiring diagram Figure 5 and proceed as follows a Wire the internal control circuit by connecting the heater WHITE wires to the terminals at the top of the relay NOTE The control relay requires externally supplied voltage to operate 24 VAC 24R and 1...

Страница 3: ...er RED wire from the relay base and the YELLOW transformer wire to the remote low voltage thermostat by others wires d Connect the Black wire primary from the transformer to power block L1 terminal e For TR4 only Connect the RED wire 208V or the ORANGE wire 240V from the transformer to terminal L2 of the power block Clip off and tape the end of the unused transformer wire f For TR7 only Connect th...

Страница 4: ...IES ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS AGREEMENT MARLEY ENGINEERED PRODUCTS SHALL NOT BE LIABLE FOR CONSEQUENTIAL DAMAGES ARISING WITH RESPECT TO THE PRODUCT WHETHER BASED UPON NEGLIGENCE TORT STRICT LIABILITY OR CONTRACT Some states do not allow the exclusion on limitation of incidental or consequential damages so the above exclusion or limitation may not apply to you This warranty give...

Страница 5: ...A NOMINAL NOTAS T Termostato interno unipolar Pilot Duty 720 de Res de Interv de temp 40ºF 95ºF 25A 120 277 VCA 24R Relé de control bobina retenedora Amps inducs 7 0 120 277 VAC Demora 45 60 seg cierra al de 24 VCA Amps resist 25 120 277 VAC activarse R12 Relé de control bobina retenedora Amps induc 7 0 120 277 VAC Demora 45 60 seg cierra al de 120 VCA Amps resist 24 120 277 VAC activarse DS Inter...

Страница 6: ...BLANCO CONECTE EL CABLE BLANCO NEGRO BLANCO NEGRO DEMORA DEL VENTILADOR NEGRO NEGRO NEGRO ROJO ELEMENTO 1 ELEMENTO 2 BLOQUE DE POTENCIA NEGRO AZUL LIMITE SUPERIOR VENTILADOR AMARILLO AMARILLO INSTALACION DEL RELE DE CONTROL 24R O R120 1 Instale en Relé de Control según se muestra en al Figura 4 NOTA Asegúrese que la lengüeta en la placa de control del relé esté bien enganchada en el orificio grand...

Страница 7: ...el transformador f Para TR7 solamente Conecte el cable MARRON 277V desde el transformador al terminal L2 del bloque de potencia 3 Para una operación de vuelta a cero nocturna refiérase al esquema eléctrico Figura 9 NOTA El relé de control debe activarse para la operación diurna EL VOLTAJE DEL TRANSFORMADOR DEBE CORRESPONDER CON EL VOLTAJE DEL CALENTADOR INDICADO EN LA PLACA DE NOMBRE DEL CALENTADO...

Страница 8: ...a mutuamente que tal reparación o reemplazo es el remedio exclusivo disponible de Marley Engineered Products LAS GARANTIAS INDICADAS ARRIBA SON A CAMBIO DE CUALQUIER OTRA GARANTIA EXPRESA O IMPLICITA Y SE DESCONOCENY EXCLUYEN DE ESTE ACUERDO TODAS LAS GARANTIAS IMPLICITAS DE COMERCIALIZACIONY APTI TUD PARA UN FIN PARTICULAR QUE EXCEDAN LAS GARANTIAS PREVIAMENTE EXPRESADAS MARLEY ELECTRICAL NO SERA...

Страница 9: ...lote 720 24R Relais de commande Bobine de Ampérage inductif 7 0 à 120 277 V alt Délais de fermeture de 45 à 60 s lorsqu il maintien de 24 V aPt Ampérage résistif 2 5 à 120 277 V alt est activé R12 Relais de commande Bobine de Ampérage inductif 7 0 à 120 277 V alt Délais de fermeture de 45 à 60 s lorsqu il maintien de 120 V aPt Ampérage résistif 2 4 à 120 277 V alt est activé DS Commutateur d alime...

Страница 10: ...terne en branchant deux fils de commande du site de la tension appro priée sur les deux fils ROUGES de la base de relais en utilisant deux connecteurs à écrou fournis 3 Pour l arrêt pendant la nuit voir le schéma de câblage figure 8 REMARQUE ELe relais de commande doit être alimenté pour le fonctionnement dans la journée APOUR ÉVITER DES RISQUES D ÉLECTROCUTION S ASSURER QUE L ÉLECTRICITÉ SOIT COU...

Страница 11: ...eur inutilisé f Pour le TR7 uniquement Brancher le fil MARRON 277 V du transformateur sur la borne L2 du bloc d ali mentation 3 Pour un fonctionnement avec arrêt de nuit voir le schéma de câblage figure 11 REMARQUE Le relais de commande doit être alimenté pour le fonctionnement de jour LA TENSION DU TRANSFORMATEUR DOIT CORRESPONDRE À LA TENSION DU RADIATEUR INDIQUÉE SUR LA PLAQUE SIGNALÉTIQUE DU R...

Страница 12: ...y Engineered Products LES GARANTIES CI DESSUS REMPLACENT TOUTES LES AUTRES GARANTIES EXPLICITES OU IMPLICITES ET TOUTES LES GARANTIES IMPLICITES DE COMMERCIABILITÉ ET D ADAPTATION À UN USAGE PARTICULIER QUI DÉPASSENT LES GARANTIES EXPLICITES DÉCRITES CI DESSUS SONT RÉFUTÉES PAR LA PRÉSENTE ET EXCLUES DE CET ACCORD MARLEY ENGINEERED PRODUCTS NE SERA PAS RESPONSABLE DES DOMMAGES CIRCON STANCIELS CAU...

Отзывы: