22
6.0 TROUBLE-SHOOTING
(Continued)
Door Interlock Switch
Malfunction of the cooker door interlock switch prevents timer indicator lights from turning on
and steam generator from operating when the timer dial is set. If steam does not enter the
compartment and the cooking indicator light fails to turn on with the door latch securely
engaged, the fault may be in the door interlock switch. Proceed as follows:
1. Turn off power to the cooker.
2. Disconnect wires to the door switch terminals.
3. Connect a
n ohmmeter between the terminals of the switch. The switch is marked “C” for
common, ‘NC’ for normally closed and “NO” for normally open.
4. Actuate the switch by closing the cooking compartment door. If a zero reading cannot
be obtained between the C and NO terminals, the switch is defective and must be
replaced.
5. Remove the ohmmeter and replace the leads on switch terminals.
Indicator Lights
If the cooker compartment functions correctly, with the single exception that the indicator light
fails to ligh
t during operation, the fault is a defective indicator light. A “burned out” or defective
light is verified by using an AC volt-meter at the leads, with input power on the selector switch in
the correct position for that timer, the timer set, and the door latches closed. If 240 volts is
present, the fault is in the indicator light and requires replacement. If 240 volts is not present,
the fault is in the wiring or control components (selector switch, timer or door switch).
Buzzer
If the buzzer does not sound at the termination of the operator-selected timer setting (timer dial
returned to “0 - Minute” position), the fault may be a defective buzzer. Buzzer operation is
verified using an AC volt-meter at buzzer coil connections with input power on and selector
switch and coinciding timer dial set at the “0 - Minute” position. If voltage is 240 volts, the fault
is in the buzzer, which must be replaced. If 240 volts is not present, the fault is in the wiring or
control components (timer or selector switch).
Wiring
Using an ohmmeter, wiring continuity between the connections shown on the wiring diagram is
readily verified. This is best done in stages, removing only those wires required for each
continuity check. As each lead is replaced, it should be checked for evidence of corrosion, and
cleaned if necessary. All leads must be tightly attached so as to provide a good electrical
connection.
Содержание MPS-3E
Страница 27: ...24 8 0 PARTS FIGURE 3 Exploded View ...
Страница 33: ...30 9 0 WIRING ...
Страница 34: ...31 9 0 WIRING Continued ...
Страница 35: ...32 9 0 WIRING Continued ...
Страница 36: ...33 9 0 WIRING Continued ...
Страница 37: ...34 9 0 WIRING Continued ...
Страница 38: ...35 9 0 WIRING Continued ...