Table for total pressure drop calculation
1
2
3
4
5
6
7
8
9
Number Flue
gas
Ø250mm
Number Air
Ø200mm
delta
pressure
component
Fluegas
delta
pressure
component
Air
Total
pressure
drop Fluegas
out [Pa]
(2*4)
Total
pressure
drop Air in
[Pa] (3*5)
Total
Pressure
Terminal In
[Pa]
Total
pressure
drop
F
air in [Pa]
(6 + 7 + 8)
1 Meter Pipe
Bend 90°
Bend 45°
Terminal:
Total delta pressure [Pa]
How to use the table:
- Column 1 : used material
- Column 2: total number of used material of column 1 for flue gas out
- Column 3: total number of used material of column 1 for air in
- Column 4: pressure drop from pressure drop table /component for flue gas components
- Column 5: pressure drop from pressure drop table /component for air components
Select the correct column for the selected boiler type
(850-11: 1,2 , 1020-13: 3,4)
- Column 6: total pressure drop flue gas: multiply column 2 *4
- Column 7: total pressure drop air: multiply column 3 *5
- Column 8: total pressure drop terminal
- Column 9: total pressure drop flue gas and air: column 6 + 7 + 8
- Finally add all together column 9
Total pressure drop must be lower than 500 Pa (Megaflex 850-11) and (Megaflex 1020-13).
If the combined inlet/outlet system exceeds the maximum allowed pressure, this will result in a decrease
of more than 5 % of heat capacity. This is not allowed.
All components must be obtained from M&G
A list of allowed articles of M&G with corresponding OEM nrs is given below and on the next page.
APPLIANCE TYPE
FLUEGAS OUTLET
SUPPLY AIR INLET
ROOF TERMINAL ALU 250
LEAF CATCHER ALU
ROOF TERMINAL ALU
250/250-250/350
EXPANDER
B23