![Mark MEGAFLEX Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/mark/megaflex/megaflex_technical-manual_1727449031.webp)
EN
31
USER MENU
Recommended
Min
Max
After factory
reset
1. HEATING
1. CH tempera-
ture/OTC set
1. CH setpoint
85
20
90/Technician
75
2. Outside temperature
for CH off
OFF
7
30
OFF
2. ECO set-
point reduction
50
0
50
50
3. Scheduler set 1. Enable/disable on
board scheduler
Enabled
Disabled
Enabled
Enabled
2. Scheduler set
ON
ON|OFF
ECO
ON
2. DOMESTIC
HOT WATER
1. DHW setpoint (Switch)
80
35
85
80
1. DHW setpoint (NTC sensor)
60
10
65
60
2. ECO setpoint reduction
20
0
50
20
3. Scheduler set 1. Enable/disable on
board scheduler
Enabled
Enabled
Enabled
Enabled
2. Scheduler set
ON
ON|OFF
ECO
ON
3. HOLIDAY
1. CH holiday setpoint
20
20
90/Technician
20
2. DHW holiday setpoint (Thermostated)
80
35
85
80
2. DHW holiday setpoint (NTC sensor)
60
10
65
60
4. MAINTENANCE 1. Service information
Service tel. set by Technician
2. Service due date
Date set by Technician
5. SETTINGS
1. Select language
English
English|Italian|German|Russian|Spanish
2. Select units
Celsius
Fahrenheit
Celsius
3. Set date
set date
4. Set time
24 hours
24 hours
12 hours
5. Restore factory settings
Reset to factory/check settings
6. CHIMNEY
SWEEPER
OFF
0
100
1. Boiler information
Real time boiler status
2. Lockout
history
Overview lockout
history
Status boiler at time of lock/block
TECHNICIAN MENU
Recom-
mended
Min
Max
After factory
reset
1. ADVANCED
CH SETTINGS
1. CH power set
1. Maximum power
100
0
100
100
2. Minimum power
0
0
100
0
2. CH
temperatures
1. Absolute max. temperature
90
20
90
80
Higher than 90 not allowed
2. CH maximum setpoint
85
20
Abs. max CH
temp.
75
3. CH minimum setpoint
20
20
70
40
4. CH setpoint hysteresis
5
2
10
3
3. OTC
parameters
1. Outside temp for max CH
-10
-34
10
-10
2. Outside temp for min CH
18
15
25
18
3. Outside temp for CH off
OFF
7
30
OFF
4. OTC setpoint table
OTC table
5. OTC curve
OTC curve
4. CH pump set-
tings
1. Post pump time
10
1
30
5
5. CH anticycling timer
3
0
15
6. CH request type
RT+SP/
OT
onlyOTC|RT
0-10Vdc %
| SP
RT+SP/OT