6.3 Water connection
6.3.1 Pump
The boiler does not have a built in CH-pump. Therefore a CH-pump must be mounted separately . Select
a pump that matches the hydraulic resistance of the boiler and the installation. The graph below shows
the resistance characteristics for the different boiler models.
For electrical connections see chapter 6.7.
6.3.2 Minimum flow
The minimum flows shown below must be guaranteed.
Input in kW
Flow [m3/h] @ delta
T 25 full load
Flow [m3/h] @ delta
T 30 Start=25%
Flow [m3/h] @ delta
T 30 part load
850-11
29,2
9,7
4,9
680-11
23,4
9,7
4,9
1020-13
35,1
11,9
5,8
850-13
29,2
11,9
5,8
6.3.3 Water-treatment
Before filling up the installation (old and new), the installation should be rinsed
thoroughly with clean water from the tap.There are some rinsing/cleaning products
listed below and it is recommended that these are used.