CLMD16 Configuration Guide___________________________________
40 CLMD16 Configuration Guide Rev.1.1
Step 1
:
Apply the desired momentary inputs to control this circuit to a “Logic Element”. Where “0” is Off
and “1” is On, configure the “Logic Output” in a manner to where if any input source is On the
“Logic Element’s Output” becomes active. This step is not necessary if only one control point is
necessary for the circuit. If only one control point is being used for this circuit place that control
input in the stead of “Logic Output 1”.
Step 2
:
Apply “Logic Output” to the “Counter Element”, Select “One Button Smooth Scroll” for the
“Counter Type” Set “Counter” parameters. The parameters depicted in this example are a
good choice for this circuit type however can be adjusted as desired.
Step 3
:
Apply “Logic Output” to a “Toggle Element”
Step 4
:
After setting the ECB “Type” to “PWM”, Apply both the “Toggle Output” and the “Counter
Element” to the ECB parameters. Ensure “Toggle Mode” is Off.