Turning On two Circuits with one Switch
In the following example there is a single freshwater pump
controlled by “Network Input” in a
vessel however the end user desires to add another pump but wishes to continue to use only
one switch to control both pumps. The first pump already has a control circuit. See the
following step to configure the second pump.
Step 1:
Find the original freshwater
pump’s control source, in this example it is “Network Input 5”.
Replicate the
“Input Signal” of the original pump’s “Input Signal” to the new secondary pump’s
“Input Signal”. The secondary pump is only desired to be controlled by the original Pump’s
ECB control, for this reason, the secondary pump ECB
’s “Manual Mode” will need to be
enabled. This dis-allows B
reaker #6’s direct control of the secondary pump by “Network Input
6”, but instead will allow for only control of Breaker #6 by the “Input Signal” selected (“Network
Input 5”). Turn “Toggle Mode” for Breaker #6 Off to ensure Breaker #6 will follow the state of
the original freshwater pump’s control.