Settings
LCD Display
Detail
Selection/Option Default
Output Voltage
O/P V Setting Nominal Voltage Selection
208/220/230/240V
230V
Input / Frequency
I/P F Setting Input frequency range selection
when UPS is in free run mode
±2%
±5%
±7%
±5%
Input / Bypass Voltage
I/P Bypass Set Input Voltage range selection
when bypass is available
±10%
+10/-15%
+15/-20%
+10/-15%
Free Run Mode
•
Bypass Enable /
Disable in Free run
Mode
Free Run Set UPS run in Free run mode
selection (unsynchronized)
ON / OFF
ON
Bypass
disable
Allows the UPS to go into bypass
mode when unsynchronized
Disable / Enable
Disable
High Efficiency Mode
HE Mode Set Allows the UPS to run in high
efficiency mode
ON / OFF
OFF
Manual Bypass Force
Manual
Bypass
Forces the UPS into bypass mode.
(For service only)
ON / OFF
OFF
Load Segment / Group
Management
Outlet Setting
Allows load group/segments to be
turned on and off from the front
panel
1 ON & 2 ON
1 OFF & 2 ON
1 OFF & 2 OFF
1 ON & 2 OFF
ON &
ON
Initiate Battery Test
Battery Test
Detects whether battery is in good
condition or not.
Alarm Silence
Silence Set
Enables or disables alarm
silencing
ON/OFF
OFF
External Battery Pack
Quantity
Bat Cabinet
Set
Allows the UPS to more accurately
determine remaining backup time
1
2
3
4
5
1
Site Wiring Fault Alarm
Sit Fault Set
Enables or disables site wiring
fault alarm
Enable /Disable
Disable
Language
Language
Selects load language
English, German,
French, Spanish, Italian English
Generator Mode
•
Bypass Enable /
Disable in Free run
Mode
Generator
Places UPS in generator mode *** ON / OFF
OFF
Bypass
disable
Allows the UPS to go into bypass
mode when unsynchronized
Disable / Enable
Disable
RS-232 communication
RS232 Control Enables or disables RS-232
communication capability
Enable / Disable
ENABLE
7.5 Manual UPS or Battery Test
A manual UPS or battery test can be initiated from the UPS configuration/settings display and
can be carried out even when the UPS is not charging the battery. To initiate, scroll through the
parameters until Manual Bat test is displayed on the LCD panel. Press the Enter push-button
twice.
** NOTE: In order for the UPS and power management software to function correctly, Manual
Bypass should always be set to OFF as the load will not be protected by the UPS when Manual
Bypass is ON.
*** NOTE: The UPS should be turned off but kept connected to the AC power supply before
activating the Generator Mode.