background image

Settings 

  LCD Display 

Detail 

 Selection/Option Default 

 Output Voltage 

 O/P V Setting   Nominal Voltage Selection 

 208/220/230/240V 

 230V 

 Input / Frequency 

 I/P F Setting   Input frequency range selection  

when UPS is in free run mode 

±2% 

±5% 

±7% 

 ±5% 

Input / Bypass Voltage 

 I/P Bypass Set  Input Voltage range selection  

when bypass is available 

±10% 

+10/-15% 

+15/-20% 

+10/-15% 

Free Run Mode 

 

  Bypass Enable / 

Disable in Free run 

Mode 

Free Run Set  UPS run in Free run mode  

selection (unsynchronized) 

 ON / OFF 

 ON 

Bypass  

disable 

Allows the UPS to go into bypass  

mode when unsynchronized 

Disable / Enable 

Disable 

High Efficiency Mode 

HE Mode Set  Allows the UPS to run in high  

efficiency mode 

ON / OFF 

OFF 

 Manual Bypass Force 

Manual  

Bypass 

Forces the UPS into bypass mode.  

(For service only) 

 ON / OFF 

 OFF 

 Load Segment / Group  

Management 

 Outlet Setting 

 Allows load group/segments to be  

turned on and off from the front  

panel 

1 ON & 2 ON 

1 OFF & 2 ON 

1 OFF & 2 OFF 

1 ON & 2 OFF 

 

ON & 

ON 

Initiate Battery Test 

Battery Test 

Detects whether battery is in good  

condition or not. 

 

 

Alarm Silence 

Silence Set 

Enables or disables alarm  

silencing 

ON/OFF 

OFF 

 

External Battery Pack  

Quantity 

 

Bat Cabinet  

Set 

 

Allows the UPS to more accurately  

determine remaining backup time 

 

Site Wiring Fault Alarm 

Sit Fault Set 

Enables or disables site wiring  

fault alarm 

Enable /Disable 

Disable 

Language 

Language 

Selects load language 

English, German,  

French, Spanish, Italian  English 

Generator Mode 

 

  Bypass Enable / 

Disable in Free run 

Mode 

Generator 

Places UPS in generator mode ***  ON / OFF 

OFF 

Bypass  

disable 

Allows the UPS to go into bypass  

mode when unsynchronized 

Disable / Enable 

Disable 

RS-232 communication 

RS232 Control  Enables or disables RS-232  

communication capability 

Enable / Disable 

ENABLE 

 

 

7.5 Manual UPS or Battery Test

 

A manual UPS or battery test can be initiated from the UPS configuration/settings display and 

can be carried out even when the UPS is not charging the battery. To initiate, scroll through the 

parameters until Manual Bat test is displayed on the LCD panel. Press the Enter push-button 

twice.

 

** NOTE: In order for the UPS and power management software to function correctly, Manual 

Bypass should always be set to OFF as the load will not be protected by the UPS when Manual 

Bypass is ON.

 

*** NOTE: The UPS should be turned off but kept connected to the AC power supply before 

activating the Generator Mode.

 

 

 

Содержание vault series

Страница 1: ...9DXOW 6HULHV 7UXH 2Q LQH RXEOH RQYHUVLRQ 8QLQWHUUXSWLEOH 3RZHU 6XSSO 86 5 0 18 25 02 6 9 9...

Страница 2: ...2...

Страница 3: ...kVARear Panel Views 21 5 4 Connecting an Extended Run Time battery Pack 22 5 5 Factory Default Settings 22 6 Communication Interface andAlarm Connections 22 6 1 Overview 22 6 2 Connecting the UPS to a...

Страница 4: ...KH HTXLSPHQW LW LV UHFRPPHQGHG WR XVH RQH RI WKH IROORZLQJ SUHYHQWLYH PHDVXUHV 3ODFH WKH UHFHLYLQJ DQWHQQD LQ D VHSDUDWH ORFDWLRQ RU RULHQWDWLRQ QVXUH D JUHDWHU GLVWDQFH LV DFKLHYHG EHWZHHQ WKH UHFHLY...

Страница 5: ...electrolyte may be released which is harmful to the skin and eyes 8 CAUTION A battery can present a risk of electric shock and high short circuit current The following precautions should be taken whe...

Страница 6: ...G LQWR LW 6326 QGLFDWHV WKDW WKH 836 DQG LWV EDWWHULHV VKRXOG EH GLVSRVHG RI LQ WKH FRUUHFW PDQQHU VLQFH WKH EDWWHULHV DUH RI WKH OHDG DFLG W SH W LV UHFRPPHQGHG WKDW WKH EDWWHULHV EH UHF FOHG 87 21 7...

Страница 7: ...H HYHQW WKDW D SRZHU LQWHUUXSWLRQ ODVWV ORQJHU WKDQ WKH 836 V EDFNXS WLPH FDSDELOLW LW ZLOO VKXW GRZQ WR DYRLG FRPSOHWH EDWWHU GLVFKDUJH V VRRQ DV SRZHU LV UHVWRUHG WKH 836 ZLOO DXWRPDWLFDOO UHVWDUW D...

Страница 8: ...WH E SDVV PRGH ZKLOH WKH 836 LV LQ IUHH UXQ PRGH LDJQRVWLF WHVWV KHQHYHU WKH 836 LV WXUQHG RQ D GLDJQRVWLF WHVW WR FKHFN WKH VWDWXV RI WKH LQWHUQDO HOHFWURQLFV DQG EDWWHU LV DFWLYDWHG Q HUURUV RU IDXO...

Страница 9: ...install the UPS safely and correctly Please read it thoroughly and keep this manual for future reference User Allowable Operations The only UPS related operations that the user is allowed to perform...

Страница 10: ...rdous situation and damage to the UPS and or loads Various input and sometimes output cables are supplied with all models 1 Ensure that the UPS is disconnected from the AC supply when connecting Exter...

Страница 11: ...the output of the UPS will shut down immediately Note Local safety requirements may require a separate external Emergency Power Off that opens output circuit breakers Refer to local wiring regulation...

Страница 12: ...L N PE Bypass Input Rectifier Input EPO Circuit Breaker Input Output PFC Booster Inverter Battery Static Bypass L1 N1 PE L N PE L2 N2 PE L1 N1 PE J L2 N2 PE L N PE EPO Input PFC Booster Battery Invert...

Страница 13: ...OODWLRQ DOO 0RXQW QVWDOODWLRQ 9HUWLFDO DQG DOO 0RXQW QVWDOODWLRQ 7KH IROORZLQJ GLDJUDPV LOOXVWUDWH KRZ WR LQVWDOO RU PRXQW WKH 836 DQG EDWWHU SDFNV ZKHQ DSSOLFDEOH LQ HLWKHU YHUWLFDO RU ZDOO PRXQW DSS...

Страница 14: ...ZHU 6LGH 5DLO QVWDOODWLRQ 5HDU UDFNHW QVWDOODWLRQ 5DFN 0RXQW QVWDOODWLRQ 7KH IROORZLQJ GLDJUDPV LOOXVWUDWH KRZ WR LQVWDOO RU PRXQW WKH 836 DQG EDWWHU SDFNV ZKHQ DSSOLFDEOH LQ UDFN PRXQW DSSOLFDWLRQV 1...

Страница 15: ...6WDFN QVWDOODWLRQ 8QLW 6WDFN QVWDOODWLRQ 7KH IROORZLQJ GLDJUDPV LOOXVWUDWH KRZ WR VWDFN WKH XQLWV DQG EDWWHU SDFNV ZKHQ DSSOLFDEOH 15...

Страница 16: ...9LHZV D 7RZHU 0RGHOV N N9 5HDU 3DQHO 9LHZV 97 5HDU 9LHZ RU 97 5HDU 9LHZ RU LIIHUHQW RXWSXW UHFHSWDFOH RSWLRQV DYDLODEOH N9 5 5 3 1 9 7 SH 5HDU 9LHZ N9 5 5 3 1 9 7 SH 5HDU 9LHZ N9 5 5 3 1 9 1 0 7 SH 5...

Страница 17: ...E 7RZHU 0RGHOV N9 5HDU 3DQHO 9LHZV 97 5HDU 9LHZ RU LIIHUHQW RXWSXW UHFHSWDFOH RSWLRQV DYDLODEOH N9 5 5 3 1 ZLWKRXW 62 5HDU 9LHZ N9 5 5 3 1 ZLWK 62 5HDU 9LHZ 17...

Страница 18: ...F 7RZHU 0RGHOV N N9 5HDU 3DQHO 9LHZV N9 5 5 3 1 ZLWK 62 5HDU 9LHZ N9 5 5 3 1 ZLWKRXW 62 5HDU 9LHZ 97 5HDU 9LHZ RU 97 5HDU 9LHZ RU LIIHUHQW RXWSXW UHFHSWDFOH RSWLRQV DYDLODEOH 18...

Страница 19: ...G 7RZHU 0RGHOV N9 5HDU 3DQHO 9LHZV 9 5 5 3 1 ZLWK RU ZLWKRXW 62 5HDU 9LHZ 97 5HDU 9LHZ LIIHUHQW RXWSXW UHFHSWDFOH RSWLRQV DYDLODEOH 19...

Страница 20: ...H 7RZHU 0RGHOV N N9 5HDU 3DQHO 9LHZV 97 5HDU 9LHZ 97 5HDU 9LHZ LIIHUHQW RXWSXW UHFHSWDFOH RSWLRQV DYDLODEOH 9 5 5 3 1 ZLWK RU ZLWKRXW 62 5HDU 9LHZ 20...

Страница 21: ...DU 3DQHO 9LHZV 9 5 5 3 1 5HDU 9LHZ 9 5 5 3 1 5HDU 9LHZ 9 5 5 3 1 5HDU 9LHZ 5DFN 0RXQW DWWHU 3DFN 5HDU 9LHZ 237 21 237 21 957 5HDU 9LHZ 957 5HDU 9LHZ 957 5HDU 9LHZ 957 5HDU 9LHZ 957 5HDU 9LHZ 957 5HDU...

Страница 22: ...WD LQWHUIDFH DQG DQ 32 PHUJHQF 3RZHU 2II FRQQHFWRU 127 7KH 56 SRUW FDQQRW EH XVHG ZKHQ WKH 86 LQWHUIDFH LV LQ XVH 7KHUH LV DOVR DQ RSWLRQDO LQWHUIDFH VORW WKDW DOORZV IRU WKH LQVWDOODWLRQ RI DGGLWLRQD...

Страница 23: ...nnecting and removing power from the UPS output Any manual or automatic shutdown procedures including those directed by power management software are overridden To activate make sure the UPS and loads...

Страница 24: ...QG RII 7R LQLWLDWH D VWDUW XS RU VKXW GRZQ SUHVV DQG KROG WKLV SXVK EXWWRQ IRU VHFRQGV 67 786 7KLV SXVK EXWWRQ LV XVHG WR FKHFN FXUUHQW 836 DQG ORDG VHWWLQJV LQIRUPDWLRQ DQG SRZHU PHDVXUHPHQWV 7R DFWL...

Страница 25: ...LQ QRUPDO RU VWDWLF E SDVV PRGH DQG YROWDJH LV SUHVHQW DW WKH RXWSXW WHUPLQDOV 7KLV V PERO LV DFFRPSDQLHG E D HOORZ WKDW LOOXPLQDWHV ZKHQ WKH 836 LV RSHUDWLQJ LQ EDWWHU PRGH 7KLV V PERO LV DFFRPSDQLHG...

Страница 26: ...AT CHARG xx Approximate Battery capacity expressed as a percentage TEMPERATURE xx C Approximate ambient temperature BAT PACK NUM x External Battery Pack quantity RATING xxxx VA U UPS Rating CPU VERSIO...

Страница 27: ...ng ON OFF OFF External Battery Pack Quantity Bat Cabinet Set Allows the UPS to more accurately determine remaining backup time 1 2 3 4 5 1 Site Wiring Fault Alarm Sit Fault Set Enables or disables sit...

Страница 28: ...enerator or a noisy line The factory default setting is normal where the unit runs on normal parameters Switching to Generator makes it run on noisy generator parameters If the unit constantly switche...

Страница 29: ...PHQW LPPHGLDWHO 7KH 836 ZLOO UHVWDUW DXWRPDWLFDOO RQFH SRZHU KDV EHHQ UHVWRUHG 1R DFWLRQ UHTXLUHG FRQWUROOHG VKXWGRZQ RI FRQQHFWHG HTXLSPHQW FDQ EH LQLWLDWHG LI QHFHVVDU 7XUQ RII SURWHFWHG ORDGV WKHQ...

Страница 30: ...ent 2 Once the covers have been removed and placed out of the way disconnect the positive RED and negative BLACK bus wires from the battery string then the interconnecting cable between each battery 3...

Страница 31: ...UHTXHQF UHJXODWLRQ ZKLOH RQ EDWWHU RU LQ IUHH UXQ PRGH QDPLF UHVSRQVH PD IURP WR RU IURP WR OLQHDU ORDG 2YHUORDG FDSDFLW IRU PLQ IRU VHF I FLHQF 0RGH UHDWHU WKDQ I FLHQF 2Q OLQH 0RGH UHDWHU WKDQ UHVW...

Страница 32: ...d 9Ah 12V PLQ 6HDOHG OHDG DFLG K 9 PLQ 5 PLQ 7RZHU 0RGHOV DUGZLUH 7HUPLQDO ORFN DUGZLUH 7HUPLQDO ORFN DQG RU YDULRXV UHFHSWDFOHV DUGZLUH 7HUPLQDO ORFN DQG RU YDULRXV 1 0 UHFHSWDFOHV DUGZLUH 7HUPLQDO O...

Страница 33: ...OHDG DFLG K 9 PLQ 5 PLQ DUGZLUH 7HUPLQDO ORFN DUGZLUH 7HUPLQDO ORFN DQG RU YDULRXV UHFHSWDFOHV DUGZLUH 7HUPLQDO ORFN DQG RU YDULRXV 1 0 UHFHSWDFOHV DUGZLUH 7HUPLQDO ORFN DQG RU YDULRXV XURSHDQ UHFHSWD...

Страница 34: ...V DUH LQWHQGHG WR OLPLW WKH PD LPXP DPSOLWXGH RI WUDQVLHQW YROWDJH VXUJHV RQ SRZHU OLQHV WR VSHFL HG YDOXHV 7KH DUH QRW LQWHQGHG WR IXQFWLRQ DV VXUJH DUUHVWRUV 7KH 836 LV LQWHQGHG WR EH LQVWDOOHG RQ W...

Страница 35: ...35...

Страница 36: ...ult 4k 20k User Man_Oct_2019 Marathon Power Inc 2019 Marathon Power Inc 2019 2538 E 54th Street Huntington Park CA Office 310 689 2328 Fax 310 689 2329 support marathon power com www marathon power co...

Отзывы: