Table 1
Additional Installation Information (for 6000VA ~ 20000VA Models)
1.
Ensure that all electrical connections have been correctly implemented for the installation site
out.
2.
Refer to Table 2 for input and output breaker rating.
3.
Isolate and prevent the source from activating. Both input and output circuit breakers (located
on
the rear of the unit) must be in the "OFF" position.
4.
Refer to figure 2 for single cable input connection and figure 3 for dual cable input connection.
If
installing dual cables, the interconnection jumper (J) shown in figure 2 needs to be removed.
5.
If during installation, it cannot be determined that the neutral is grounded or identification
of
the status of the neutral in the AC supply is unreliable, an additional two pole disconnect
device
may be necessary in the for the installation.
6.
Should the optional Emergency Power Off (EPO) circuit on the rear on the unit be used, the
output of the UPS will shut down immediately
.
Note:
Local safety requirements may require a separate external Emergency Power Off that
opens output circuit breakers. Refer to local wiring regulations.
Table 2
Wire size
6-8 AWG
Wire Stripping length
8 mm
Minimum temperature
60
℃
Wire conductor material
Copper only
Screw Torque
18 lb.-in
VGD 4K-12K, Tower UPS:
UPS Model
Input Breaker Rating Output Breaker Rating
Battery Breaker Rating
4KVA
1P, 277Vac, 20A
1P,125/250VAC,16A 1P,125/250VAC,10A NA
5KVA (bat*10)
1P, 250Vac, 30A
1P,125/250VAC,16A 1P,125/250VAC,10A NA
5KVA (bat*20)
2P, 250Vac, 30A
2P, 250Vac, 30A
NA
6KVA
2P, 250Vac, 30A
2P, 250Vac, 30A
NA
8KVA
2P, 250Vac, 63A
NA
2P, 250Vac, 63A
10KVA
2P, 250Vac, 63A
NA
2P, 250Vac, 63A
12KVA
2P, 250Vac, 63A
NA
2P, 250Vac, 63A
VRM 4K-12K, Rack Mount UPS:
UPS Model
Input Breaker Rating Output Breaker Rating
Battery Breaker Rating
4KVA
1P, 277Vac, 20A
NA
NA
5KVA (bat*10)
1P, 250Vac, 30A
NA
NA
5KVA (bat*20)
2P, 250Vac, 30A
2P, 250Vac, 30A
NA
6KVA
2P, 250Vac, 30A
2P, 250Vac, 30A
NA
8KVA
1P, 250Vac, 65A
1P, 250Vac, 65A
NA
10KVA
1P, 250Vac, 65A
1P, 250Vac, 65A
NA
12KVA
1P, 250Vac, 65A
1P, 250Vac, 65A
NA
11