Over Excitation Protection
Threshold:
0.500 to 4.000 Adc
Timer:
1.0 to 15.0 seconds
Under Excitation Protection
Threshold:
-100.0% to -5.0% of rated
kVAR
Timer:
1.0 to 15.0 seconds
Field Current Limit
Threshold:
0.500 to 6.500 Adc
Power Limit
Threshold:
5.0 to 115.0 % of rated kW
Field Instantaneous Over Current Protection
Threshold:
11 Adc
Generator Over Voltage Protection
Threshold:
5.0 to 20.0 % of voltage
set point
Timer:
0.1 to 15.0 seconds
Generator Under Voltage Protection
Threshold:
5.0 to 50.0 % of voltage
set point
Timer:
1.0 to 15.0 seconds
Generator Reverse Power Protection
Threshold:
5.0 to 100.0 % of rated kW
Timer:
1.0 to 15.0 seconds
Soft-Start Function
Range:
2 to 120 seconds
Auxiliary Input
Auxiliary – Control1 Mode (AVR3, AVR1, VAR or
PF regulation)
Voltage Range:
-3 Vdc to +3 Vdc
Set Point Range:
-X to +X % shift where
X = 1.0 to 30.0
Burden:
2260 Ω
Terminals:
J1-1 (+), J1-12 (-)
Auxiliary – Control1 Mode (FCR regulation)
Voltage Range:
-3 Vdc to +3 Vdc
Set Point Range:
-3.000 Adc to + 3.000 Adc
Increment: 1 mA per 1mV
Burden:
2260 Ω
Terminal:
J1-1 (+), J1-12 (-)
Auxiliary – Control2 Mode (AVR3, AVR1, VAR or
PF regulation)
Current Range
4 mA to 20 mA
Set Point Range:
-X to +X % shift where X =
1.0 to 30.0
Burden:
250 Ω
Terminals:
J1-1 (+), J1-12 (-)
Jumper:
J1-5 to J1-8
Auxiliary – Control2 Mode (FCR regulation)
Current Range
4 mA to 20 mA
Set Point Range:
-3.000 Adc to + 3.000 Adc
Increment:
1 mA per 2.67 uA
Burden:
250 Ω
Terminal:
J1-1 (+), J1-12 (-)
Jumper:
J1-5 to J1-8
Auxiliary – Meter (Voltage input)
Voltage Range:
-5 Vdc to 5 Vdc
Scale Factor:
User-defined
Burden:
2260 Ω
Terminal:
J1-1 (+), J1-12 (-)
Auxiliary – Meter (Current input)
Current Range:
4 mA to 20 mA
Scale Factor:
User-defined
Burden:
250 Ω
Terminal:
J1-1 (+), J1-12 (-)
Jumper:
J1-5 to J1-8
Metering
Accuracy of all metering values assumes 25° C,
50/60 Hz and less than 20 % THD.
Regulator-side Metering
Generator Voltage
Range:
10 Vac to 600 Vac
Accuracy:
0.5 %
Generator Current
Range:
0.1 to 5.000 Aac (5 Aac CTs)
Accuracy:
0.5 %
Specifications
GPN046 04-13.indd 6
4/5/13 10:24 AM
Содержание DVR 2000E+
Страница 1: ...DVR 2000E EC User Manual A Regal Brand...
Страница 21: ...19 5 Installation Figure 5 2 DVR Rear dimensions with cover Valid for E EC versions...
Страница 22: ...20 5 Installation Figure 5 3 Cutout and Drilling Dimensions...
Страница 57: ...55 8 Maintenance and Troubleshooting...
Страница 58: ...56 8 Maintenance and Troubleshooting...
Страница 60: ...58 8 Maintenance and Troubleshooting...
Страница 61: ...59 8 Maintenance and Troubleshooting...
Страница 62: ...60 8 Maintenance and Troubleshooting...
Страница 69: ...67 Notes...
Страница 70: ...68 Notes...
Страница 71: ......