36
6
Human-Machine Interface (HMI)
Parameter Name Parameter Value
Description
SIZE
281 to 1040
Frame size of generator
REG
AVR3
AVR3 – Voltage regulator with three-phase sensing
AVR1
AVR1 – Voltage regulator with single-phase sensing
FCR
FCR – Field current regulator
VAR
VAR – Reactive VAR regulation (EC+ only)
PF
PF – Power Factor regulation (EC+ only)
STPT
100.0 to 630.0
Voltage set point (Vrms) in AVR3 and AVR1 mode
0.000 to 3.000
Field current set point (Adc) in FCR mode
0.0% to 10.0%
VAR set point (% of rated VAR) in VAR mode. (EC+ only)
0.000 to 0.999
PF set point (PU) in PF mode (EC+ only)
UFRQ
40.0H to 70.0H
Under frequency knee (Hz)
DROP
0.0% to 10.0%
Voltage droop (%) at rated reactive power
AU
OFF
Auxiliary Off – Auxiliary input is disabled
CNT1
Auxiliary Control-1 – Auxiliary input modifies regulation set point
(-3 to +3 Vdc input)
SCLF
Auxiliary Meter – Auxiliary input is used as a meter with user-defined
scale factor
CNT2
Auxiliary Control-2 – Auxiliary input modifies regulation set point
(4 to 20 mA input)
Table 6-3. DVR
®
HMI
EDIT
Mode Parameters
GPN046 04-13.indd 36
4/5/13 10:24 AM
Содержание DVR 2000E+
Страница 1: ...DVR 2000E EC User Manual A Regal Brand...
Страница 21: ...19 5 Installation Figure 5 2 DVR Rear dimensions with cover Valid for E EC versions...
Страница 22: ...20 5 Installation Figure 5 3 Cutout and Drilling Dimensions...
Страница 57: ...55 8 Maintenance and Troubleshooting...
Страница 58: ...56 8 Maintenance and Troubleshooting...
Страница 60: ...58 8 Maintenance and Troubleshooting...
Страница 61: ...59 8 Maintenance and Troubleshooting...
Страница 62: ...60 8 Maintenance and Troubleshooting...
Страница 69: ...67 Notes...
Страница 70: ...68 Notes...
Страница 71: ......